* 34 x 77mm sized.
* On-Off control.
* 3 contact outputs for cooling defrost and fan controls.
* 2 probes for temperature and defrost controls.
* A buzzer warning for probe failure or alarm cases.
*
* NTC or PTC sensor.
* Adjustable offset for probe.
* The maximum and the minimum values of the setpoint can
be limited.
* Upper and lower alarm values can be entered depending on
setpoint value.
* Time and evaporator temperature dependent defrosting is possible.
* Fan may be operated depending on defrost and compressor.
CE marked according to European Norms.
SÝSEL MÜHENDÝSLÝK ELEKTRONÝK SAN. VE TÝC. A.Þ.
Yukarý Dudullu 34775 - ÜMRANÝYE/ÝSTANBUL/TÜRKÝYE
Tel : +90 216 499 46 64 Pbx. Fax : +90 216 365 74 01
url : www.enda.com.tr
Barbaros Cad. Kutup Sok. No:20
Panel cut-out
Dimensions
EDT1323-E-04
34mm
70mm 8mm
85mm
71mm
29mm
Flush mounting
clamp
Flush mounting
clamp
Depth
Rubber
gasket
Panel
2
1
°C
SET
EDT1323
ENDA
°C
SET
EDT1323
ENDA
1 2 3 4 5 6 7 8 9 10 11 12
EDT1323-NTC-12 DIGITAL THERMOSTAT
WITH DEFROST AND FANS-MANAGING
DEFROST (NTC)
THERMOSTAT (NTC)
12V AC/DC ±10%
50/60 Hz 7VA
SN: XXXXXXXXX
ENDA INDUSTRIAL ELECTRONICS
DEFROST
250V AC 8A
RESISTIVE LOAD
FAN
250V AC 8A
RESISTIVE LOAD
COMPRESSOR
250V AC 8A
RESISTIVE LOAD
Connection Diagram
Holding screw
0.4-0.5Nm
Equipment is protected
throughout by DOUBLE
INSULATION.
ENDA EDT1323 is intended for installation in control panels. Make sure that the device is used
only for intended purpose.
During an installation, all of
the cables that are connected to the device must be free of electrical power. The device must be
protected against inadmissible humidity, vibrations, severe soiling and make sure that the operation
temperature is not exceeded. The cables should not be close to the power cables or components.
The electrical connections must be carried out by a qualified staff
and must be according to the relevant locally applicable regulations.
NOTE :
SENSOR INPUT:
Pay attention to the colors of the PTC probe cables while
connecting them to the PTC SENSOR input of the device.
1) Mains supply cords shall meet the requirements of
IEC 60227 or IEC 60245.
2) In accordance with the safety regulations, the power
supply switch shall bring the identification of the
relevant instrument and it should be easily
accessible by the operator.
Note :
For removing mounting clamps:
Push out the flush-mounting
clamp in direction 1as shown
in the figure below. Then, pull
out the clamp in direction 2.
Note :
1) Panel thickness
should be maximum
7 mm.
2) If there is no 60mm
free space at the back
side of the device, it
would be difficult to
remove it from the
panel.
ENDA EDT1323 TEMPERATURE CONTROLLER
Thank you for choosing ENDA EDT1323 temperature controller.
Supply voltage 230V AC +%10 -%20, 50/60Hz(with external transformer) or 24V AC/DC ±%10, 50/60Hz or
12V AC/DC ±%10, 50/60Hz
Power consumption Max. 7VA
2.5mm² screw-terminal connections.
±1°C
Wiring
Scale
Sensitivity
Accuracy
EMC
Safety requirements
EN 61326-1: 1997, A1: 1998, A2: 2001 (Performance criterion B is satisfied for EMC tests.
The device is designed to operate in controlled electromagnetic environment)
EN 61010-1: 2001 (Pollution degree 2, overvoltage category II)
CONTROL
Control type Dual-setpoint control
On-Off control
Control algorithm
Hysteresis Adjustable between 1 ... 20°C.
OUTPUT
ELECTRICAL CHARACTERISTICS
DEFROST Relay: 250V AC, 8A (for resistive load), NO+NC ; ½ HP 250V AC CosF=0.4 (for inductive load
Relay: 250V AC, 8A (for resistive load), NO ; ½ HP 250V AC CosF=0.4 (for inductive load)
Mechanical 30.000.000 operation; Electrical 100.000 operation.
Note: The relay contacts are suitable for in-line switching of compressors up to 0,5 HP at 240V AC or 1/4 HP at 110V AC.
COMPRESSOR
Life expectancy for relay
-50...+100°C for NTC, -50...+150°C for PTC.
1°C
HOUSING
Housing type Suitable for flush-panel mounting.
Dimensions W77xH34xD70mm
Weight EDT 1323-230 : Approx. 375g (after packing the device ,transformer and a probe)
EDT 1323-12 : Approx. 180g (after packing the device and a probe)
Enclosure material Self extinguishing plastics
Technical Specifications
ENVIRONMENTAL CONDITIONS
Height Maximum 2000m
80%, up to 31 decreasing linearly 50% at 40°C °C
Ambient/storage temperature
Max. relative humidity
0 ... +50 /°C -25 ... +70°C (with no icing)
Rated pollution degree According to EN 60529 Front panel : IP60
Rear panel : IP20
Do not use the device in locations subject to corrosive and flammable gasses.
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
Relay: 250V AC, 8A (for resistive load), NO ; ½ HP 250V AC CosF=0.4 (for inductive load)
FAN
Order Code : EDT1323--
1 2
1 - Probe Type
NTC.....NTC Probe
PTC.....PTC Probe
2 - Supply Voltage
230VAC...230V AC with external transformer
24............24V AC/DC
12............12V AC/DC
sr h s o b p e e l b
Plea e ead t idcument carefully efore using this roduct. Th guarante wi l e
ci m n ru e
invalidated if the devi e s da aged by not followi g inst ctions detail d in the
l e o l b re sm o e hmanua . Th c mpany sha l not e spon ible for any da age r loss s owever
si n o o s
cau ed, which may be exper e ced as a result f the installati n or ue of this product.
12345678910 11 12
EDT1323-PTC-12 DIGITAL THERMOSTAT
WITH DEFROST AND FANS-MANAGING
DEFROST (PTC)
THERMOSTAT (PTC)
12V AC/DC ±10%
50/60 Hz 7VA
RWW
SN: XXXXXXXXX
ENDA INDUSTRIAL ELECTRONICS
DEFROST
250V AC 8A
RESISTIVE LOAD
FAN
250V AC 8A
RESISTIVE LOAD
COMPRESSOR
250V AC 8A
RESISTIVE LOAD
12345678910 11 12
EDT1323-NTC-12 DIGITAL THERMOSTAT
WITH DEFROST AND FANS-MANAGING
DEFROST (NTC)
THERMOSTAT (NTC)
12V AC/DC ±10%
50/60 Hz 7VA
SN: XXXXXXXXX
ENDA INDUSTRIAL ELECTRONICS
DEFROST
250V AC 8A
RESISTIVE LOAD
FAN
250V AC 8A
RESISTIVE LOAD
COMPRESSOR
250V AC 8A
RESISTIVE LOAD
8
9
SUPPLY:
10,8-13,2V AC
50/60Hz 7VA
230V AC
Supply
Switch
Cable size: 1,5mm²
Fuse
F 100 mA
250V AC
Fuse should
be connected.
Transformer
EDT1323 PROGRAMMING DIAGRAM
FAN
LED DEFROST
LED
Compressor
hysteresis
value
If this key is pressed,
COMPRESSOR setpoint
value appears.
Measurement
temperature COMPRESSOR
setpoint value
SET
2/3
RUN MODE
°C
SET
EDT1323
ENDA
COMPRESSOR
LED
If this key is pressed,
hysteresis value for
compressor switch
appears.
If this key is pressed,
lower limit of the setpoint
appears.
If this key is pressed,
state of Fan control is
seen,
state of Fan
control
Lower limit of
the Setpoint
Rdý 2
-50
N
Rll
FaC
PROGRAMMING MODE
Means, thermostat probe is broken or failed or the cold room temperature is out of the
measurement range.
Means, measured value is out of the adjusted alarm limits.
Means, defrost probe is broken or failed or evaporator temperature is out of the measurement
scale range.
Er0
Er1
-30
ERROR MESSAGES
Used for increasing the setpoint value, as well as the
parameter when in programming. When held down for a few
seconds, the change rate accelerates.
When held down for 4 second in the run mode, manual defrost
starts.
Used for decreasing the setpoint value, as well as the parameter
when in programming. When held down for a few seconds, the
change rate accelerates.
Used for adjusting the value of the setpoint in
selected parameter in the programming mode.
the run mode and
for adjusting the
Increment
key
Decrement
key
Programming
key
SET
If both & keys are pressed and held for 5 seconds, programming mode is entered.
By using and keys while holding key, setpoint value
can be adjusted.
SET
By using and keys while holding key, compressor hysteresis
°C , Maximum = 20 °C
value can
be adjusted to a desired temperature.
Minimum = 1
By using and keys while holding key,
°C , Maximum = the value of the ruL parameter.
the lower limit of the setpoint can
be adjusted to a desired temperature.
Minimum = -50
By using and keys while holding key, fan control can be selected as room
temperature dependent or not.
SET
SET
SET
The same procedure is also valid for adjusting the other parameters.
If any no key is pressed within 25 seconds, the device will time out back to the run mode. Alternatively, re-energising the device,
run mode is entered.
EDT1323-E-04
EDT 1323 CONTROL PARAMETERS TABLE
RDI Switch hysteresis for compressor. 120 °C 2
RLL The lower limit of the setpoint of the cold room. -55 Rul °C -50
Rul The upper limit of the setpoint of the cold room.(+100°C for NTC, +150°C for PTC.) Rll 150 °C 150
Rof The offset value for the refrigeration. -20 20 °C 0
Cpo Delay time for the compressor after power is on 015 min 0
Csb Delay time required between successive restarts of the compressor. 015 min 5
Cfs Delay time required for the compressor to restart following a stop. 015 min 3
Cdp Compressor protection delay (n= no delay, y= 3s delay) NYN
Cpp Compressor protection during temperature sensor is broken (off = Compressor is Off during
sensor failure, on= Compressor is On during sensor failure) off on Off
Dty
Defrosting type (El=Electrical defrost, In= hot gas defrost )
Dit Defrosting interval
Dtl Defrosting time limit
Dst Defrosting temperature. If evaporator temperature is higher than this value, defrosting is disabled.
Dpo Defrosting after power on (y=Defrosting begins when power is on,
n=Defrosting doesn’t begin when power is on)
Ddp
Delay time for defrosting after power is on
Ddl
Locking of temperature indication during defrosting. (n= temperature is displayed during defrosting,
y= Displayed value do not changes during Defrosting process.)
Ddt Drainage time
Daa Time interval required for alarm activation after completing defrosting
Ddc Compressor with delay time at the selection of hot gas defrosting (y= Yes, n= No,
Note: Delay time is adjusted by using CPO, CSB and CFS parameters)
Dpr
The display of evaporator temperature
Dtb Defrosting period time base (hr= Hour, minute Sc=Minute,second)
Adi
Switch hysteresis for alarm
Alr Limit for low alarm level (If temperature falls down setpoint by this value, buzzer starts ringing)
Ahr Limit for upper alarm level (If temperature exceeds setpoint by this value, buzzer starts ringing)
Apd Time delay required for alarm to become active after power is on
Frt
Fan is controlled depending on temperature.
Fst If evaporator temperature is above this parameter, fan stops
Fdi Switch hysteresis for fan
Fco Does fan stop when compressor stops? (off= Yes, on= No)
Fdo Does fan stop during defrosting? (off= Yes, on= No)
Fdt
The time period of stopping fan after drainage.
el in el
099 Hour/(min) 8
199 Min./(sec.) 30
-55 99 °C 2
NYY
015 min./(sec.) 2
015 Hour 2
NYY
°C
hr Sc hr
015 °C 2
150 °C 10
150 °C 10
015 Hour 2
NYY
-55 99 1
°C
215 °C 2
off On off
off On off
015 min./(sec.) 2
NYN
031 min 0
NYN
Does the fan control depend on the temperature of cold room? (Y= Yes, n= No)
If (n) is selected, while
(y) is selected, fan stops while the difference between cold room and the evaporator temperature
is lower than the value of the parameter
fan stops evaporator temperature is above the value of Fst parameter,
If
Fst .
Fan restarts again, if the difference between cold room and the evaporator temperature
becomes higher than the total of the values of fst and fdi parameters.
Fac
Min. Max. Unit Initial
values
Refrigeration control parameters
Compressor protection parameters
Defrost control parameters
Alarm parameters
Fan control parameters
3/3 EDT1323-E-04
100 100

Other ENDA Temperature Controllers manuals

ENDA EI1410 NTC User manual

ENDA

ENDA EI1410 NTC User manual

ENDA ET2011 User manual

ENDA

ENDA ET2011 User manual

ENDA ET2011 User manual

ENDA

ENDA ET2011 User manual

ENDA EDT1411P User manual

ENDA

ENDA EDT1411P User manual

ENDA ET4430 User manual

ENDA

ENDA ET4430 User manual

ENDA EDT1411 User manual

ENDA

ENDA EDT1411 User manual

Popular Temperature Controllers manuals by other brands

SensoScientific OTA Series user guide

SensoScientific

SensoScientific OTA Series user guide

IKA IKATRON ETS-D5 operating instructions

IKA

IKA IKATRON ETS-D5 operating instructions

Fuji Electric PXH Series manual

Fuji Electric

Fuji Electric PXH Series manual

eltherm ELTC-W operating manual

eltherm

eltherm ELTC-W operating manual

HeaterMate HY02TP Quick start up guide

HeaterMate

HeaterMate HY02TP Quick start up guide

Honeywell T7470A1009 Product data and installation instructions

Honeywell

Honeywell T7470A1009 Product data and installation instructions

Hanna Instruments HI 993301 instruction manual

Hanna Instruments

Hanna Instruments HI 993301 instruction manual

AKO AKO-16526A quick guide

AKO

AKO AKO-16526A quick guide

Danfoss CP715 Si Installation & user's instructions

Danfoss

Danfoss CP715 Si Installation & user's instructions

Autonics TX Series product manual

Autonics

Autonics TX Series product manual

Black Box BDS-8W quick start guide

Black Box

Black Box BDS-8W quick start guide

elsner elektronik KNX T-AP Installation and adjustment

elsner elektronik

elsner elektronik KNX T-AP Installation and adjustment

Delta DTE Series instruction sheet

Delta

Delta DTE Series instruction sheet

Lake Shore 335 user manual

Lake Shore

Lake Shore 335 user manual

Ebmpapst 210-OMI10878 Operating and maintenance instructions

Ebmpapst

Ebmpapst 210-OMI10878 Operating and maintenance instructions

HANYOUNG NUX NP200 user manual

HANYOUNG NUX

HANYOUNG NUX NP200 user manual

Pro 1 IAQ True Comfort T905pro1 Installation & maintenance

Pro 1 IAQ

Pro 1 IAQ True Comfort T905pro1 Installation & maintenance

Fantini Cosmi CH180K3 Instructions for use

Fantini Cosmi

Fantini Cosmi CH180K3 Instructions for use

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.