Envirco Hospi-Gard IsoClean 800 User manual

Hospi-Gard®IsoClean®800 & IsoClean®400
HEPA Filtration Systems
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
ENVIRCO Technical Support: 800-884-0002

Hospi-Gard®IsoClean®800 & 400
HEPA Filtration System
2Innovators in Clean Air Technology | www.envirco.com
Installation, Operation, & Maintenance Manual
Table of Contents
Introduction....................................................................................................................... 3
Installation ........................................................................................................................ 4
Operation.......................................................................................................................... 5
Maintenance & Service..................................................................................................... 7
Troubleshooting................................................................................................................11
Wiring Diagram................................................................................................................ 12
Specications .................................................................................................................. 14
Replacement Parts.......................................................................................................... 15
Airow Measurement & Testing....................................................................................... 17
Air Change Rates ............................................................................................................ 17
Limited Warranty ..............................................................................................................18
Contact Envirco ................................................................................................................18

Hospi-Gard®IsoClean®800 & 400
HEPA Filtration System
3Innovators in Clean Air Technology
Installation, Operation, & Maintenance Manual
■Introduction
Description
The Hospi-Gard® IsoClean® is a portable, self-contained high eciency particulate air (HEPA) ltration system with an
optional ultraviolet lamp that helps to disinfect the lter face. The IsoClean® is designed to easily and economically create
a negative pressure isolation room that will meet OSHA and CDC TB guidelines. The IsoClean® can be used as a positive
pressure clean air recirculating system in clinics, waiting rooms, hospital emergency rooms and other conned areas or as a
partial or complete exhausting system to create a negative pressure isolation room for possible use with patients known or
suspected of having TB, SARS, COVID-19, or other infectious diseases. The IsoClean® is available in two dierent sizes: the
IsoClean® 400 and the IsoClean® 800. As a recirculating unit, the IsoClean®’s powerful motor/blower can deliver up to 370
CFM (628 m3/hr) for the IsoClean® 400 and up to 800 CFM (1360 m3/hr) for the IsoClean® 800 to provide a large number
of room air changes per hour to minimize the spread of airborne diseases to patients and health care workers. As a negative
pressure unit, the air passing through the HEPA lter is ltered of 99.99% of particles at 0.3 micron and may be exhausted
directly to the exterior through a window, or through a wall, simply by connecting exible ducting to the 6 in. (152 mm) collar
located on the top of the IsoClean®.
Features
• Low Cost Isolation Room
The IsoClean® is an easy and economical solution for creating a negative pressure isolation room. Simply roll the
IsoClean® into a standard room, connect exible ducting to the 6 in. (152 mm) collar on the top of the unit for partial
exhaust or to the optional 8 in. (204 mm) anged collar for total exhaust, and vent the puried air to the exterior through
a window or wall.
• Flexible Applications
The versatile IsoClean® can be used as a clean air recirculating unit, a negative pressure unit, or as a split system
to create both negative pressure and clean air recirculation by simultaneously exhausting some of the air out while
recirculating the remainder back into the room.
• Small and Portable
The IsoClean® can be rolled from one room to another and easily ts into areas with limited oor space.
• Simple Maintenance
Both HEPA lter and prelter are easily accessible for replacement by authorized personnel.
• Adjustable Airow
The IsoClean® provides eective air ltration for a wide variety of room sizes. The IsoClean® 400 utilizes a solid state
speed control with airows ranging from 70 to 370 CFM (118 to 628 m3/hr). The IsoClean® 800 utilizes a three position
switch with airows ranging from 560 to 800 CFM (951 to 1360 m3/hr).
• Low-High Clean Air Circulation Pattern
Room air, along with airborne contaminants, is drawn into the intake grill at the bottom while the puried air is discharged
at a high velocity from the exhaust grill located at the top of the IsoClean® to generate a sweeping, low-to-high air
circulation pattern with adequate “reach” to optimize the clean breathing zone for patient and sta.
• Quiet Operation
52 dBA on low, 56 dBA on medium, and 60 dBA on high speed measured 30 in. (762mm) from face of the unit.
Applications
Hospital
• Negative Pressure Rooms
• Emergency Rooms
• Waiting Rooms
• Sputum Induction
• Aerosol Pentamidine Treatment
• Intensive Care Units
• Bronchoscopy Rooms
• Renal Dialysis Rooms

Hospi-Gard®IsoClean®800 & 400
HEPA Filtration System
4Innovators in Clean Air Technology | www.envirco.com
Installation, Operation, & Maintenance Manual
Other
• Clinics
• Physician Oces
• Correctional Facilities
• Nursing Homes
• Homeless Shelters
• Addiction Recovery Center
Options
• IsoClean® with UV
• IsoClean® with ULPA Filter Upgrade
• Minihelic Pressure Gauge
• Keylock ON/OFF Switch
• 220 V, 50/60 Hz Unit Available
• 8 in. (203 mm) 100% Exhaust Collar Kit
■Installation
Unpacking Instructions
1. The Hospi-Gard® lsoClean® is shipped in an open-framed crate.
The module should be inspected for exterior shipping damage
immediately upon arrival. If any damage is observed, a claims
report should be completed and promptly led with the responsible
carrier.
2. Uncrate and remove all packing material. Examine the unit for
internal damage. lf damage is discovered inside the crating, le
a claim with the responsible carrier immediately. The shipping
components list and actual material received should be compared and any shortages reported to Envirco immediately.
Assembly
1. The Hospi-Gard® lsoClean® is shipped completely assembled from the factory and requires no assembly. Every unit is
tested prior to shipment to verify airow and that the unit is leak-free.
2. Place the unit in its nal operating position.
3. Lock the wheel locks on the casters to keep the unit from accidental repositioning.
Initial Start-Up
NOTE:THECDCREQUIRESTHATQUANTITATIVELEAKAGEANDFILTERPERFORMANCETESTSBEPERFORMED
AT THE INITIAL INSTALLATION AND EVERY TIME THE FILTER IS CHANGED OR MOVED. TESTS SHOULD BE
REPEATEDEVERYSIXMONTHSORTHEAPPROPRIATETIMEFRAMETHATISREQUIREDFORTHEAPPLICATION.
THE FACTORY TESTS SHOULD NOT BE SUBSTITUTED FOR THE INITIAL TEST.
CAUTION AND WARNINGS
READ AND SAVE THESE INSTRUCTIONS
WARNING: To reduce the risk of re, electrical
shock, or injury to persons, observe the following.
1. Installation work and electrical wiring
must be done by a qualied person(s)
in accordance with all applicable codes
and standards, including re-rated
construction.
2. Service to this equipment should be
performed by an authorized technician
trained and experienced in performance
evaluation and maintenance of clean air
equipment.
3. Before servicing or cleaning unit, unplug
the unit power cord from outlet to
prevent power from being switched on
accidentally.
4. This unit may have UV lamps. Eye
damage may result from direct exposure
to the light. Take UV radiation protective
measures for personnel during service.
5. Use this unit only in the manner intended
by the manufacturer.

Hospi-Gard®IsoClean®800 & 400
HEPA Filtration System
5Innovators in Clean Air Technology
Installation, Operation, & Maintenance Manual
■Operation
Initial Start-Up
1. Connect the power cord to a standard 115-Volt, Single Phase, 60 Hertz, or 220-Volt, 50/60 Hertz, grounded power source.
Verify that the circuit is sized to provide sucient amperage as noted on the Hospi-Gard® lsoClean® data plate.
2. Locate the “ON/OFF” switch on the right side of the unit. The switch is a maintain contact rocker type.
3. Turn the Hospi-Gard® lsoClean® unit on by pressing downward on the raised portion of the rocker switch. A light whirring
sound will be heard as the motor starts. Within 5 to 10 seconds, the module will start to provide clean air into the environment.
Speed Adjustment
Note: The Hospi-Gard® IsoClean® unit is set on high speed at the factory.
1. To change speeds, remove the exhaust grille by pulling down and lifting out.
2. Turn the 3-speed switch (or solid state speed control) to the desired setting on the IsoClean® 800 or 400.
3. Replace the exhaust grille when nished.
Filter Change Indicator
1. Locate the airow indicator on the right side of the unit above the “ON/OFF” switch. On high speed, the light will turn on
when there is insucient pressure, indicating the need for a lter change. It is recommended to change prelter. If the
lter change indicator light is still illuminated, it is recommended to replace the HEPA lter. The airow indicator should
not be used as the only guide for when a lter change is necessary. The unit should be checked at each use to ensure
recommended room air changes per hour are being met.
2. The lter change indicator light can be adjusted by adjusting the pressure switch which can be seen on the nack panel of
the IsoClean®. For setting the light, block the lower intake grill approximately 75% while the unit is on high speed. The
pressure switch should be set to have the light icker while covered 75%. Once the restriction is removed, the light should
go o. If the intake grille is completely covered, the light should be solid on.
3. The air velocity generated by the unit may be checked using an airow measurement device. The volume of air entering
the lower intake grille should be approximately 560 CFM (951 m3/h) on low, 690 CFM (1172 m3/h) on medium, and
800 CFM (1359 m3/h) on high with a new lter for the IsoClean® 800. Air volume on the IsoClean® 400 should be
approximately 70 CFM (118 m3/h) to 370 CFM (628 m3/h) depending on the position of the speed control with a new lter.
Recirculation Mode
1. The Hospi-Gard® IsoClean® unit is set at the factory on the 100% air recirculation mode.
2. The room air change rate of the unit will depend on both the Hospi-Gard IsoClean speed setting and the size of the room.
See Air Change Rates on page 17 for representative room air changes per hour (ACH).
3. For maximum recirculation eciency, the unit should be placed between the entry door and the patient’s bed or the activity
area (see Figure 1 below). However, the unit will function eectively at other locations within the room.

Hospi-Gard®IsoClean®800 & 400
HEPA Filtration System
6Innovators in Clean Air Technology | www.envirco.com
Installation, Operation, & Maintenance Manual
Partial Exhaust/Recirculation Mode
Note: The lsoClean® units come with a removable Exhaust Cover Plate and a removable 6-inch (152mm) Duct Collar for
attachment to exhaust ducting (not included) to create a negative pressure room. lf the Exhaust Cover Plate is not removed,
the lsoClean® units will operate in the 100% recirculation mode.
1. Remove the Exhaust Cover Plate located on top of the lsoClean® unit by taking o the four (4) screws and plastic caps
used to secure the cover to the lsoClean® exhaust port.
2. Remove the 6-inch (152mm) duct collar underneath the top cover and ip the collar over.
3. Attach exhaust ducting (not included) onto the collar and fasten tightly with a round hose clamp (not included).
4. Mount the duct collar with ducting onto the lsoClean® exhaust port using the four (4) screws that originally held the cover
plate. Note: Keep the top plate and plastic washers for re-assembly when needed.
5. The HEPA ltered exhaust air can now be vented to the outside or returned to the main HVAC system1. lf the unit is ducted
to an exhaust duct rather than directly to the outside, it must be veried that the exhaust duct is capable of handling the
exhaust air expelled by the unit.
6. The lsoClean® is designed to exhaust 100-300 CFM for the 800 and 25-150 CFM for the 400 at the 6-inch exhaust port. lt
is recommended that the unit be set on the high-speed setting when operating in this mode to achieve maximum exhaust
and negative pressure. At this setting, the lsoClean® will exhaust approximately 300 CFM (510 m3/h) and recirculate 500
CFM (850 m3/h) for the 800 and exhaust approximately 150 CFM (254 m3/h) and recirculate 220 CFM (373 m3/h) for the
400.
Total Exhaust Mode (Negative Pressure)
CAUTION: To reduce risk of re and to properly exhaust air, be sure to duct air outside - Do not vent exhaust air into
spaces within walls or ceilings or into attics, crawl spaces, or garages.
CAUTION: For General Ventilating Use Only. Do Not Use to Exhaust Hazardous or Explosive Materials and Vapors.
Note: The cover plate must be securely attached to the top of the lsoClean® for the unit to run in the 100% exhaust mode.
An optional 8-inch (203mm) Exhaust Collar with Flange is available to convert the lsoClean® unit to the 100% exhaust mode.
1. Remove the front exhaust grille by pulling down and lifting out.
2. Place the optional 8-inch (203mm) exhaust collar over the opening where the grille was removed and attach with the
screws included with the 8-inch collar.
3. Attach exible exhaust duct (not included) over the 8-inch collar and fasten tightly with a round hose clamp (not included).
4. The HEPA ltered exhaust air can now be vented to the outside or returned to the main HVAC system1. lf the unit is ducted
to an exhaust duct rather than directly to the outside, it must be veried that the exhaust duct is capable of handling the
exhaust air expelled by the unit.
Negative Pressure
NOTE: CDC GUIDELINES RECOMMEND THAT ROOMS USED FOR NEGATIVE PRESSURE ISOLATION SHOULD
BE SINGLE PATIENT ROOMS WITH NEGATIVE PRESSURE RELATIVE TO THE CORRIDOR OR OTHER AREAS
CONNECTED TO THE ROOM. THE MINIMUM PRESSURE DIFFERENCE NECESSARY TO ACHIEVEAND MAINTAIN
NEGATIVE PRESSURE THAT WILL RESULT IN AIRFLOW INTO THE ROOM IS 0.01 INCH W.G. (2.5PA) (A HIGHER
PRESSURE IS PREFERRED). TO ACHIEVE THIS, THE EXHAUST FLOW SHOULD BE 10% OR 50 CFM (85 M3/H)
GREATER THAN THE SUPPLY (WHICHEVER IS GREATER).
Achieving Negative Pressure
1. The lsoClean® unit is designed to exhaust 100-300 CFM (800 unit) or 25-150 CFM (400 unit) when the 6-inch (152.4mm)
exhaust collar is used. lt is recommended that the unit be set on the high-speed setting when operating in this mode to
achieve maximum exhaust and negative pressure.
2. lf an exhaust volume greater than 300 CFM (800 unit) or 150 CFM (400 unit) is required to create a negative pressure
room, the optional 8-inch (203.2 mm) 100% exhaust collar should be used.
3. The attachment of ductwork to the exhaust port decreases the air volume exhausted through the port. The magnitude of the
1 CDC recommends that air from negative pressure rooms be exhausted to the outside in accordance with federal, state, local or country regulations.
The air should not be recirculated into the general ventilation. ln certain cases in existing facilities, recirculation of air into the general ventilation system
is unavoidable and, in such cases, CDC guidelines state that HEPA lters should be installed in the exhaust duct leading from the room to the general
ventilation system.

Hospi-Gard®IsoClean®800 & 400
HEPA Filtration System
7Innovators in Clean Air Technology
Installation, Operation, & Maintenance Manual
decrease varies depending on the length and type of duct as well as unit conguration.
NOTE: IT IS THE RESPONSIBILITY OF THE PURCHASER, AND NOT ENVIRCO, TO ENSURE THE ROOM IN WHICH
THE UNIT IS USED IS IN COMPLIANCE WITH CDC GUIDELINES2FOR A NEGATIVE PRESSURE ISOLATION ROOM
AND MONITORED TO ENSURE ITS CONTINUING PERFORMANCE.
Diculty Achieving Negative Pressure
The equipment may not be able to achieve or maintain negative pressure in conformance with the CDC Guidelines2due to
building ventilation of rooms or air leakage. The room should be inspected for air leakage through doors, windows, plumbing,
and wall penetrations. Appropriate corrective action should be taken to seal leaks.
■Maintenance & Service
2 CDC. Guidelines for Preventing the Transmission of Tuberculosis in Healthcare Facilities, 1994. MMWR, October 28, 1994; 43 (No. RR-13.)

Hospi-Gard®IsoClean®800 & 400
HEPA Filtration System
8Innovators in Clean Air Technology | www.envirco.com
Installation, Operation, & Maintenance Manual
CAUTION: PROPER PROTECTIVE EQUIPMENT AND MEASURES MUST BE USED AT ALL TIMES DURING UNIT
CLEANING AND MAINTENANCE. CHECK WITH YOUR SAFETY OFFICE TO ASSURE THE CLEANING SOLUTIONS,
PROTECTIVE EQUIPMENT (DISPOSABLE HOSPITAL GOWN, HEPA RESPIRATOR, PROTECTIVE GLOVES) AND
PROTOCOLS FOLLOWED COMPLY WITH YOUR FACILITY’S AND CDC GUIDELINES.
CAUTION:DISCONNECTTHEUNITFROMTHEELECTRICALPOWERSOURCEBEFOREATTEMPTINGSERVICE.DONOT
WORK INSIDETHE ISOCLEAN UVWITH THEUV LIGHT ON. PROPERREPLACEMENT OFUV CONTAINMENT BAFFLES
AFTERMAINTENANCEISMANDATORYTOMAINTAINSAFESHORT-TERMAND LONG-TERMUVEXPOSURELEVELS.
Cleaning the Unit
1. Periodic Cleaning of the unit may be done with a mild disinfecting soap and water solution. A 1% or 1/100 dilution of bleach
is an optional disinfectant3.
2. Exterior cabinet cleaning must be performed with the unit running. Wipe the exterior of the unit with a damp sponge or
cloth, paying particular attention to the prelter intake grille.
3 Rutala WA, APlC guideline for selection and use of disinfectants, Am J lnfect Control 1996 Aug ; 24(4): 313-42.

Hospi-Gard®IsoClean®800 & 400
HEPA Filtration System
9Innovators in Clean Air Technology
Installation, Operation, & Maintenance Manual
Prelter Replacement
1. The prelter should be replaced every 60 to 90 days. Regularly replacing the prelter will maximize the life of the HEPA lter.
The lsoClean comes standard with an anti-microbial pleated prelter.
2. Clean the unit as described in the prevous section.
THE FOLLOWING STEPS MUST BE PERFORMED WITH THE UNIT (FAN) RUNNING:
3. Spray a mist of phenolic disinfectant such as “Amply “ or “Lysol” into the air intake grille.
4. Remove the four (4) screws from the face of the intake grille and pull the grille out.
5. lnsert gloved hand into a red plastic, medical waste disposal bag. Grasp the top portion of the prelter with bagged hand
and gently pull outward. The airow of the unit will oer a resistance to pulling the prelter out.
6. Turn the bag inside out over the prelter then seal the bag for containment.
7. lnstall a new prelter and secure the grille by following step these instructions in reverse order of removal.
CAUTION: APPROPRIATE DECONTAMINATION PROCEDURES (SEE PAGE 11) MUST BE FOLLOWED PRIOR TO
REMOVALOFTHEACCESSPANELSTOREPLACETHEHEPAFILTEROROTHERPARTS.CONTACTYOURSAFETY
OFFICE TO ASSURE IT CONFORMS TO YOUR FACILITY’S PROTOCOL.
Removal of Front and Rear Panels
1. Remove the front access panel by taking o the screw covers and removing the four (4) screws. The front panel may now
be lifted o.
2. Remove the 18 screws securing the rear access panel. The rear panel may now be lifted o.
Primary Filter Replacement
The CDC recommends that in any application, HEPA lters should be maintained meticulously and should be carefully installed
by adequately trained personnel wearing an appropriate respirator. A regular maintenance program should include procedures
for installation, removal and disposal of lter elements and a program to monitor the HEPA lter for possible leakage and for
lter loading.
The expected HEPA lter life should range from eighteen (18) months to two (2) years depending on the environment and
prelter maintenance schedule.The lter indicator light will give a warning of lter loading by ickering on high speed. When
the light stays on at high speed, the prelter should rst be changed. If the light stays on after prelter replacement, the HEPA
lter is recommended to be changed.
1. Remove the front access panel by following the instructions under removal of front and rear panels.
2. For IsoClean® UV units, follow the steps in the below section to remove the UV Light Assembly.
3. Remove the six (6) bolts and clamps holding the HEPA lter in place.
4. In many cases, lters must be decontaminated before removal. See decontamination process for more information. Tilt
the top of the lter outward and slip a plastic biohazard bag over the top of the lter, and then wrap the bag over the bottom
of the lter.
5. Seal the bag for containment. Note: It may be necessary to use two (2) biohazard bags to fully contain the lter.
6. Remove the new HEPA lter from its container and install it in the reverse order of removal. Care must be taken when
handling the lter. Do not bump or squeeze the lter as this may damage the lter and render it non-eective.
Removal of the UV Light Assembly for the lsoClean®UV
WARNING - Skin or eye damage may result from directly viewing the light produced by the lamp in this apparatus.
Always disconnect power before relamping or servicing. Replace lamp with lamp TUV 15W SLV, manufactured by
Philips for IsoClean® 400. Replace lamp with TUV 30W SLV, manufactured by Phillips for IsoClean®800.
1. Remove the front access panel by following the instructions under removal of front and rear panels. Set the front access
panel to the side.
2. Disconnect the three-pin connector located near the UV lamp ballast and remove the wires from the wire routing clamp.
3. Remove the ve (5) screws on the left hand UV containment bae, and then lift the bae out of the unit and set it to the
side. Repeat this for the right hand UV containment bae. (Note: This is for IsoClean® 800 model only)

Hospi-Gard®IsoClean®800 & 400
HEPA Filtration System
10 Innovators in Clean Air Technology | www.envirco.com
Installation, Operation, & Maintenance Manual
4. Remove the two (2) screws that fasten it with the top of the UV lamp assembly.
5. Remove the remaining two (2) screws that fasten the mounting bracket to the cabinet and set the mounting bracket to
the side.
6. Remove the two (2) screws fastening the UV lamp assembly to the bottom of the cabinet.
7. Carefully remove the UV lamp assembly taking care not to touch the glass tube.
The expected life of the UV light tube is 9,000 hours. To remove the UV light follow the below instructions.
1. Rotate the light tube 90 degrees in either direction to enable removal (you should feel tension on the tube release). To
remove the light tube, carefully pull away from the UV lamp assembly, towards the HEPA lter. Dispose of the light tube
(or recycle) following local guidelines.
2. Use Clean latex gloves to ensure that the new light tube remains clean. Clean the new light tube using a cloth dampened
with a 10% alcohol (or ammonia) and water solution. To replace, reverse the order of removal.
Power Cord
1. With the back panel removed, unplug the white connector on the power cord.
2. Remove nut on ground wire.
3. Remove strain relief on the side of the unit.
4. Remove the old cord and replace with the new one by following the steps above in reverse order.
On/O Switch
1. With the back panel removed, unplug the white connector on the switch and squeeze the snap-in legs to remove switch
from side of the unit.
2. Install new switch by snapping it into the cutout and then connecting it to the white connector.
Speed Control Switch
1. Remove the exhaust grille by pushing down and lifting out.
2. Remove J-box screws.
3. Remove knob.
4. Remove switch screws.
5. Unplug connecting wires and replace with the new switch by following the steps above in reverse order.
Capacitor
1. With the back panel removed, remove one screw from capacitor strap. Note: Make sure to provide ample time for
capacitor to discharge.
2. Slide capacitor out.
3. Remove the rubber boot and disconnect wires.
4. Replace with the new capacitor by following the steps above in reverse order.
Filter Change Indicator Light
1. With the back panel removed, unplug the two (2) wires and push out the lter indicator light from the inside of the unit.
2. Replace the lter indicator light by following the step above in reverse order.
Motor Assembly Removal
1. The motor can only be removed from the front side of the unit. First ensure that the front panel, UV light assembly (for
UV units), and lter are removed. Refer to the removal of front and rear panels, primary lter replacment, and removal of
the UV light assembly sections.
2. Remove the screw fastening the green motor ground wire to the motor panel.
3. Remove the screw fastening the black wire clamp to the motor panel.
4. Most of the motor wires feed into a quick-connect socket. Disconnect this socket from its mating half.
5. Remove the six (6) screws fastening the motor ring to the panel and remove the motor assembly from the unit.
CAUTION:WHENREINSTALLINGTHEMOTORENSURETHATITDOESNOTTOUCHORPUNCTURETHEHEPAFILTER.

Hospi-Gard®IsoClean®800 & 400
HEPA Filtration System
11Innovators in Clean Air Technology
Installation, Operation, & Maintenance Manual
Relocating a Contaminated Unit
NOTE: USE PROPER PROTOCOL, GOWNING, AND PROTECTIVE MEASURES.
1. lf an existing unit is to be placed into storage for an extended period of time, remove and replace the prelter.
2. Turn the unit o and disconnect from power source.
3. Clean the exterior surfaces of the unit.
4. Unlock caster wheel locks and move unit to its new location.
Unit Decontamination
NOTE: USE PROPER PROTOCOL, GOWNING, AND PROTECTIVE MEASURES DURING UNIT DECONTAMINATION.
Should decontamination of the unit be required, it is recommend to follow basic guidelines and a modied prodedure based on
Decontamination of Large Spaces located in Biosafety in Microbiological and Biomedical Laboratories, 5th Ed. from the CDC.
Conrm with appropriate Biosafety and lndustrial Safety Professionals that the procedures meet your facility’s guidelines.
Decontamination should be performed by specialists with proper training and protective equipment.
The primary methods of space decontamination are:
• Paraformaldehyde Decontamination
• Hydrogen Peroxide Vapor
• Chlorine Dioxide Gas
After decontamination process has been completed, remove the HEPA lter. The lter can now be disposed of as general
waste.
Phenolic Decontamination
ln facilities where the above decontamination procedures are prohibited or not feasible, the unit can be disinfected by the
following procedure.
1. Remove the prelter.
2. After the intake grille and prelter are removed, turn the unit on, and with the unit running, spray a mist of phenolic
disinfectant such as Amphyl or Lysol into the air intake opening. Approximately two (2) to ve (5) ounces is adequate.
3. Remove the HEPA lter. Since the lter has not been decontaminated by the methods above, the lter should be disposed
of properly.
■Troubleshooting
Before attempting to service and repair the unit, use proper protocol and follow appropriate decontamination procedures
described in the following sections:
• Cleaning the Unit
• Prelter Replacement
• Relocating a Contaminated Unit
• Unit Decontamination
Inoperative Air Flow
1. Conrm that the power cord is plugged into the building receptacle and power is present.
2. Conrm that the unit power switch is turned “ON”.
3. Conrm the speed control is not in a position that is preventing airow. Recommended to change the position for
conrmation.
4. Check switch and internal wiring per Wiring Diagram (Section 6). Replace or repair faulty component(s).
5. Check the motor and replace if necessary.
6. Check the motor capacitor and replace if necessary. Recommended to change motor capacitor with motor replacement.

Hospi-Gard®IsoClean®800 & 400
HEPA Filtration System
12 Innovators in Clean Air Technology | www.envirco.com
Installation, Operation, & Maintenance Manual
Low Air Flow
1. Check prelter for obstruction and remove obstruction as necessary.
2. Replace dirty prelter media.
3. Switch the speed control to the next higher airow setting.
4. Check power supply for proper voltage, amperage and distribution frequency.
5. Check for down-stream obstructions or erratic isolation room ventilation balance.
6. Replace HEPA lter if the air velocity remains low after checking all other causes of low air ow.
High Air Flow
1. Adjust the speed control down to the next lowest setting.
2. Verify all lters are properly in place.
Excessive Contamination
1. Replace HEPA lter.
2. Verify the HEPA lter is installed properly.
■Wiring Diagrams
IsoClean® 800 Wiring Diagram

Hospi-Gard®IsoClean®800 & 400
HEPA Filtration System
13Innovators in Clean Air Technology
Installation, Operation, & Maintenance Manual
■Wiring Diagrams Cont.
IsoClean® 400 Wiring Diagram

Hospi-Gard®IsoClean®800 & 400
HEPA Filtration System
14 Innovators in Clean Air Technology | www.envirco.com
Installation, Operation, & Maintenance Manual
■Specifications
IsoClean® 800 (10850 for 120V/10921 for 220V)
• Dimensions: 62.25 H x 23.66 W x 15.75 D (in.), 1581 H x 601 W x 400 D (mm)
• Weight: 250 lbs. (113 kg) ship weight
• Power Requirements: 6.9 A at 120V, 60 Hz, Single Phase, 3.5 A at 220V, 60 Hz, Single Phase
• Airow: 560 CFM (951 m3/hr) on Low ±10%, 690 CFM (1172 m3/hr) on Medium ±10%, 800 CFM (1359 m3/hr) on High ±10%
• HEPA Filter Media: 99.99% at 0.3 micron minimum eciency
• Prelter: MERV8 multi-pleat anti-microbial pleated prelter with frame
• Motor: 1/3 HP (0.25 kW), direct drive, three-speed, continuous duty
• Exhaust Port: 6-lnch (152.4mm) Duct Collar
IsoClean® 800 UV (10850-005 for 120V/10921-004 for 220V)
• Dimensions: 62.25 H x 23.66 W x 19.75 D (in), 1581 H x 601 W x 502 D (mm)
• Weight: 285 lbs.(129 kg) ship weight
• Power Requirements: 8.0 A at 120V, 60 Hz, Single Phase, 4.0 A at 220V, 60 Hz, Single Phase
• Airow: 560 CFM (951 m3/hr) on Low ±10%, 690 CFM (1172 m3/hr) on Medium ±10%, 800 CFM (1359 m3/hr) on High ±10%
• HEPA Filter Media: 99.99% at 0.3 micron minimum eciency
• Prelter: MERV8 multi-pleat anti-microbial pleated prelter with frame
• Motor: 1/3 HP (0.25 kW), direct drive, three-speed, continuous duty
• Exhaust Port: 6-inch (152.4mm) Duct Collar
IsoClean® 400 (10950 for 120V/10960 for 220V)
• Dimensions: 38.25 H x 23.66 W x 15.75 D (in.), 972 H x 601 W x 400 D (mm)
• Weight: 153 lbs. (70 kg) ship weight
• Power Requirements: 2.8 A at 120V, 60 Hz, Single Phase, 1.5 A at 220V, 60 Hz, Single Phase
• Airow: 70 CFM (118 m3/hr) at minimum ±10% and 370 CFM (628 m3/hr) on High ±10%
• HEPA Filter Media: 99.99% at 0.3 micron minimum eciency
• Prelter: MERV8 multi-pleat anti-microbial pleated prelter with frame
• Motor: 1/4 HP (0.19 kW), direct drive, three-speed, continuous duty
• Exhaust Port: 6-lnch (152.4mm) Duct Collar
IsoClean® 400 UV (10950-005 for 120V/10921-004 for 220V)
• Dimensions: 38.25 H x 23.66 W x 19.75 D (in), 972 H x 601 W x 502 D (mm)
• Weight: 173 lbs.(79 kg) ship weight
• Power Requirements: 2.9 A at 120V, 60 Hz, Single Phase, 1.6 A at 220V, 60 Hz, Single Phase
• Airow: 70 CFM (118 m3/hr) at minimum ±10% and 370 CFM (628 m3/hr) on High ±10%
• HEPA Filter Media: 99.99% at 0.3 micron minimum eciency
• Prelter: MERV8 multi-pleat anti-microbial pleated prelter with frame
• Motor: 1/4 HP (0.19 kW), direct drive, three-speed, continuous duty
• Exhaust Port: 6-inch (152.4mm) Duct Collar

Hospi-Gard®IsoClean®800 & 400
HEPA Filtration System
15Innovators in Clean Air Technology
Installation, Operation, & Maintenance Manual
■Replacement Parts
IsoClean®800
Part No. Description Quantity
10850 IsoClean® 800 120V 1
10921 IsoClean® 800 220V 1
S62954-
WIRED Motor, 1/3 HP, 3-Speed, 115V 1
S63093-
WIRED Motor, 1/3 HP, 3-Speed, 220V 1
S24000 Motor/Blower Assembly, 120V 1
S24000-002 Motor/Blower Assembly, 220V 1
63252 Air Inlet Ring 1
63270 Blower Wheel 1
63775 3-Speed Switch 1
63779-002 Switch Knob 1
23888 Power Cord - 120V 1
23888-002 Power Cord - 220V 1
140204-002 Motor Capacitor 15 mfd, 120V 1
60078 Motor Capacitor 5 mfd, 220V 1
63027 Air Pressure Switch 1
61400 Filter Indicator Light 1
63352 Prelter 1
S69391-001 HEPA Filter 1
S69391-002 ULPA Filter 1
62973 Caster 2
62974 Caster with Brake 2
257738-001 6-inch Duct Collar 1
257633-001 Exhaust Cover Plate for IsoClean 1
11055 8-inch A/C Collar with Flange for 100% 1
267745-001 Intake Grille - Painted 1
37453 Exhaust Grille 1
61528 Minihelic Gauge 1
63360 Keylock 1
IsoClean®800 UV
Part No. Description Quantity
10850-005 IsoClean® 800 120V UV 1
10921-004 IsoClean® 800 220V UV 1
S62954-
WIRED Motor, 1/3 HP, 3-Speed, 115V 1
S63093-
WIRED Motor, 1/3 HP, 3-Speed, 220V 1
S24000 Motor/Blower Assembly, 120V 1
S24000-002 Motor/Blower Assembly, 220V 1
63252 Air Inlet Ring 1
63270 Blower Wheel 1
63775 3-Speed Switch 1
63779-002 Switch Knob 1
23888 Power Cord - 120V 1
23888-002 Power Cord - 220V 1
140204-002 Motor Capacitor 15 mfd, 120V 1
60078 Motor Capacitor 5 mfd, 220V 1
63027 Air Pressure Switch 1
61400 Filter Indicator Light 1
63352 Prelter 1
S69391-001 HEPA Filter 1
S69391-002 ULPA Filter 1
62973 Caster 2
62974 Caster with Brake 2
257738-001 6-inch Duct Collar 1
257633-001 Exhaust Cover Plate for IsoClean 1
11055 8-inch A/C Collar with Flange for 100% 1
267745-001 Intake Grille - Painted 1
37453 Exhaust Grille 1
24392-001 UV Bae Assembly 1
60265 Germicidal Lamp 1
61528 Minihelic Gauge 1
63360 Keylock 1

Hospi-Gard®IsoClean®800 & 400
HEPA Filtration System
16 Innovators in Clean Air Technology | www.envirco.com
Installation, Operation, & Maintenance Manual
■Replacement Parts (continued)
IsoClean®400
Part No. Description Quantity
10950 IsoClean® 400 120V 1
10960 IsoClean® 400 220V 1
S267793-
001 Motor, 1/4 HP, 3-Speed, 115V 1
S267793-
002 Motor, 1/4 HP, 3-Speed, 220V 1
S24332-015 Motor/Blower Assembly, 120V 1
S24332-016 Motor/Blower Assembly, 220V 1
63252 Air Inlet Ring 1
63270 Blower Wheel 1
271806-001 Speed Control, 120V 1
271806-002 Speed Control, 220V 1
23888 Power Cord - 120V 1
23888-002 Power Cord - 220V 1
61485 Motor Capacitor 10 mfd, 370VAC 1
63027 Air Pressure Switch 1
61400 Filter Indicator Light 1
63352 Prelter 1
S69391-005 HEPA Filter 1
S69391-006 ULPA Filter 1
62973 Caster 2
62974 Caster with Brake 2
257738-001 6-inch Duct Collar 1
257633-001 Exhaust Cover Plate for IsoClean 1
11055 8-inch A/C Collar with Flange for 100% 1
267745-001 Intake Grille - Painted 1
37453 Exhaust Grille 1
61528 Minihelic Gauge 1
63360 Keylock 1
IsoClean®400 UV
Part No. Description Quantity
10950-005 IsoClean® 400 120V UV 1
10960-005 IsoClean® 400 220V UV 1
S267793-
001 Motor, 1/4 HP, 3-Speed, 115V 1
S267793-
002 Motor, 1/4 HP, 3-Speed, 220V 1
S24332-015 Motor/Blower Assembly, 120V 1
S24332-016 Motor/Blower Assembly, 220V 1
63252 Air Inlet Ring 1
63270 Blower Wheel 1
271806-001 Speed Control, 120V 1
271806-002 Speed Control, 220V 1
23888 Power Cord - 120V 1
23888-002 Power Cord - 220V 1
61485 Motor Capacitor 10 mfd, 370VAC 1
63027 Air Pressure Switch 1
61400 Filter Indicator Light 1
63352 Prelter 1
S69391-005 HEPA Filter 1
S69391-006 ULPA Filter 1
62973 Caster 2
62974 Caster with Brake 2
257738-001 6-inch Duct Collar 1
257633-001 Exhaust Cover Plate for IsoClean 1
11055 8-inch A/C Collar with Flange for 100% 1
267745-001 Intake Grille - Painted 1
37453 Exhaust Grille 1
60265-002 Germicidal Lamp 1
61528 Minihelic Gauge 1
63360 Keylock 1
For Isoclean 400 units purchased prior to February 2021, contact the factory for verication of correct motor, motor/blower,
and capacitor parts.

Hospi-Gard®IsoClean®800 & 400
HEPA Filtration System
17Innovators in Clean Air Technology
Installation, Operation, & Maintenance Manual
■Airflow Measurement & Testing
■Air Change Rates
Room Size (Room Air Volume) in Feet
Isoclean Model Fan Speed 10 x 10 x 8
(800 ft3)
12 x 12 x 8
(1152 ft3)
12 x 15 x 8
(1440 ft3)
12 x 15 x 9
(1620 ft3)
15 x 15 x 8
(1800 ft3)
15 x 20 x 8
(2400 ft3)
20 x 20 x 8
(3200 ft3)
800 Low
560 CFM 42 ACH 29 ACH 23 ACH 20 ACH 18 ACH 14 ACH 10 ACH
800 Medium
690 CFM 51 ACH 35 ACH 28 ACH 25 ACH 23 ACH 17 ACH 12 ACH
800 High
800 CFM 60 ACH 41 ACH 33 ACH 29 ACH 26 ACH 20 ACH 15 ACH
400 Min
70 CFM 5 ACH 3 ACH 2 ACH 2 ACH 2 ACH 1 ACH 1 ACH
400 Max
370 CFM 27 ACH 19 ACH 15 ACH 13 ACH 12 ACH 9 ACH 6 ACH

Hospi-Gard®IsoClean®800 & 400
HEPA Filtration System
18 Innovators in Clean Air Technology | www.envirco.com
Installation, Operation, & Maintenance Manual
■Limited Warranty
a) Unless otherwise set forth in the Sales Conrmation, Seller warrants to Buyer, for a period of twelve (12) months following
the date of shipment to the Delivery Location (the “Warranty Period”), that the Goods will be free from defects in material
and workmanship. Notwithstanding the foregoing, the Warranty Period for consumable Goods shall in no event exceed
recommended replacement intervals set forth in the Instructions (hereinafter dened). If, prior to the expiration of the Warranty
Period, Buyer informs Seller in writing of any breach of this limited warranty, then Seller may repair or replace the Goods that
gave rise to such breach or, in Seller’s sole and exclusive discretion, refund the amounts that Buyer paid for such Goods.
The foregoing limited warranties do not apply to (i) any defect in Goods not manufactured by Seller; and (ii) any Goods
manufactured according to Buyer’s specications.
(b) Buyer shall bear the costs of access, de-installation, re-installation and transportation of the Goods to Seller and back
to Buyer. Any repair or replacement pursuant to this limited warranty shall not extend the Warranty Period. Seller does not
warrant the Goods, or any repaired or replacement parts, against normal wear and tear. This limited warranty and remedy
are expressly conditioned upon: (i) Buyer’s payment of the purchase price in full, (ii) Buyer giving written notice of the defect,
reasonably described, to Seller within ten (10) days of the time when Buyer discovers or ought to have discovered the defect,
(iii) the storage, installation, operation, use, and maintenance of the Goods in compliance with the published specications
and instructions provided by Seller or its suppliers or subcontractors (the “Instructions”), (iv) the existence of proper records
of Buyer’s operation and maintenance of the Goods during the Warranty Period, (v) Buyer providing Seller with a reasonable
opportunity to examine the Goods and the aforementioned records, and (vi) the absence of any unauthorized modication or
repair of the Goods.
(c) Before any test may be used to evaluate the Goods, Buyer shall: (i) provide Seller with reasonable written notication of
such test, (ii) allow Seller to be present during such test, and (iii) receive Seller’s consent to the conditions of such test, which
consent will not be unreasonably withheld. If a test is performed on the Goods, and Seller has not consented to the conditions
of such test, then this limited warranty shall be void.
(d) THE REMEDIES SET FORTH IN THIS SECTION ARE BUYER’S SOLE AND EXCLUSIVE REMEDIES FOR ANY
FAILURE OF SELLER TO COMPLY WITH ITS OBLIGATIONS UNDER THIS AGREEMENT, INCLUDING ANY BREACH
OF THE LIMITED WARRANTY SET FORTH IN THIS SECTION. Correcting any defect in the manner set forth in this Section
8 shall constitute complete fulllment of Seller’s obligations and liabilities under the Agreement following the delivery of the
Goods, regardless of whether a claim is based in contract law, tort law (including negligence, strict liability or otherwise), or
other legal theory.
THE LIMITED WARRANTY SET FORTH IN THIS SECTION IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES,
WHETHER STATUTORY, EXPRESS, OR IMPLIED. EXCEPT AS SET FORTH IN THIS SECTION, SELLER MAKES NO
EXPRESS OR IMPLIED WARRANTIES, INCLUDING, BUT NOT LIMITED TO ANY WARRANTIES OF MERCHANTABILITY,
NON-INFRINGEMENT, OR FITNESS FOR A PARTICULAR PURPOSE, OR ANY WARRANTIES ARISING FROM COURSE
OF DEALING OR USAGE OF TRADE. Any other oral or written statements, whether contained in general advertising or other
printed material, do not constitute warranties, and Buyer agrees that it is not entering into the Agreement in reliance upon any
such statements.
■Contact Envirco
For warranties, replacement parts, technical support, or any other questions please contact Envirco at 1-800-884-0002. For
tech support related issues including troubleshooting and warranty, please email [email protected]. For customer
service related issues inlcuding parts ordering, please email [email protected].

Hospi-Gard®IsoClean®800 & 400
HEPA Filtration System
19Innovators in Clean Air Technology
Installation, Operation, & Maintenance Manual
This page intentionally left blank.

Envirco USA
101 McNeill Road | Sanford, NC 27330, USA
tel: 919.775.2201 | toll free: 800.884.0002 | fax:800.458.2379
www.envirco.com | [email protected] or [email protected]
Copyright ©2013 Envirco. All Rights Reserved.
Clean air solutions built for you.
MORE INFORMATION AVAILABLE AT WWW.ENVIRCO.COM
Industrial
Cleanroom Products
»MAC 10®Original
»MAC 10®IQ™
»MAC 10®LEAC2™
»MAC 10®LEDC™
»MAC 10®RFAC™
»Ducted Ceiling Module:
DCM & RSR
»AC or DC Control Systems
Hospital & Healthcare
Hospital & Healthcare
»IsoClean®800
»IsoClean®400
»IsoClean®CM
Laboratory & Research
»Unidirectional Flow
Horizontal Flow Bench (LF)
»TT Table Top Horizontal
Flow Clean Bench
»EnviraLab Sterility Module:
ESM
Pharmaceutical
»Unimodule M-2 Vertical
Unidirectional Flow
Workstation
»METD 100% Exhausted
Vertical Flow Workstation
»Unidirectional Downow
Module
Form P/N#: 267426
This manual suits for next models
1
Table of contents
Other Envirco Air Cleaner manuals
Popular Air Cleaner manuals by other brands

Tanis Technologies
Tanis Technologies Module-Air AF-24 Series Operating instructions & parts manual

Stadler Form
Stadler Form Viktor operating instructions

UCHEER
UCHEER T1 manual

MOOKA
MOOKA GL-FS32 user manual

SilverOnyx
SilverOnyx KJ150F-C02 user manual

TrueLife
TrueLife AIR Purifer P7 WiFi Instructions for use