ENDA EI1410 NTC User manual

TECHNICAL SPECIFICATIONS
ENVIRONMENTAL CONDITIONS
Height Max. 2000m
Ambient/storage temperature
Max. relative humidity
Rated pollution degree According to EN 60529 Front panel : IP65 , Rear panel : IP20
Do not use the device in locations subject to corrosive and flammable gases.
Thank you for choosing ENDA EI1410 NTC temperature indicator.
SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş.
Şerifali Mah. Barbaros Cad. No:18 Y.Dudullu 34775 - ÜMRANİYE/İSTANBUL/TÜRKİYE
Tel : +90 216 499 46 64 Pbx. Fax : +90 216 365 74 01
url : www.enda.com.tr
* 77 x 35mm sized.
* 4 digits display.
* Easy to use with front panel keypad.
* Display can be selected decimal or integer.
* Temperature unit can be selected as °C or °F.
* Stores maximum and minimum measurement values.
* Upper and lower alarm limit values can be adjusted.
* CE marked according to European Norms.
Supply
Power consumption
2.5mm² screw-terminal connections
±
Wiring
Scale
Sensitivity
Accuracy
EMC
Safety requirements
EN 61326-1: 2006
EN 61010-1: 2010 (Pollution degree 2, overvoltage category II)
ELECTRICAL CHARACTERISTICS
-60.0°C...150.0°C
0.1°C
Max. 4 VA
1°C
Decimal
Integer -60°C...150°C
HOUSING
Housing type Suitable for flush-panel mounting.
Dimensions W77xH35xD71mm
Weight
Enclosure material Self extinguishing plastics.
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
EI1410-230VAC Approx. 190g (after packing)
EI1410-24 and EI1410-12
EI1410-E-10-R-201307
1/3
Please read this document carefully before using this product. The guarantee will be invalidated if the device is
damaged by not following instructions detailed in the manual. The company shall not be responsible for any
damage or losses however caused, which may be experienced as a result of the installation or use of this product.
Order Code : EI1410-NTC-
1
Supply Voltage
230VAC...230V AC
24............24V AC/DC
12............12V AC/DC
Approx. 110g (after packing)
ENDA EI1410 NTC TEMPERATURE INDICATOR
SET
SET
EI 1410
ENDA
°F
°C
230V AC +%10 -%20, 50/60Hz or 24V AC/DC ±%10, 50/60Hz or 12V AC/DC ±%10, 50/60Hz
80 Relative humidity for temperatures up to 31°C, decreasing linearly to 50% at 40°C.%
0 ...+50°C / -25 ...+70°C

SN: XXXXXXXXX
EI1410-NTC-12
NTC TEMPERATURE INDICATOR
ENDA INDUSTRIAL ELECTRONICS
12V AC/DC ±10%
50/60Hz 4VA
1 2 3 4 5 6 7 8 9 10 11 12
NTC
SENSOR
SN: XXXXXXXXX
EI1410-NTC-24
NTC TEMPERATURE INDICATOR
ENDA INDUSTRIAL ELECTRONICS
24V AC/DC ±10%
50/60Hz 4VA
1 2 3 4 5 6 7 8 9 10 11 12
NTC
SENSOR
8 680407 703623
Made in Turkey Made in Turkey
8 680407 703630
SN: XXXXXXXXX
EI1410-NTC-230VAC
NTC TEMPERATURE INDICATOR
ENDA INDUSTRIAL ELECTRONICS
230V AC +10% -20%
50/60Hz 4VA
1 2 3 4 5 6 7 8 9 10 11 12
NTC
SENSOR
8 680407 703616
Made in Turkey
2/3
DIMENSIONS
CONNECTION DIAGRAM
ENDA EI1410
intended purpose. The electrical connections must be carried on by a qualified staff and must be
according to the relevant locally applicable regulations. During an installation, all of the cables that are
connected to the device must be free of electrical power. The device must be protected against
inadmissible humidity, vibrations and severe soiling. Make sure that the operation temperature is not
exceeded. The cables should not be close to the power cables or components.
is intended for installation in control panels. Make sure that the device is used only for
7
8
SUPPLY:
NOTE :
184-253V AC
50/60Hz 4VA
Line
Neutral
230V AC
Supply
Switch
Cable size: 1,5mm²
Fuse
F 100 mA
250V AC
Fuse should be connected.
1) Mains supply cords shall meet the requirements of
IEC 60227 or IEC 60245.
2) In accordance with the safety regulations, the power
supply switch shall bring the identification of the relevant
instrument and it should be easily accessible by the
operator.
UP.l1
UP.l1 HYS -
LO.l1
LO.l1 HYS +
Alarm
Input
t
t
When an alarm condition occurs, measured temperature value flashes on the display.
Equipment is protected througout
by DOUBLE INSULATION.
Holding screw 0.4-0.5Nm
Panel cut-out
Note :
1) Panel thickness should be maximum 7 mm.
2) There must be at least 60mm free space
behind the device,otherwise it would be
difficult to remove it from the panel.
71,5mm
29,5mm
Flush mounting
clamp
1
Depth
Panel
2
71mm 5mm
Rubber
packing
35mm
77mm
SET
°C
SET
Ei1410
ENDA
°F
For removing mounting clamps:
- Push the flush-mounting clamp in direction 1 as
shown in the figure left.
- Then, pull out the clamp in direction 2.
SN: XXXXXXXXX
EI1410-NTC-230VAC
NTC TEMPERATURE INDICATOR
ENDA INDUSTRIAL ELECTRONICS
230V AC +10% -20%
50/60Hz 4VA
1 2 3 4 5 6 7 8 9 10 11 12
NTC
SENSOR
8 680407 703616
Made in Turkey
EI1410-E-10-R-201307

3/3
Used for displaying and configuring the selected parameter value.
Programming
Key
Used for increasing the setpoint value and changing parameters.
When held down for a few seconds, configured numeric value increases faster..
When held down for a few seconds, configured numeric value increases faster.
Used for decreasing the setpoint value and changing parameters.
Increment
Key
Decrement
Key
EI1410 PROGRAMMING DIAGRAM
If without pressing any button for 20 seconds or powered down and powered up the device, then it returns to operation mode.
If both & keys are pressed and held for 3 seconds, programming mode is entered or run mode is returned.
Alarm
upper limit
value
Process value
RUN MODE
PROGRAMMING MODE
Alarm lower limit value. If the process value falls below A.lol value, display flashes.
By using and keys, while holding key, the lower limit can be adjusted to desired value
between -60.0°C and A.upl.
Alarm upper limit value. If the process value exceeds A.upl value, display flashes.
By using and keys, while holding key, the upper limit can be adjusted to desired value
between A. and 150.0°C.lol
Alarm
lower limit
value
Alarm hysteresis value.
By using and keys, while holding key, hysteresis value can be adjusted to desired value
between 0.0°C and 15.0°C. Maximum value of this parameter must be ( - ) / .A.upl A.Lol 2
If this key is pressed,
upper limit value
appears.
If this key is pressed,
lower limit value
appears.
Selecting decimal place.Display can be selectable decimal or integer.
By using and keys, while holding key, display can be selected decimal or integer.
When is selected, decimal case is entered. If is selected, integer case is entered.
All of other parameters are adjusted according to selection.
Yes no
If this key is pressed,
temperature unit
appears.
Temperature unit.
By using and keys, while holding key, temperature unit can be selected °C or °F.
If this key is pressed,
display alternatives
appears.
Alarm
hysteresis
value
If this key is pressed,
hysteresis value
appears.
If this key is pressed,
offset value
appears.
Offset value.
By using and keys, while holding key, offset can be adjusted to desired value
between -20.0°C ile 20.0°C.
Means, indicator probe is short circuit.
Means, indicator probe is broken.
ERROR MESSAGES
Means, process value is higher than the scale.
Means, process value is lower than the scale.
EI 1410
ENDA
SET
SET
°F
°C
SET
Temperature
unit
Selecting
decimal place
Offset
value
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
In run mode, key is held down, the highest measured temperature is displayed.
Pressing this key while holding down the or the first power up of the device,
measured at the highest temperature value set to the value of the current temperature.
In run mode, key is held down, the highest measured temperature is displayed.
Pressing this key while holding down the or the first power up of the device,
measured at the lowest temperature value set to the value of the current temperature.
if the measurement temperature is above A.uPL value, the indicator flashes a warning.
EI1410-E-10-R-201307
Table of contents
Other ENDA Temperature Controllers manuals
Popular Temperature Controllers manuals by other brands

Hanna Instruments
Hanna Instruments HI 993301 instruction manual

AKO
AKO AKO-16526A quick guide

Danfoss
Danfoss CP715 Si Installation & user's instructions

Autonics
Autonics TX Series product manual

Black Box
Black Box BDS-8W quick start guide

elsner elektronik
elsner elektronik KNX T-AP Installation and adjustment

Delta
Delta DTE Series instruction sheet

Lake Shore
Lake Shore 335 user manual

Ebmpapst
Ebmpapst 210-OMI10878 Operating and maintenance instructions

HANYOUNG NUX
HANYOUNG NUX NP200 user manual

Pro 1 IAQ
Pro 1 IAQ True Comfort T905pro1 Installation & maintenance

Fantini Cosmi
Fantini Cosmi CH180K3 Instructions for use