ENMET LC1 User manual

ENMET
680 Fairfield Court
Ann Arbor, MI 48108
734.761.1270 Fax 734.761.3220
www.enmet.com
LC-Series Controller
1-4 Channel
Operation and Maintenance Manual

LC-Series Controller: 1-4 Channel
ENMET
Manual Revision Date – June 13, 2017
Page | 1
Manual Part No. – 80003-050
Table of Contents
1.0 INTRODUCTION....................................................................................................................................................................2
1.1 Unpack.............................................................................................................................................................................................2
1.2 Check Order.....................................................................................................................................................................................2
1.3 Serial Numbers.................................................................................................................................................................................2
2.0 FEATURES ...........................................................................................................................................................................3
2.1 Front panel features..........................................................................................................................................................................3
3.0 INSTALLATION.....................................................................................................................................................................4
4.0 WIRING THE LC SERIES.......................................................................................................................................................6
4.1 System Wiring .................................................................................................................................................................................6
4.1.1 Power Supply Module.....................................................................................................................................................................................7
4.1.3 Connections LC1.............................................................................................................................................................................................8
4.1.4 Connections LC2.............................................................................................................................................................................................9
4.1.5 Connections LC4...........................................................................................................................................................................................10
4.2 Sensor Transmitter Installation......................................................................................................................................................11
4.2.1 Example 2 Wire Sensor Transmitter.............................................................................................................................................................11
4.2.2 Example 3 Wire Sensor Transmitter.............................................................................................................................................................11
5.0 OPERATION .......................................................................................................................................................................12
5.1 LC-Series Microcontroller Module................................................................................................................................................12
5.2 Analogue Output Configuration.....................................................................................................................................................14
5.2.1 4-20mA Current Source................................................................................................................................................................................ 14
5.2.2 4-20mA Current Sink....................................................................................................................................................................................15
5.2.3 1-5V Voltage Output..................................................................................................................................................................................... 16
6.0 MAINTENANCE ..................................................................................................................................................................17
7.0 TECHNICAL DATA AND SPECIFICATIONS.............................................................................................................................18
8.0 TERMS AND CONDITIONS ...................................................................................................................................................21
8.1 Ordering Information.....................................................................................................................................................................21
8.2 Delivery .........................................................................................................................................................................................21
8.3 Payment Terms ..............................................................................................................................................................................21
8.4 Warranty Information and Guidelines ...........................................................................................................................................21
8.5 Return Policy .................................................................................................................................................................................21
9.0 INSTRUCTIONS FOR RETURNING AN INSTRUMENT FOR SERVICE...........................................................................................22
List of Figures
Figure 1: LC Series Front Panel Features..................................................................................................................................................3
Figure 2: Mounting LC Series ...................................................................................................................................................................5
Reference Information:
NOTE:[important information about use of instrument]
CAUTION:[affects equipment – if not followed may cause damage to instrument, sensor etc.…]
WARNING:[affects personnel safety – if not followed may cause bodily injury or death.]
Attention / Warning
Earth Ground
!

LC-Series Controller: 1-4 Channel
ENMET
Manual Revision Date – June 13, 2017
Page | 2
Manual Part No. – 80003-050
1.0 Introduction
The LC Series Control Units that provide facilities to monitor a wide variety of industry standard environmental and other sensors.
The LC1 provides 1 monitoring channel.
The LC2 provides up to 2 monitoring channels.
The LC4 provides up to 4 monitoring channels.
The LC-Series Controller has been designed to allow the use of any ENMET sensor transmitter and has been preprogrammed to
match the sensor transmitters supplied at time of delivery. The LC-Series can also be used with any manufactures sensor transmitter
that can produce a voltage or current output within a specified range; however, it is advisable that you contact ENMET for proper
setup and programming instructions. Care has been taken with the design of the MCU housings and internal chassis to facilitate ease
of connection and wire termination. All on-site wiring to the system is via screw terminal connectors. The terminal cover has an
internal label giving details of the external connections.
NOTE:All specifications stated in this manual may change without notice.
1.1 Unpack
Unpack the LC-Series Controller and examine it for shipping damage. If such damage is observed, notify both ENMET
customer service personnel and the commercial carrier involved immediately.
Regarding Damaged Shipments
NOTE: It is your responsibility to follow these instructions. If they are not followed, the carrier will not honor any claims for
damage.
This shipment was carefully inspected, verified and properly packaged at ENMET and delivered to the carrier in good
condition.
When it was picked up by the carrier at ENMET, it legally became your company’s property.
If your shipment arrives damaged:
Keep the items, packing material, and carton “As Is.” Within 5 days of receipt, notify the carrier’s local office and
request immediate inspection of the carton and the contents.
After the inspection and after you have received written acknowledgment of the damage from the carrier, contact
ENMET Customer Service for return authorization and further instructions. Please have your Purchase Order and Sales
Order numbers available.
ENMET either repairs or replaces damaged equipment and invoices the carrier to the extent of the liability coverage, usually
$100.00. Repair or replacement charges above that value are your company’s responsibility.
The shipping company may offer optional insurance coverage. ENMET only insures shipments with the shipping company
when asked to do so in writing by our customer. If you need your shipments insured, please forward a written request to
ENMET Customer Service.
Regarding Shortages
If there are any shortages or questions regarding this shipment, please notify ENMET Customer Service within 5 days of receipt at
the following address: ENMET
680 Fairfield Court
Ann Arbor, MI 48108
734-761-1270 Fax 734-761-3220
Toll Free: 800-521-2978
1.2 Check Order
Check, the contents of the shipment against the purchase order. Verify that the LC-Series Controller is received as ordered. If
there are accessories on the order, ascertain that they are present. Check the contents of calibration kits. Notify ENMET customer
service personnel of any discrepancy immediately.
1.3 Serial Numbers
Each LC-Series Controller is serialized. These numbers are on tags on the equipment and are on record in an ENMET database.

LC-Series Controller: 1-4 Channel
ENMET
Manual Revision Date – June 13, 2017
Page | 3
Manual Part No. – 80003-050
2.0 Features
The LC-Series Controller houses all of the components required to implement a sophisticated and reliable monitoring system (alarm
relays etc.). See Figure 1 for location of features:
2.1 Front panel features
See Figure 1 for location of features.
LED
Description
Power
Green LED for Power
AL3
Red LED indication of Alarm Level 3
AL2
Red LED indication of Alarm Level 2
AL1
Red LED indication of Alarm Level 1
Fault
Yellow LED, Lower most, indication of Fault Condition
Keypad Buttons, 4
2 as indicated in figure 1 that are
used during normal operation and 2
that are used during setup and
programming
Menu – Main Select Switch
Increase – Menu Option, used in setup & programming
Decrease – Change Switch, used in setup & programming
Alarm Acknowledgment – Horn Defect Switch
Display
Graphic display simultaneously showing reading for each channel and sensor type
An Audible signal is also provided by a sounder mounted within Microcontroller module. This provides a local audible tone during
alarm or conditions.
Figure 1: LC Series Front Panel Features
C1 60 %
LEL
CH4
C2 0.0 %v/v
CO2
Display
Power LED
Fault LED
Alarm 1, 2 & 3 LED
Alarm Acknowledgment Switch
Menu Switch
Increase & Decrease Switches

LC-Series Controller: 1-4 Channel
ENMET
Manual Revision Date – June 13, 2017
Page | 4
Manual Part No. – 80003-050
3.0 Installation
The LC-Series Controller is fully tested prior to delivery. However, it is recommended that the LC-Series Controller system be
checked after installation is complete.
CAUTION: The MCU Control Units and associated modules contain no user serviceable parts. Refer all servicing to qualified
service personnel
The LC series control units must be mounted in a non-hazardous location where there is no risk of the presence of potentially
explosive gas
Either a 100-240VAC 50/60 Hz supply or a 24V DC supply can be used to power the control unit
The location of installation should be chosen with regard to the following:
This equipment should not be located near to known sources of heat.
Operating personnel should be within convenient reach of the equipment and within audible distance of alarms
Maximum loop lengths of cable run and cable inductance to resistance ratios must not exceed limits shown in the relevant
loop diagrams
Avoid mounting this equipment near potential sources of electrical interference e.g. motors, switch gear, radio transmitters etc.
Mounting details for the LC Controller enclosures are located below:
LC-2 Control Unit
4.585
[116.4]
2.968
[75.4] 5.937
[150.8]
.38
[9.6]
7.39
[188]
5.26
[134]
6.30
[160.0]
LC-1 CONTROL UNIT
7.656
[194.4]
4.764
[121.0] 9.528
[242.0]
11.02
[280] 6.14
[156]
8.58
[218.0]
.39
[10.0]

LC-Series Controller: 1-4 Channel
ENMET
Manual Revision Date – June 13, 2017
Page | 5
Manual Part No. – 80003-050
LC-4 Control Unit
Figure 2: Mounting LC Series

LC-Series Controller: 1-4 Channel
ENMET
Manual Revision Date – June 13, 2017
Page | 6
Manual Part No. – 80003-050
4.0 Wiring the LC Series
The electrical installation should conform to appropriate electrical codes, such as the National Electrical Code in the United States.
WARNING:The compliance of the installation to appropriate codes is not ENMET’s responsibility.
4.1 System Wiring
All connections should be made according to the appropriate sensor or loop diagram for the configuration required. It is advised
that ‘Bootlace Ferrules’ or ‘flat blade crimps’ be used for tidy and reliable connections of wires into the Control Unit and Detector
Head connectors
Power Supply Input
An isolating switch should be provided between the power source and the MCU control units to allow the supply to be easily
disconnected. This should incorporate over current protection or a circuit breaker. Alternatively, a fused supply would suffice
AC Mains Connection
The power supply board has three screw terminals connector assigned for the connection of an AC supply.
Pin 1 = Earth
Pin 2 = Live input
Pin 3 = Neutral input
Recommendation for mains input cable. 3-Core – 16 AWG Conductors having cross sectional area of 0.75mm2minimum (24/0.2)
DC Voltage Connection
The power supply board has two screw terminals assigned for the connection of a DC supply
Pin 4 = +24V DC input
Pin 5 = 0V DC input
Cable Routing
Due to the low signal levels generated by gas detectors it is recommended that all wiring to the sensors by segregated away from
AC mains or other high voltage/power lines to avoid interference.
Cable Screening
The use of a screened cable is recommended for the installation of all detector heads. The screening is used to minimize the effects
of electrical interference generated by external equipment e.g. motors, switchgear etc. The correct strategy for connecting the
screens depends upon the area in which the detector head is to be used (i.e. hazardous/ non-hazardous). In all cases the screen
should not be connected at the detector head

LC-Series Controller: 1-4 Channel
ENMET
Manual Revision Date – June 13, 2017
Page | 7
Manual Part No. – 80003-050
4.1.1 Power Supply Module
The Power Supply is situated on the LHS of the main PCB within the enclosure and provides the power for the whole system.
The power supply is a standard item and does not require any modifications regardless of the type and quantity of detector
heads being used.
TRACO®
POWER
FG
AC(N)
AC(L)
Input: 100 – 240 VAC
47-63 Hz
0.375 A max
Output: 24VDC / 625 mA
TML 15124
Fault relay
Fuse 1
Fuse 2
1 2 3 4 5 6 7 8 9 10 11 12
Common L3 Alarm
Relay
Power Switch
There are two power source options available to the system
100-240V AC Mains Supply, connectors 1, 2 and 3
18 to 28V DC Supply, connectors 4 and 5
There are two fuses situated on the main PCB. These are:
FS1 (T1.0A) AC supply Fuse
FS2 (T500mA) DC Supply Fuse

LC-Series Controller: 1-4 Channel
ENMET
Manual Revision Date – June 13, 2017
Page | 8
Manual Part No. – 80003-050
The LC Series Control Units are single PCB design. Each Control Unit has a power supply section and 1, 2 or 4 I/O interface
sections.
Located on the bottom edge of the main PCB is a number of screw connectors. This is used to provide connections for inputs,
outputs and external buttons:
4.1.3 Connections LC1
LC1
T R A C O®
P O W E R
FG
AC(N)
AC(L)
Input: 100 – 240 VAC
47-63 Hz
0.375 A max
Output: 24VDC / 625 mA
TML 15124
Display PCB Connector
E
L
N
+24V
0V
15 16 17 18
- OUTPUT
+4-20 mA
+ SOUNDER
- SOUNDER
J1
J2
J3
J4
J5
J6
J7
J8
J9
J10
J11
J12
J13
J14
D5 D4
100 - 240
VAC D C
FLT L1 L2
SENSOR
OPTIONS
COM
N.C
N.O
COM
N.C
N.O
COM
N.C
N.O
1 2 3 4 5 6 7 8 9 10 11 12 13 14 19 20 21 22
Channel 1
Pins 1, 2 and 3
AC power input
Pins 4 and 5
24VDC power input
Pins 6, 7 and 8
Common Fault relay contacts
Pins 9, 10 and 11
Common Alarm level1 relay contacts
Pins 12, 13 and 14
Common Alarm level1 relay contacts
Pins 15 to 18
I/O connection to sensors
Pins 19 to 20
4-20 mA output
NOTE: D5 orientation is be selected for 24Vdc supply as follows
Input Output
D5
D5

LC-Series Controller: 1-4 Channel
ENMET
Manual Revision Date – June 13, 2017
Page | 9
Manual Part No. – 80003-050
4.1.4 Connections LC2
LC2
TRACO®
POWER
FG
AC(N)
AC(L)
Input: 100 –240 VAC
47-63 Hz
0.375Amax
Output: 24VDC/ 625mA
TML15124
Display PCB Connector
E
L
N
+24V
0V
- OUTPUT
+4-20 mA
100 - 240
VAC D C
FLT L3
SENSOR
OPTIONS
COM
N.C
N.O
COM
N.C
N.O
L1
COM
N.C
N.O
L2
COM
N.C
N.O
1413 15 16
10
11
12
13
14
J1
J2
J3
J4
J5
J6
J7
J8
J9
FS1FS2
SW1
12 3 456 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Power supply sectionI/O interface section Channel
Note: connections 12 & 13 may not be fitted on some variants
Channel 1
Pins 1, 2 and 3
AC power input
Pins 4 and 5
24VDC power input
Pins 6, 7 and 8
Common Fault relay contacts
Pins 9, 10 and 11
Common Alarm level 3 relay
contacts
Pins 13 to 16
I/O connection to sensors
Pins 17 to 18
4-20 mA output
Pins 19 to 21
Alarm Level 1 relay contacts
Pins 22 to 24
Alarm Level 2 relay contacts
Chanel 2
Pins 25 to 36
The same functions as 13 to 24

LC-Series Controller: 1-4 Channel
ENMET
Manual Revision Date – June 13, 2017
Page | 10
Manual Part No. – 80003-050
4.1.5 Connections LC4
LC4
TRACO®
POWER
FG
AC(N)
AC(L)
Input: 100 – 240VAC
47-63 Hz
0.375 Amax
Output: 24VDC/ 625mA
TML15124
Display PCB Connector
E
L
N
+24V
0V
- OUTPUT
+ 4-20 mA
100 - 240
VAC D C
FLT L3
SENSOR
OPTIONS
COM
N.C
N.O
1413 15 16
10
11
12
13
14
J1
J2
J3
J4
J5
J6
J7
J8
J9
FS1FS2
SW1
1 2 3 4 5 6 7 8 9 10 11 12 17 18
N.C
N.O
COM
L1
COM
N.C
N.O
18 19 20 21 22 23
L2
COM
N.C
N.O
14 15 1613
Chanel 1
Connections
Sensor Options:
Pin 13: Signal In (1 – 5 Vdc)
Pin 14: Signal In (4-20mA)
Pin 15: Voltage Out to S/T
Pin 16: Ground to S/T
Chanel 2
Pins 25 to 36
The same functions as 13 to 24
Chanel 3
Pins 37 to 48
The same functions as 13 to 24
Chanel 4
Pins 49 to 60
The same functions as 13 to 24
An Earth ground is also provided
on the main PCB
The diagrams above show a pictorial representation of the various module positions within the LCU Series Control Units
The power supply is situated on the LHS of the main PCB with the channel I/Os to the right of the PCB.
The microcontroller module and LCD display are mounted on the top of the front panel. This connects to the main PCB via a
single flat ribbon cable
NOTE:connections 12 & 13 may not be fitted on some variants.

LC-Series Controller: 1-4 Channel
ENMET
Manual Revision Date – June 13, 2017
Page | 11
Manual Part No. – 80003-050
4.2 Sensor Transmitter Installation
Mounting location for the gas detectors need to be considered individually, initial points for consideration are:
Ensure all gas detectors are mounted to allow routine calibration and maintenance to be carried out as required.
Ensure the proposed site will not interfere with movement of existing equipment, e.g. cranes, doors etc
Install all cables neatly and securely.
Detectors for gases that are lighter than air should be positioned at, or below, a high level.
Detectors for gases that are heavier than air should be located at below head height.
Avoid location the gas detectors adjacent to potential sources of radio frequency interference, e.g. radio transmitters,
control switchgear, motors etc.
Ensure the detectors are mounted with sufficient space to allow air movement around the sensor section.
4.2.1 Example 2 Wire Sensor Transmitter
CHANNEL 1
LEVEL 1
ALARM LEVEL 2
ALARM
J1
J2
J3
J4
J5
J6
J7
J8
J9
+ve -Ve
4.2.2 Example 3 Wire Sensor Transmitter

LC-Series Controller: 1-4 Channel
ENMET
Manual Revision Date – June 13, 2017
Page | 12
Manual Part No. – 80003-050
5.0 Operation
When a preset alarm point is reached, visual and/or audio alarms are activated. The backlit graphics display automatically displays the
channel in alarm and an alarm level Led(s) are activated on the control panel. The LC-8 is factory set to maintain these alarms until
they are acknowledged.
5.1 LC-Series Microcontroller Module
Situated within the LC Control Unit front panel is the Microcontroller Module. This module communicates with all Input channels
connected to the system PCB.
The Microcontroller Module provides a user interface in the form of a back lit graphics display and a four-button multifunction
keypad.
Three LED indications are provided directly by the Microcontroller Module and these are visible via MCU front panel:
Green LED for power.
Red LED indication of Alarm level 1.
Red LED indication of Alarm level 2
Red LED indication of alarm level 3.
Yellow LED indication of fault condition.
An Audible signal is also provided by a sounder mounted within Microcontroller module. This provides a local audible tone during
alarm or conditions.
The Microcontroller Module also provides the user with many configuration and interrogation facilities via the LCD and keypad.
These facilities include:
Sensor Configuration.
Allows adjustment of Sensor type and range (e.g. Flammable 100%LEL).
Calibration of the system.
This allows each channel to be calibrated independently. The sensor zero point and span can both be set via this function.
Calibration of the retransmitted output for each channel.
Calibration of the channel power supply.
Input Module Relay Configuration.
Each Input Module contains two relays for alarm levels 1 and 2. The alarm levels can be individually set to be either rising
or falling.
Fault relay.
All relays can be configured normally energized or de-energized as required. Latching and non-latching functions can also
be selected.
The microcontroller module contains all of the software required to communicate with up to four detecting channels. The software
is common to all LC Series Control Units.

LC-Series Controller: 1-4 Channel
ENMET
Manual Revision Date – June 13, 2017
Page | 13
Manual Part No. – 80003-050
Connection Procedure
Disconnect power from the system.
Remove the terminal cover to gain access to the wiring.
Remove the terminal cover and display module to gain access to the configuration link settings.
Configure the jumper switches as shown below (i.e. J1, J2, J4, J5, J8 and J9 switched ON, all others OFF)
J1
J2
J3
J4
J5
J6
J7
J8
J9
Connect the wires from the detector head to connector on the input module observing the following:
Detector Head Label
4-20mA Loop
Channel 1
Pin Number
Channel 2
Pin Number
Channel 3
Pin Number
Channel 4
Pin Number
–
14
26
38
50
+
15
27
39
51
Connect power to the system and ensure the detector head operates (text on LCD display, LED will flash once every six
seconds approximately).
Perform software configuration (refer to ‘LC Software Configuration and System Calibration Manual’).
Perform system calibration (refer to ‘LC Software Configuration and System Calibration Manual’).

LC-Series Controller: 1-4 Channel
ENMET
Manual Revision Date – June 13, 2017
Page | 14
Manual Part No. – 80003-050
5.2 Analogue Output Configuration
In addition to providing the connections for various connector types, the Input Module can also provide an analogue output. This
output mimics the signal detected so that it may be used by external equipment (e.g. chart recorders, data loggers) for a variety of
purposes.
NOTE: It is important to ensure that the Analogue Output is calibrated if in use (refer to ‘MCU Software Configuration and
System Calibration Manual’).
5.2.1 4-20mA Current Source
Chart recorder
0V
Alarm
level1
J1
J2
J3
J4
J5
J6
J7
J8
J9
J10
J11
J12
J13
J14
Alarm
level2
14 15 16 17 18 19 20 21 22 23 24
Channel 1 26 27 28 29 30 31 32 33 34 35 36
Channel 2 38 39 40 41 42 43 44 45 46 47 48
Channel 3 50 51 52 53 54 55 56 57 58 59 60
Channel 4
16 17 18
LC 1 15
13
25
37
49
The Input Module sources current proportional to the detected gas level.
i.e. zero gas = 4mA
full scale = 20mA
The supply is taken from the internal PSU. Switch ON J12 and J14
J10
J11
J12
J13
J14
NOTE: Incorrect jumper switch configuration can cause damage to the system.

LC-Series Controller: 1-4 Channel
ENMET
Manual Revision Date – June 13, 2017
Page | 15
Manual Part No. – 80003-050
5.2.2 4-20mA Current Sink
Chart recorder
+24VDC
0V
Alarm
level 1
J10
J11
J12
J13
J14
Alarm
Level 2
14 15 16 17 18 19 20 21 22 23 24
Channel 1 26 27 28 29 30 31 32 33 34 35 36Channel 2 38 39 40 41 42 43 44 45 46 47 48
Channel 350 51 52 53 54 55 56 57 58 59 60Channel 4
16 17 18LC 1 15
13
25
37
49
19 20
The Input Module can also sink current proportional to the detected gas level.
i.e. zero gas = 4mA
full scale = 20mA
The supply is derived from the external equipment.
NOTES
Switch ON J10 and J13
J10
J11
J12
J13
J14
NOTE: Incorrect jumper switch configuration can cause damage to the system.

LC-Series Controller: 1-4 Channel
ENMET
Manual Revision Date – June 13, 2017
Page | 16
Manual Part No. – 80003-050
5.2.3 1-5V Voltage Output
Alarm
level 1
J10
J11
J12
J13
J14
Alarm
Level 2
14 15 16 17 18 19 20 21 22 23 24Channel 1 26 27 28 29 30 31 32 33 34 35 36
Channel 2 38 39 40 41 42 43 44 45 46 47 48
Channel 350 51 52 53 54 55 56 57 58 59 60Channel 4
16 17 18
LC 1 15
13
25
37
49
19 20
Chart recorder
+ve
-ve
The LC Control Unit can provide a voltage output.
i.e. zero gas = 1V
full scale = 5V
This output is not ideal when transmitting a signal over a large distance. The resistance of a cable attached will cause a voltage
drop to occur.
Switch ON J11, J12 and J14.
J10
J11
J12
J13
J14
NOTE: Incorrect jumper switch configuration can cause damage to the system.

LC-Series Controller: 1-4 Channel
ENMET
Manual Revision Date – June 13, 2017
Page | 17
Manual Part No. – 80003-050
6.0 Maintenance
Routine Servicing
The MCU Control Unit will provide a reliable and fault free service but they rely upon sensible housekeeping and regular calibrations.
It is recommended that the system be calibrated at least once every six months. This can be arranged with Status Scientific Controls
as part of a maintenance contract.
Routine Inspection
It is advisable to periodically inspect the LC Control Unit Installation:
Check cables to ensure no damage has occurred.
Clean control unit casing using a clean cloth.
Clean detector heads using a clean DAMP cloth.
NOTE: Use of a dry cloth would constitute a static hazard.
Inspect detector heads and ensure the sensor housings aperture is not obstructed.
NOTE: Do not use solvents to clean the LCD display window on the control units or the detector heads
The time interval between routine inspections will depend upon the area in which the equipment is installed. A clean laboratory
installation may only require inspection at the time of calibration, whereas an installation in a particularly dirty environment may
require weekly inspections. It is the responsibility of the system engineer to assess the installation environment and determine the
frequency of routine inspections

LC-Series Controller: 1-4 Channel
ENMET
Manual Revision Date – June 13, 2017
Page | 18
Manual Part No. – 80003-050
7.0 Technical Data and Specifications
LC1
Type
LC1
Size (nominal) ‘mm’
188 x 160 x 106
Weight (approx.)
Operating Temp
-10ºC to +50ºC
Storage Temp
-20ºC to +50ºC
Humidity Range
0 to 95% R.H. Non-condensing
Input Voltage
18-28V DC, or 100-240V AC 50/60 Hz
Environmental Rating
IP65
User Interface
Display
Backlit 122 x 32 dot Liquid Crystal Display (LCD)
Keyboard
4 button multifunction keypad
LED Indications
Option 1
Red
Yellow
Green
Indicates alarm condition.
Indicates fault condition.
Indicates power ON
LED Indications
Option 2
Red
Red
Yellow
Indicates alarm level 1 condition.
Indicates alarm level 2 condition.
Indicates fault condition.
Input Modules
Number of channels
1 max
Signal Input
4-20mA Current Loop from 24V source.
4-20mA Current Loop sink to 0V.
3-Wire Pellistor Systems.
Analogue Output
4-20mA Current source proportional to detected signal.
4-20mA Current sink proportional to detected signal.
1-5V Voltage output proportional to detected signal.
3 – Relays
Contacts
Rating
1 relay assigned to alarm level 1.
1 relay assigned to alarm level 2.
1 relay assigned to fault condition.
Single Pole Changeover Contacts (voltage free).
5A 240V AC.
Power Supply
Fuse 1 (AC Input)
T1.0A
Fuse 2 (24VDC input)
T500mA
NOTE:All specifications stated in this manual may change without notice.

LC-Series Controller: 1-4 Channel
ENMET
Manual Revision Date – June 13, 2017
Page | 19
Manual Part No. – 80003-050
LC2
Type
LC2
Size (nominal) ‘mm’
280 x 219 x 156
Weight (approx.)
1.9Kg
Operating Temp
-10ºC to +50ºC
Storage Temp
-20ºC to +50ºC
Humidity Range
0 to 95% R.H. Non-condensing
Input Voltage
18-28V DC, or 100-240V AC 50/60
Environmental Rating
IP65
User Interface
Display
Backlit 122 x 32 dot Liquid Crystal Display (LCD)
Keyboard
4 button multifunction keypad
LED Indications
Option 1
Red
Yellow
Green
Indicates alarm condition.
Indicates fault condition.
Indicates power ON
LED Indications
Option 2
Green
Red
Red
Red
Yellow
Indicates power ON
Indicates alarm level 3 condition.
Indicates alarm level 2 condition.
Indicates alarm level 1 condition.
Indicates fault condition.
Input Modules
Number of channels
2 max
Signal Inputs x 2
4-20mA Current Loop from 24V source.
4-20mA Current Loop sink to 0V.
3-Wire Pellistor Systems.
Analogue Output x 2
4-20mA Current source proportional to detected signal.
4-20mA Current sink proportional to detected signal.
1-5V Voltage output proportional to detected signal.
6 – Relays
Contacts
Rating
1 relay assigned to alarm level 1, channel 1 & 2.
1 relay assigned to alarm level 2, channel 1 & 2.
1 relay assigned to common alarm level 3.
1 relay assigned to fault condition.
Single Pole Changeover Contacts (voltage free).
5A 240V AC.
Power Supply
Fuse 1 (AC Input)
T1.0A
Fuse 2 (24VDC input)
T500mA
NOTE:All specifications stated in this manual may change without notice.
This manual suits for next models
3
Table of contents
Popular Controllers manuals by other brands

Rockwell Automation
Rockwell Automation Allen-Bradley PowerFlex 23PFC installation instructions

Shihlin electric
Shihlin electric SA3 Series instruction manual

Panasonic
Panasonic S-LINK V user manual

Fluidwell
Fluidwell F131-P manual

Siemens
Siemens SIDOOR AT40 System manual

Alcor Micro
Alcor Micro AU9462 Technical reference manual

Eaton
Eaton Cutler-Hammer S701X25N3BP Instruction leaflet

impro
impro IMPROX SUPAGATE SGI911-1-1-GB-XX installation manual

Maestra
Maestra 8080 user manual

Fairford
Fairford XFE Series Basic Guide to the Installation and Operation

BIFFI
BIFFI EFS2000v4 Instructions and operating manual

Lexicon
Lexicon MC-12 - REV 4 user guide