Emotron FDU40-003 User manual

Emotron FDU 2.0
Variable Speed Drive
Instruction manual
English

Variable speed drive FDU 2.0
INSTRUCTION MANUAL - ENGLISH
Software version 4.0x
Document number: 01-3694-01
Edition: r2
Date of release: 01-04-2007
© Copyright Emotron AB 2005 - 2007
Emotron retains the right to change specifications and illustrations in the
text, without prior notification. The contents of this document may not
be copied without the explicit permission of Emotron AB.


Emotron AB 01-3694-01r2 1
Safety Instructions
Instruction manual
Read the instruction manual first!
Handling the variable speed drive
Installation, commissioning, demounting, taking measure-
ments, etc, of or on the variable speed drive may only be car-
ried out by personnel technically qualified for the task. The
installation must be carried out in accordance with local
standards.
Opening the variable speed drive
Always take adequate precautions before opening the varia-
ble speed drive. Although the connections for the control
signals and the switches are isolated from the main voltage,
do not touch the control board when the variable speed
drive is switched on.
Precautions to be taken with a
connected motor
If work must be carried out on a connected motor or on the
driven machine, the mains voltage must always be discon-
nected from the variable speed drive first. Wait at least 5
minutes before starting work.
Earthing
The variable speed drive must always be earthed via the
mains safety earth connection.
Earth leakage current
This VSD has an earth leakage current which does exceeding
3.5 mA a.c. or 10 mA d.c. Therefore the minimum size of
the protective earth conductor must comply with the local
safety regulations for high leakage current equipment.
Residual current device (RCD)
compatibility
This product cause a d.c. current in the protective conduc-
tor. Where a residual current device (RCD) is used for pro-
tection in case of direct or indirect contact, only a Type B
RCD is allowed on the supply side of this product. Use
RCD of 300 mA minimum.
EMC Regulations
In order to comply with the EMC Directive, it is absolutely
necessary to follow the installation instructions. All installa-
tion descriptions in this manual follow the EMC Directive.
Mains voltage selection
The variable speed drive is suitable for use with the mains
voltage listed below. Adjustment of the mains voltage is not
necessary!
380-415 V
380-480 V
440-525 V
500-690 V
Voltage tests (Megger)
Do not carry out voltage tests (Megger) on the motor, before
all the motor cables have been disconnected from the varia-
ble speed drive.
Condensation
If the variable speed drive is moved from a cold (storage)
room to a room where it will be installed, condensation can
occur. This can result in sensitive components becoming
damp. Do not connect the mains voltage until all visible
dampness has evaporated.
Incorrect connection
The variable speed drive is not protected against incorrect
connection of the mains voltage, and in particular against
connection of the mains voltage to the motor outlets U, V
and W. The variable speed drive can be damaged in this way.
Power factor capacitors for improving
cosϕ
Remove all capacitors from the motor and the motor outlet.
Precautions during Autoreset
When the automatic reset is active, the motor will restart
automatically provided that the cause of the trip has been
removed. If necessary take the appropriate precautions.
Transport
To avoid damage, keep the variable speed drive in its original
packaging during transport. This packaging is specially
designed to absorb shocks during transport.
WARNING: Always switch off the mains voltage
before opening the variable speed drive and
wait at least 5 minutes to allow the buffer
capacitors to discharge.

2Emotron AB 01-3694-01r2
IT Mains supply
The variable speed drives can easily be connected to an IT
mains supply, (non-earthed neutral), please contact your
supplier for details.
Heat warning
DC-link residual voltage
Be aware of specific parts on the VSD having
high temperature.
WARNING: After switching off the mains
supply, dangerous voltage can still be present
in the VSD. When opening the VSD for
installing and/or commissioning activities wait
at least 5 minutes. In case of malfunction a qualified
technician should check the DC-link or wait for one hour
before dismantling the VSD for repair.

Emotron AB 01-3694-01r2 3
Contents
1. Introduction..................................................... 5
1.1 Delivery and unpacking ............................................ 5
1.2 Using of the instruction manual............................... 5
1.3 Type number.............................................................. 5
1.4 Standards .................................................................. 6
1.4.1 Product standard for EMC ........................................ 6
1.5 Dismantling and scrapping....................................... 7
1.5.1 Disposal of old electrical and electronic
equipment ................................................................. 7
1.6 Glossary ..................................................................... 8
1.6.1 Abbreviations and symbols....................................... 8
1.6.2 Definitions.................................................................. 8
2. Mounting ......................................................... 9
2.1 Lifting instructions..................................................... 9
2.2 Stand-alone units .................................................... 10
2.2.1 Cooling ..................................................................... 10
2.2.2 Mounting schemes.................................................. 11
2.3 Cabinet mounting.................................................... 13
2.3.1 Cooling ..................................................................... 13
2.3.2 Mounting schemes.................................................. 13
3. Installation ................................................... 17
3.1 Before installation................................................... 17
3.2 Cable connections................................................... 17
3.2.1 Motor cables............................................................ 17
3.2.2 Mains cables ........................................................... 19
3.3 Cable specifications................................................ 19
3.4 Stripping lengths ..................................................... 19
3.4.1 Dimension of cables and fuses.............................. 20
3.4.2 Tightening torque for mains and motor cables..... 20
3.5 Connect motor and mains cables .......................... 20
3.6 Thermal protection on the motor ........................... 21
3.7 Motors in parallel .................................................... 21
4. Control Connections.................................... 23
4.1 Control board........................................................... 23
4.2 Terminal connections ............................................. 24
4.3 Connection example ............................................... 25
4.4 Inputs configuration with the switches.................. 26
4.5 Connecting the Control Signals.............................. 26
4.5.1 Cables ...................................................................... 26
4.5.2 Types of control signals .......................................... 27
4.5.3 Screening................................................................. 27
4.5.4 Single-ended or double-ended connection? ......... 27
4.5.5 Current signals ((0)4-20 mA).................................. 28
4.5.6 Twisted cables......................................................... 28
4.6 Connecting options ................................................. 28
5. Getting Started ............................................ 29
5.1 Connect the mains and motor cables.................... 29
5.1.1 Mains cables ........................................................... 29
5.1.2 Motor cables............................................................ 29
5.2 Connect control cables ........................................... 29
5.3 Using the function keys .......................................... 30
5.4 Remote control........................................................ 30
5.4.1 Switch on the mains ............................................... 30
5.4.2 Set the Motor Data.................................................. 30
5.4.3 Run the VSD ............................................................ 30
5.5 Local control............................................................ 31
5.5.1 Switch on the mains ............................................... 31
5.5.2 Select manual control............................................. 31
5.5.3 Set the Motor Data.................................................. 31
5.5.4 Enter a Reference Value......................................... 31
5.5.5 Run the VSD ............................................................ 31
6. Applications.................................................. 33
6.1 Application overview ............................................... 33
6.1.1 Pumps...................................................................... 33
6.1.2 Fans ......................................................................... 33
6.1.3 Compressors ........................................................... 34
6.1.4 Blowers .................................................................... 34
7. Main Features .............................................. 35
7.1 Parameter sets........................................................ 35
7.1.1 One motor and one parameter set ........................ 36
7.1.2 One motor and two parameter sets....................... 36
7.1.3 Two motors and two parameter sets..................... 36
7.1.4 Autoreset at trip ...................................................... 36
7.1.5 Reference priority.................................................... 36
7.1.6 Preset references.................................................... 37
7.2 Remote control functions ....................................... 37
7.3 Performing an Identification Run........................... 39
7.4 Using the Control Panel Memory............................ 40
7.5 Load Monitor and Process Protection [400]......... 40
7.5.1 Load Monitor [410]................................................. 40
7.6 Pump function ......................................................... 42
7.6.1 Introduction ............................................................. 42
7.6.2 Fixed MASTER ......................................................... 43
7.6.3 Alternating MASTER ................................................ 43
7.6.4 Feedback 'Status' input .......................................... 43
7.6.5 Fail safe operation .................................................. 44
7.6.6 PID control ............................................................... 45
7.6.7 Wiring Alternating Master....................................... 46
7.6.8 Checklist And Tips................................................... 47
7.6.9 Functional Examples of Start/Stop Transitions .... 48
8. EMC and Machine Directive........................ 51
8.1 EMC standards........................................................ 51
8.2 Stop categories and emergency stop .................... 51
9. Operation via the Control Panel.................. 53
9.1 General .................................................................... 53
9.2 The control panel .................................................... 53
9.2.1 The display............................................................... 53
9.2.2 Indications on the display....................................... 54
9.2.3 LED indicators ......................................................... 54
9.2.4 Control keys............................................................. 54

4Emotron AB 01-3694-01r2
9.2.5 The Toggle and Loc/Rem Key ................................ 54
9.2.6 Function keys .......................................................... 55
9.3 The menu structure................................................. 56
9.3.1 The main menu ....................................................... 56
9.4 Programming during operation .............................. 56
9.5 Editing values in a menu ........................................ 56
9.6 Programming example............................................ 57
10. Serial communication ................................. 59
10.1 Parameter sets........................................................ 59
10.2 Motor data ............................................................... 59
10.3 Start and stop commands ...................................... 60
10.4 Reference signal ..................................................... 60
10.5 Description of the EInt formats .............................. 60
11. Functional Description................................ 63
11.1 Resolution of settings ............................................. 63
11.2 Preferred View [100]............................................... 63
11.2.1 1st Line [110].......................................................... 63
11.2.2 2nd Line [120] ........................................................ 63
11.3 Main Setup [200].................................................... 64
11.3.1 Operation [210]....................................................... 64
11.3.2 Remote Signal Level/Edge [21A]........................... 66
11.3.3 Motor Data [220] .................................................... 67
11.3.4 Motor Protection [230] ........................................... 71
11.3.5 Parameter Set Handling [240]............................... 73
11.3.6 Trip Autoreset/Trip Conditions [250]..................... 75
11.3.7 Serial Communication [260] .................................. 81
11.4 Process and Application Parameters [300] .......... 83
11.4.1 Set/View Reference Value [310] ........................... 83
11.4.2 Process Settings [320] ........................................... 83
11.4.3 Start/Stop settings [330] ....................................... 87
11.4.4 Mechanical brake control....................................... 90
11.4.5 Speed [340]............................................................. 92
11.4.6 Torques [350].......................................................... 94
11.4.7 Preset References [360] ........................................ 96
11.4.8 PID Process Control [380] ...................................... 97
11.4.9 Pump/Fan Control [390] ...................................... 100
11.5 Load Monitor and Process Protection [400]....... 106
11.5.1 Load Monitor [410]............................................... 106
11.5.2 Process Protection [420]...................................... 111
11.6 I/Os and Virtual Connections [500]..................... 112
11.6.1 Analogue Inputs [510].......................................... 112
11.6.2 Digital Inputs [520] ............................................... 118
11.6.3 Analogue Outputs [530] ....................................... 119
11.6.4 Digital Outputs [540] ............................................ 123
11.6.5 Relays [550] .......................................................... 124
11.6.6 Virtual Connections [560]..................................... 125
11.7 Logical Functions and Timers [600] .................... 126
11.7.1 Comparators [610] ............................................... 126
11.7.2 Logic Output Y [620]............................................. 130
11.7.3 Logic Output Z [630]............................................. 132
11.7.4 Timer1 [640] ......................................................... 133
11.7.5 Timer2 [650] ......................................................... 135
11.8 View Operation/Status [700] ............................... 136
11.8.1 Operation [710]..................................................... 136
11.8.2 Status [720] .......................................................... 138
11.8.3 Stored values [730] .............................................. 140
11.9 View Trip Log [800] ............................................... 142
11.9.1 Trip Message log [810]......................................... 142
11.9.2 Trip Messages [820] - [890] ................................ 143
11.9.3 Reset Trip Log [8A0] ............................................. 143
11.10 System Data [900]................................................ 143
11.10.1 VSD Data [920] ..................................................... 143
12. Troubleshooting, Diagnoses and
Maintenance .............................................. 145
12.1 Trips, warnings and limits..................................... 145
12.2 Trip conditions, causes and remedial action ...... 146
12.2.1 Technically qualified personnel............................ 146
12.2.2 Opening the variable speed drive ........................ 146
12.2.3 Precautions to take with a connected motor...... 146
12.2.4 Autoreset Trip ........................................................ 146
12.3 Maintenance ......................................................... 149
13. Options........................................................ 151
13.1 Protection class IP54............................................ 151
13.2 Options for the control panel................................ 152
13.3 EmoSoftCom.......................................................... 152
13.4 Brake chopper....................................................... 152
13.5 I/O Board ............................................................... 153
13.6 Output coils ........................................................... 153
13.7 Serial communication and fieldbus ..................... 153
13.8 Standby supply option .......................................... 153
13.9 Safe Stop option.................................................... 153
13.10 Crane option board ............................................... 155
13.11 Encoder.................................................................. 155
13.12 PTC/PT100 ............................................................ 155
14. Technical Data ........................................... 157
14.1 Electrical specifications related to model ........... 157
14.2 General electrical specifications.......................... 159
14.3 Operation at higher temperatures ....................... 160
14.4 Operation at higher switching frequency............. 160
14.5 Dimensions and Weights...................................... 161
14.6 Environmental conditions..................................... 161
14.7 Fuses, cable cross-sections and glands.............. 162
14.8 Control signals....................................................... 163
15. Menu List .................................................... 165
Index 171

Emotron AB 01-3694-01r2 Introduction 5
1. Introduction
FDU is used most commonly to control and protect pump
and fan applications that put high demands on flow control,
process uptime and low maintenance costs. It can also be
used for e.g. compressors and blowers. Several options are
available, listed in chapter 13. page 151, that enable you to
customize the variable speed drive for your specific needs.
The following symbols can appear in this manual. Always
read these first before continuing:
Users
This instruction manual is intended for:
• installation engineers
• maintenance engineers
•operators
• service engineers
Motors
The variable speed drive is suitable for use with standard 3-
phase asynchronous motors. Under certain conditions it is
possible to use other types of motors. Contact your supplier
for details.
1.1 Delivery and unpacking
Check for any visible signs of damage. Inform your supplier
immediately of any damage found. Do not install the varia-
ble speed drive if damage is found.
The variable speed drives are delivered with a template for
positioning the fixing holes on a flat surface. Check that all
items are present and that the type number is correct.
1.2 Using of the instruction
manual
Within this instruction manual the abbreviation “VSD” is
used to indicate the complete variable speed drive as a single
unit.
Check that the software version number on the first page of
this manual matches the software version in the variable
speed drive.
With help of the index and the contents it is easy to track
individual functions and to find out how to use and set
them.
The Quick Setup Card can be put in a cabinet door, so that
it is always easy to access in case of an emergency.
1.3 Type number
Fig. 1 gives an example of the type code numbering used on
all variable speed drives. With this code number the exact
type of the drive can be determined. This identification will
be required for type specific information when mounting
and installing. The code number is located on the product
label, on the front of the unit.
Fig. 1 Type number
NOTE: Read this instruction manual carefully before
starting installation, connection or working with the
variable speed drive.
NOTE: Additional information as an aid to avoid
problems.
CAUTION: Failure to follow these instructions
can result in malfunction or damage to the
variable speed drive.
WARNING: Failure to follow these instructions
can result in serious injury to the user in addition
to serious damage to the variable speed drive.
HOT SURFACE:
!
Position Configuration
1VSDtype FDU
VFX
2Supplyvoltage
40=400 V mains
48=400 V mains
50=500 V mains
3 Rated current (A) continuous
-003=2.5 A
-
-1500=1500 A
4 Protection class 20=IP20
54=IP54
5 Control panel –=Blank CP
C=Standard CP
6 EMC option
E=Standard EMC
F=Extended EMC
I=IT-Net
FDU48-175-54 C E B S T A V C E P N A
12345678910111213141516

6Introduction Emotron AB 01-3694-01r2
1.4 Standards
The variable speed drives described in this instruction man-
ual comply with the standards listed in Table 1. For the dec-
larations of conformity and manufacturer’s certificate,
contact your supplier for more information or visit
www.emotron.com.
1.4.1 Product standard for EMC
Product standard EN(IEC)61800-3, second edition of 2004
defines the :
First Environment (Extended EMC) as environment that
includes domestic premises. It also includes establishments
directly connected without intermediate transformers to a
low voltage power supply network that supplies buildings
used for domestic purposes.
Second Environment (Standard EMC) includes all other
establishments.
Category C2: Power Drive System (PDS) of rated volt-
age<1.000 V, which is neither a plug in device nor a movable
device and, when used in the first environment, is intended
to be installed and commissioned only by a professional.
Category C3: PDS of rated voltage <1.000 V, intended for
use in the second environment and not intended for use in
the first environment.
Category C4: PDS or rated voltage equal or above 1.000 V,
or rated current equal to or above 400 A, or intended for use
in complex systems in the second environment.
The variable speed drive complies with the product standard
EN(IEC) 61800-3:2004 (Any kind of metal screened cable
may be used). The standard variable speed drive is designed
to meet the requirements according to category C3.
7 Brake chopper option
–=Brake N.C
B=Brake
D=DC interface
8 Stand-by power supply option -=No SBS
S=SBS included
9 Safe stop option –=No safe stop
T=Safe stop incl.
10 Brand label
11 Coated boards, option –=No coating
V=Coated boards
12 Option position 1 N=No option
C=Crane I/O
E=Encoder
P=PTC/PT100
I=Extended I/O
13 Option position 2
14 Option position 3
15 Option position, communica-
tion
N=No option
D=DeviceNet
P=Profibus
S=RS232/485
16 Software type
Position Configuration
WARNING: In a domestic environment this
product may cause radio interference, in
which case it may be necessary to take
adequate additional measures.
WARNING: The standard VSD, complying with
category C3, is not intended to be used on a
low-voltage public network which supplies
domestic premises; radio interference is
expected if used in such a network. Contact
your supplier if you need additional
measures.
CAUTION: In order to comply fully with the
standards stated in the Manufacturer’s
Declaration ANNEX IIB, the installation
instructions detailed in this instruction
manual must be followed to the letter.
!

Emotron AB 01-3694-01r2 Introduction 7
1.5 Dismantling and scrapping
The enclosures of the drives are made from recyclable mate-
rial as aluminium, iron and plastic. Each drive contains a
number of components demanding special treatment, for
example electrolytic capacitors. The circuit boards contain
small amounts of tin and lead. Any local or national regula-
tions in force for the disposal and recycling of these materials
must be complied with.
1.5.1Disposal of old electrical and
electronic equipment
This information is applicable in the European Union and
other European countries with separate collection systems.
This symbol on the product or on its packaging indicates
that this product shall be treated according to the WEEE
Directive. It must be taken to the applicable collection point
for the recycling of electrical and electronic equipment. By
ensuring this product is disposed of correctly, you will help
prevent potentially negative consequences for the environ-
ment and human health, which could otherwise be caused
by inappropriate waste handling of this product. The recy-
cling of materials will help to conserve natural resources. For
more detailed information about recycling this product,
please contact the local distributor of the product or visit our
home page www.emotron.com.
Ta b l e 1 St a n d a rd s
Market Standard Description
European
Machine Directive 98/37/EEC
EMC Directive 2004/108/EEC
Low Voltage Directive 2006/95/EC
WEEE Directive 2002/96/EC
All
EN 60204-1
Safety of machinery - Electrical equipment of machines
Part 1: General requirements.
Machine Directive: Manufacturer’s certificate
acc. to Appendix IIB
EN(IEC)61800-3:2004
Adjustable speed electrical power drive systems
Part 3: EMC requirements and specific test methods.
EMC Directive: Declaration of Conformity and
CE marking
EN50178
(<90 A)
Electronic equipment for use in power installations.
Low Voltage Directive: Declaration of Conformity and
CE marking
EN(IEC)61800-5-1
(≥90 A)
Adjustable speed electrical power drive systems Part 5-1.
Safety requirements - Electrical, thermal and energy.
Low Voltage Directive: Declaration of Conformity and
CE marking
IEC 60721-3-3
Classification of environmental conditions. Air quality chemical vapours, unit in
operation. Chemical gases 3C1, Solid particles 3S2.
Optional with coated boards
Unit in operation. Chemical gases Class 3C2, Solid particles 3S2.
Russian GOST R For all sizes

8Introduction Emotron AB 01-3694-01r2
1.6 Glossary
1.6.1Abbreviations and symbols
In this manual the following abbreviations are used:
1.6.2 Definitions
In this manual the following definitions for current, torque
and frequency are used:
Table 2 Abbreviations
Abbreviation/
symbol Description
DSP Digital signals processor
VSD Variable speed drive
CP Control panel, the programming and pres-
entation unit on the VSD
EInt Communication format
UInt Communication format
Int Communication format
Long Communication format
The function cannot be changed in run
mode
Table 3 Definitions
Name Description Quantity
IIN Nominal input current of VSD A, RMS
INOM Nominal output current of VSD A, RMS
IMOT Nominal motor current A, RMS
PNOM Nominal power of VSD kW
PMOT Motor power kW
TNOM Nominal torque of motor Nm
TMOT Motor torque Nm
fOUT Output frequency of VSD Hz
fMOT Nominal frequency of motor Hz
nMOT Nominal speed of motor rpm
ICL Maximum output current for 60s A, RMS
Speed Actual motor speed rpm
Torque Actual motor torque Nm
Sync
speed Synchronous speed of the motor rpm

Emotron AB 01-3694-01r2 Mounting 9
2. Mounting
This chapter describes how to mount the VSD.
Before mounting it is recommended that the installation is
planned out first.
• Be sure that the VSD suits the mounting location.
• The mounting site must support the weight of the VSD.
• Will the VSD continuously withstand vibrations and/or
shocks?
• Consider using a vibration damper.
• Check ambient conditions, ratings, required cooling air
flow, compatibility of the motor, etc.
• Know how the VSD will be lifted and transported.
2.1 Lifting instructions
Recommended for VSD models -090 to -250
Fig. 2 Lifting VSD model -090 to -250
Recommended for VSD models -300 to -1500
Fig. 3 Remove the roof plate.
Fig. 4 Remove roofunit
Note: To prevent personal risks and any damage to the
unit during lifting, it is advised that the lifting methods
described below are used.
Load: 56 to 74 kg
*
*
*
A
DETAIL A
*

10 Mounting Emotron AB 01-3694-01r2
Fig. 5 Lifting VSD model -300 to -1500
2.2 Stand-alone units
The VSD must be mounted in a vertical position against a
flat surface. Use the template (delivered together with the
VSD) to mark out the position of the fixing holes.
Fig. 6 Variable speed drive mounting models 003 to 250
2.2.1 Cooling
Fig. 6 shows the minimum free space required around the
VSD for the models 003 to 250 in order to guarantee ade-
quate cooling. Because the fans blow the air from the bot-
tom to the top it is advisable not to position an air inlet
immediately above an air outlet.
The following minimum separation between two variable
speed drives, a VSD and a non-dissipating wall must be
maintained:
Table 4 Mounting and cooling
003-
013
018-
037
046-
073
090-
250
300-
1500
FDU-
FDU
(mm)
a 200 200 200 200 100
b 200 200 200 200 0
c 30 0 30 0 0
d 30 0 30 0 0
FDU-
wall
(mm)
a 100 100 100 100 100
b 100 100 100 100 0
c 30 0 30 0 0
d 30 0 30 0 0
NOTE: When a 300 to 1500 model is placed between two
walls, a minimum distance at each side of 200 mm must
be maintained.

Emotron AB 01-3694-01r2 Mounting 11
2.2.2 Mounting schemes
Fig. 7 VSD models 003 - 013 (X1)
Fig. 8 Cable interface for mains, motor and communication,
VSD models 003 - 013(X1)
Fig. 9 VSD models 018 - 037 (S2)
Fig. 10 Cable interface for mains, motor and communication,
VSD models 018 - 037 (S2).
154,5
20 180
7,5385
400
220
Ø 7 (4x)
Ø 13 (2x)
External
Interface
Glands
M20
273
23,75 128,5
10510
176
Ø 7 (4x)
530
Ø 13 (2x)
External
Interface
Glands
M20
Glands
M25 M32M32

12 Mounting Emotron AB 01-3694-01r2
Fig. 11 VSD models 046 - 073 (X2)
Fig. 12 Cable interface for mains, motor and communication,
VSD models 046 - 073 (X2)
Fig. 13 VSD models 090 - 175 including cable interface for
mains, motor and communication (E)
10570
220
30 160
Ø 13 (2x)
Ø 7 (4x)
590
External
Interface
Glands
M20
Glands
M40
284,5
275
30
922,50
120
240
Ø9(6x)
Ø16(3)
10
22,5
952,50
314
925
Membrane cable
gland M60

Emotron AB 01-3694-01r2 Mounting 13
Fig. 14 VSD models 210 - 250 including cable interface for
mains, motor and communication (F)
2.3 Cabinet mounting
2.3.1 Cooling
If the variable speed drive is installed in a cabinet, the rate of
airflow supplied by the cooling fans must be taken into con-
sideration.
2.3.2 Mounting schemes
Fig. 15 VSD models 300 - 500 (G and H)
Table 5 Flow rates cooling fans
FDU Model Flow rate [m3/hour]
003 – 013 40
018 – 037 150
046 – 073 165
090 – 175 510
210 – 250 800
300 – 375 1020
430 – 500 1600
600 – 750 2400
860 – 1k0 3200
1200 – 1500 4800
335
344,5
30
922,50
300
22.50
10
925
952,50
150
Ø16(3x)
Ø9(x6)
314
Cable dimensions 27-66 mm
NOTE: For the models 860 to 1500 the mentioned
amount of air flow should be divided equally over the two
cabinets.
600
2320
600

14 Mounting Emotron AB 01-3694-01r2
Fig. 16 VSD models 600 - 750 (I) Fig. 17 VSD models 860 - 1000 (J)
600
2320
1000
600
2320
1200

Emotron AB 01-3694-01r2 Mounting 15
Fig. 18 VSD models 1200 - 1500 (K)
600
2320
2000

16 Mounting Emotron AB 01-3694-01r2

Emotron AB 01-3694-01r2 Installation 17
3. Installation
The description of installation in this chapter complies with
the EMC standards and the Machine Directive.
Select cable type and screening according to the EMC
requirements valid for the environment where the VSD is
installed.
3.1 Before installation
Read the following checklist and think through your appli-
cation before installation.
• External or internal control.
• Long motor cables (>100m).
• Motors in parallel.
• Functions.
• Suitable VSD size in proportion to the motor/applica-
tion.
• Mount separately supplied option boards according to
the instructions in the appropriate option manual.
If the VSD is temporarily stored before being connected,
please check the technical data for environmental condi-
tions. If the VSD is moved from a cold storage room to the
room where it is to be installed, condensation can form on
it. Allow the VSD to become fully acclimatised and wait
until any visible condensation has evaporated before con-
necting the mains voltage.
3.2 Cable connections
3.2.1 Motor cables
To comply with the EMC emission standards the variable
speed drive is provided with a RFI mains filter. The motor
cables must also be screened and connected on both sides. In
this way a so-called “Faraday cage” is created around the
VSD, motor cables and motor. The RFI currents are now
fed back to their source (the IGBTs) so the system stays
within the emission levels.
Recommendations for selecting motor
cables
• Use screened cables according to specification in table 7.
Use symmetrical shielded cable; three phase conductors
and a concentric or otherwise symmetrically constructed
PE conductor, and a shield.
• When the conductivity of the cable shield is <50% of the
conductivity of the phase conductor, a separate PE con-
ductor is required.
• Use heat-resistant cables, +60°C or higher.
• Dimension the cables and fuses in accordance with the
nominal output current of the motor. See table 43, page
162.
• Keep the motor cable between VSD and motor as short
as possible.
• The screening must be connected with a large contact
surface of preferable 360× and always at both ends, to
the motor housing and the VSD housing. When painted
mounting plates are used, do not be afraid to scrape
away the paint to obtain as large contact surface as possi-
ble at all mounting points for items such as saddles and
the bare cable screening. Relying just on the connection
made by the screw thread is not sufficient.
• The litz connection is only necessary if the mounting
plate is painted. All the variable speed drives have an
unpainted back side and are therefore suitable for
mounting on an unpainted mounting plate.
Connect the motor cables according to U - U, V - V and
W - W.
Fig. 19
Switches between the motor and the
VSD
If the motor cables are to be interrupted by maintenance
switches, output coils, etc., it is necessary that the screening
is continued by using metal housing, metal mounting plates,
etc. as shown in the Fig. 21.
Fig. 22 shows an example when there is no metal mounting
plate used (e.g. if IP54 variable speed drives are used). It is
important to keep the “circuit” closed, by using metal hous-
ing and cable glands.
NOTE: It is important that the motor housing has the
same earth potential as the other parts of the machine.
L2 L3 PEL1 U V WR
DC
+
DC
-
OPTION
This manual suits for next models
35
Table of contents