Envirco MAC 10 LEAC Owner's manual

ENVIRCO Technical Support: 800-884-0002
MAC 10®LEAC
Fan Filter Unit
Standard, RSR, & RSRE Models
INSTALLATION, OPERATION & MAINTENANCE MANUAL

2 Innovators in Clean Air Technology | www.envirco.com | Installation, Operation, & Maintenance
Installation, Operation, & Maintenance Manual
MAC 10®LEAC
Fan Filter Unit
Table of Contents
Important Information ....................................................................................................... 3
Contact Information .......................................................................................................... 3
Critical Operations of the MAC 10®.................................................................................. 4
Warnings .......................................................................................................................... 4
Part Numbers ................................................................................................................... 4
Installation ........................................................................................................................ 5
Cleaning the Prelter (Foam) ........................................................................................... 6
Cleaning the Prelter (G4 Pleated)................................................................................... 6
Service: Removal and Replacement of Standard Filters.................................................. 7
Service: Removal and Replacement of RSRE Filters ...................................................... 8
Service: Standard Motor Removal and Installation .......................................................... 9
Service: RSRE Motor Removal and Installation.............................................................. 10
Unit Control Box ...............................................................................................................11
Troubleshooting............................................................................................................... 12
MAC 10 LEAC Wiring Diagrams...................................................................................... 13
MAC 10 LEAC Replacement Parts List........................................................................... 14
Limited Warranty ............................................................................................................. 15
Testing ............................................................................................................................. 15

3
■Important Information
To ensure ordering of the proper replacement parts or complete MAC 10 unit, record the information from the serial
number label, located adjacent to the electrical box, in the elds below for easy future reference. If you cannot locate
the Sales Order Number, please contact ENVIRCO for this information.
■Contact Information
Innovators in Clean Air Technology | www.envirco.com | Installation, Operation & Maintenance
Installation, Operation, & Maintenance Manual
MAC 10®LEAC
Fan Filter Unit
Order Number
CO-XXXXXXX
Serial Number
150412345-BA-AS1CH
Unit Part Number
11194-001
Date
MM/DD/YYYY
SERIAL/DATA LABEL SAMPLE
N
R
Fan Filter Unit
AC: 120v 60 Hz 1.80 amps
Covered by one or more
of the following patents:
nos. 4,560,395, & 5,470,363
Envirco
1-800-884-0002
www.envirco.com
LABEL PN 268177-XXX
150412345-BA-AS1CH
LISTED 2F82
AIR FILTER
E152685
Innovators in clean air technology
LEAC
SUITABLE FOR COMMERCIAL
OR INDUSTRIAL USE ONLY
C
R
R
R
Company Purchased From _____________________________________________________________________________
ENVIRCO Job Number ________________________________________________________________________________
Order Number _______________________________________________________________________________________
Serial Number _______________________________________________________________________________________
Unit Part Number ____________________________________________________________________________________
Date ______________________________________________________________________________________________
Airows per Certication _______________________________________________________________________________
ENVIRCO USA
101 McNeill Road
Sanford, NC 27330
Tel: (919) 775-2201
Tel: (800) 884-0002
Fax: (800) 458-2379
Serial No. Label

4
■Critical Operation Conditions of the MAC 10 LEAC
1. Touching of the HEPA filter will damage it, voiding the warranty on the filter. The screen is only to protect against an
accidental ‘touch’ of the filter. Never place a hand or tool on the filter. Never lie filter face flat down on a surface always
have filter on its side or back to protect from damage.
2. Prior to powering the unit, verify that the unit has been plugged into the correct voltage. The serial number label on the top
of the MAC 10 unit has the required voltage.
3. For reorder prepossess the MAC 10 part number and serial number should be recorded. This information is located on
the serial number label, located adjacent to the electrical box. If you can’t located the Sales Order Number please contact
ENVIRCO for this information.
■Warning
TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
A. Installation work and electrical wiring must be done by qualied person(s) in accordance with all applicable codes and
standards, including re-rated construction.
B. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
C. If this unit is to be installed over an area using liquid, such as water or chemical cleaning solutions, it must be marked as
appropriate for the application.
D. Use this unit only in the manner intended by the manufacturer. If you have any questions, contact the manufacturer.
E. Before servicing or cleaning the unit, switch power off at unit service panel and lock service panel to prevent power from
being switched on accidentally.
■Part Numbers Covered by This Manual
11194-XXX MAC 10 LEAC 2x4 (600x1210mm) Standard Filter
11194-XXX MAC 10 LEAC 2x4 (600x1210mm) RSR/E Filter
Note: A “Z” in the part number indicates that the unit is special. This may indicate a size change from standard or a special
lter. Please contact the factory for part numbers if this is the situation.
Installation, Operation, & Maintenance Manual
MAC 10®LEAC
Fan Filter Unit
Innovators in Clean Air Technology | www.envirco.com | Installation, Operation, & Maintenance

5
Installation, Operation, & Maintenance Manual
MAC 10®LEAC
Fan Filter Unit
■Installation
Note: The MAC 10 LEAC Fan Filter Unit is completely assembled at the factory with the exception of the optional ¼” (0.64
cm)-20 eyebolts, which can be used when hanging the unit from an overhead structure.
Step 1. Carefully remove the unit from the shipping carton and inspect for any damage that may have occurred during
transportation. (See Figure 1)
Figure 1: Unboxing
Step 2. Wipe down plastic bag and move unit into clean room. (Double bagging is available upon request.)
Step 3. If using rigidly supported grid (usually 2” (50 mm) or wider), raise unit through ceiling and lower onto the gasketed grid.
If using a exible grid (typically supported with wires) the unit must be secured to an overhead structure with eyebolts, s-hooks
and chain or ¼-20 all thread. A roll of high-density gasket has been provided for use with ungasketed grids. Note: special size
units are available to t specic clean room grid systems.
Note: Conrm fan dimensions to match T-grid dimensions. Special size units are available to t specic cleanroom grid systems.
Step 4. Have an electrician wire the unit to the appropriate voltage (115V, 220V, 277VAC), according to the wiring diagram in
section IX and local electric codes. If optional power cord was purchased, plug unit into a grounded receptacle. The optional
power cord is not acceptable for plenum installations.
Innovators in Clean Air Technology | www.envirco.com | Installation, Operation & Maintenance

6
Installation, Operation, & Maintenance Manual
Innovators in Clean Air Technology | www.envirco.com | Installation, Operation, & Maintenance
MAC 10®LEAC
Fan Filter Unit
■Cleaning the LEAC Prefilter (Standard Foam)
Tools Required: None.
Note: To keep the lter in top operating condition, washing the foam prelter
(if installed) is recommended every three to six months.
Step 1. To gain access to the prelter, remove the ceiling panel next to the
unit, if applicable.
Step 2. Switch the ON/OFF switch to the OFF position.
Step 3. Remove the prelter from the snap-in frame. (See Figure 2, below.)
Step 4. Clean the prelter by hand washing in water with a mild detergent or by using a vacuum cleaner. Allow prelter to dry
completely before replacing.
Step 5. Complete by reversing the above steps.
■Changing the LEAC Prefilter (G4 Pleated)
Tools Required: None.
Note: To keep the lter in top operating condition, replacing the pleated
prelter is recommended every twelve months or sooner.
Step 1. To gain access to the prelter, remove the ceiling panel next to the
unit, if applicable.
Step 2. Switch the ON/OFF switch to the OFF position.
Step 3. Remove the prelter from the snap-in frame. The beverage board frame has slots that have to be depressed to release
the lter from the prelter housing (See Figure 5, above.)
Step 4. After removing the new G4 pleated prelter from the box, remove the die cut slots from the beverage board frame and
install on prelter bracket.
Step 5. Complete by reversing the above steps.
Figure 4 - Foam Prefilter Cleaning
ON/OFF SWITCH
PREFILTER SURFACE ON TOP SIDE
(3/8" THK BLACK 20 PPI OPEN CELL POLYURETHANE FOAM)
SUPPORT SCREEN ON BOTTOM SIDE
(UNI-GRID EXPANDED ALUMINUM 85% OPEN)
20" x 20" Prelter
Figure 2: Foam Cleaning Prelter
Figure 5 - G4 Prefilter Placement
ON/OFF SWITCH
20" x 20" Prelter
Prelter retention slots
Beverage board frame
Figure 3: G4 Prelter Placement
WARNING
DISCONNECT THE UNIT FROM THE
ELECTRICAL POWER SOURCE BEFORE
ATTEMPTING ANY SERVICE.
WARNING
DISCONNECT THE UNIT FROM THE
ELECTRICAL POWER SOURCE BEFORE
ATTEMPTING ANY SERVICE.

7
Installation, Operation, & Maintenance Manual
MAC 10®LEAC
Fan Filter Unit
Innovators in Clean Air Technology | www.envirco.com | Installation, Operation & Maintenance
■Service: Removal and Replacement of Standard HEPA/ULPA Filters
Note: All lters should be visually inspected for freight damage before installation. It is necessary to use two workers when
removing the lter and for installation to avoid twisting or separation of the media seals. Handle the lter only by the frame
and never place anything on the upstream lter side of the lter. Additionally, it is important to keep the lter level to prevent
any shearing force on the media itself.
For Standard Filters:
Tools Required: Phillips head screwdriver, rivet hand tool, Ø5/32 aluminum rivet grip range .126-.187
Step 1. Remove unit from ceiling.
Step 2. Remove the 10 screws holding the HEPA/ULPA lter to the lid assembly.
Step 3. Lift the lid assembly off the HEPA/ULPA lter. (See Figure 4.) Discard the used lter as per requirements of the
applicable regulations. Carefully install the lter deectors into the new lter using the 5/32 rivets. Do not touch or place the
lter deectors on the HEPA/ULPA media pack. This could cause tears in the lter pack.
Note: Before replacing with a new HEPA/ULPA lter, carefully inspect the new lter for any visual damage. Also, inspect the
gasket in the “tee” bar to ensure a tight seal. Replace as necessary.
Step 4. Replace with the new HEPA/ULPA lter and complete by reversing the above steps.
WARNING
DISCONNECT THE UNIT FROM THE ELECTRICAL
POWER SOURCE BEFORE ATTEMPTING
ANY SERVICE.
WARNING
THE STANDARD FILTER IS PROTECTED WITH AN
EXPANDED METAL FACE SCREEN. THIS IS
NEVER TO BE USED TO HANDLE THE FILTER.
IT IS ONLY FOR PROTECTION AGAINST AN
ACCIDENTAL TOUCH OF THE FILTER.
ONLY HANDLE THE FILTER BY THE FRAME.
Ø5/32 RIVET (6X)
(NONE ON 2X2)
#8x3/8 FLAT HEAD PHILLIPS SHEET METAL SCREW
2X4 & 2X3.5 = 10X; 2X3 & 2X2 = 8X
LID ASSEMBLY
STD FILTER
Figure 6 - Standard Filter Replacement
Figure 4: Standard Filter Replacement

8
Installation, Operation, & Maintenance Manual
MAC 10®LEAC
Fan Filter Unit
■Service: Removal and Replacement of RSR/E Gel Seal Filters
Note: All lters should be visually inspected for freight damage before installation. It is necessary to use two workers when
removing the lter and for installation to avoid twisting or separation of the media seals. Handle the lter only by the frame
and never place anything on the upstream lter side of the lter. Additionally, it is important to keep the lter level to prevent
any shearing force on the media itself.
For RSRE Filters:
Tools Required: Phillips head screwdriver, 3/16” ball driver hex head wrench
Step 1. Remove the diffuser screen by removing the six 10-32x1/2 screws.
Step 2. Loosen the six 1/4x20 socket cap head screws far enough to rotate the lter clip 90°. The lter will not drop during this
operation. Slowly pull the lter away from the knife-edge seal, taking care not to touch the lter face during this operation. It
is important to pull the lter slowly and evenly away from the seal so that the gel remains in the lter gel track.
Step 3. Inspect lter for visual damage. If damaged, set aside for replacement or repair.
Step 4. Inspect the gel seal if reinstalling the removed lter. Determine if the gel has lost its ability to seal. If so, have a certied
professional replace the missing, dried out, and/or severely damaged gel.
Step 5. Place the lter evenly against the lter plenum housing of the RSR/E unit. Install lter clips and screws. The clips
can be rotated and angled into place. Using the clips as a lever, the lter can be seated. It is recommended to work either
clockwise or counter-clockwise around the lter and raise the lter into the gel.
Step 6. Reinstall screen. Reinstall and hand-tighten diffuser screen screws. Avoid overtightening the screen hardware.
WARNING
DISCONNECT THE UNIT FROM THE ELECTRICAL
POWER SOURCE BEFORE ATTEMPTING
ANY SERVICE.
WARNING
THE RSR/E FILTERS ARE PROTECTED WITH AN
EXPANDED METAL FACE SCREEN. THIS IS
NEVER TO BE USED TO HANDLE THE FILTER.
IT IS ONLY FOR PROTECTION AGAINST AN
ACCIDENTAL TOUCH OF THE FILTER.
ONLY HANDLE THE FILTER BY THE FRAME.
FILTER PLENUM
(DOWN STREAM)
1/4-20 CAP SCREW
FILTER CLIP
SCREEN HARDWARE:
#10-32x1/2 PHP SCREW
#10 NYLON WASHER
GEL TRACK
PLENUM KNIFE EDGE
FILTER PLENUM
(UP STREAM)
GEL SEAL FILTER
PERFORATED DIFUSSER
SCREEN
SCREEN HARDWARE
FILTER CLIP
1/4-20 CAP SCREW
2-PIECE WELDED
FILTER PLENUM
HOUSING
FAN FILTER UNIT
GEL SEAL FILTER
Figure 7 - RSRE Filter Replacement
FILTER MEDIA
PERFORATED DIFUSSER SCREEN
Figure 5: RSRE Filter Replacement
Innovators in Clean Air Technology | www.envirco.com | Installation, Operation, & Maintenance

9
Installation, Operation, & Maintenance Manual
MAC 10®LEAC
Fan Filter Unit
Innovators in Clean Air Technology | www.envirco.com | Installation, Operation & Maintenance
■Service: Standard and RSR Motor Removal and Installation
Tools Required: Phillips head screwdriver, 3/8” (10 mm) Hex Head wrench, pliers, 5/32” (0.40 cm) Allen wrench
Step 1. To gain access to the motor, remove the ceiling panel next to the unit, if applicable.
Step 2. Switch the ON/OFF switch to the OFF position.
Step 3. Remove the prelter off the prelter frame.
Step 4. Loosen the electrical cover screws (two), and slide/lift off cover. (See Figure 6.)
Step 5. Make note of all wire locations for reinstallation later.
Step 6. Disconnect 5-pin and 16-pin wire harnesses from the electrical box housing.
Step 7. Remove the eight screws to free the motor/blower assembly from the lid assembly. If using power drivers, set the unit
to a low torque setting to avoid stripping the sheet metal screws (See Figure 6.)
Step 8. Using an adjustable wrench, loosen the two set screws that attach the blower wheel to the motor shaft.
Step 9. Mark the location of the motor support bracket (belly band), then loosen the bolt just enough to allow the motor support
bracket to slide off the motor.
Step 10. Using the removed motor, mark the new motor with the location of the motor support bracket.
Step 11. Replace with the new motor and reassemble by reversing the above steps 1-8. Set the spacing at 0.25” (6.35 mm)
clearance between the blower and the upper motor plate/prelter frame. This will give a 0.11” overlap between the venturi
ring and the blower.
WARNING
DISCONNECT THE UNIT FROM THE ELECTRICAL
POWER SOURCE BEFORE ATTEMPTING
ANY SERVICE.
WARNING
ELECTRICAL SERVICE SHOULD ONLY
BE PERFORMED BY LICENSED ELECTRICIANS OR
AUTHORIZED ENVIRCO SERVICE TECHNICIANS.
PREFILTER
ELECTRICAL COVER
COVER MOUNTING HARDWARE (2X)
PREFILTER BRACKET
VENTURI RING
MOTOR/BLOWER ASSEMBLY
PREFILTER BRACKET
HARDWARE (8X)
FILTER (STD)
FILTER PLENUM (RSRE - NOT SHOWN)
CONDUIT PLATE
Figure 9.1 - Motor Replacement
LID PANEL ASSEMBLY
MOTOR/BLOWER MOUNTING
BRACKET
Figure 6: Standard/RSR Motor Replacement

10
Installation, Operation, & Maintenance Manual
MAC 10®LEAC
Fan Filter Unit
■Service: RSRE Motor Removal and Installation
Tools Required: 3/16 hex head wrench, Phillips head screwdriver
Note: It is highly recommended to also change the motor capacitor when changing the motor.
Step 1. To gain access to the motor, remove the gel seal HEPA/ULPA lter.
Step 2. Prior to removing motor/blower assembly, remove blower wheel to expose motor connectors on motor. Using an
adjustable wrench loosen the two set screws that attach the blower wheel to the motor shaft. Disconnect the ve and sixteen
pin connectors from the motor.
Step 3. While supporting the motor blower assembly from below, remove the six screws on the underside of the venturi ring
and lower the assembly. (See Figure 7). Note the bafe does not have to be removed to remove the motor/blower assembly.
Step 4. Before removal of the motor mount bracket, measure the precise location of the bracket on the motor. Remove the bracket.
Step 5. Replace with the new motor and reassemble by reversing the above steps. Set the location of the motor mount bracket
as measured (see above Step 6). Set the spacing at 0.25” (6.35 mm) clearance between the blower and the upper motor plate/
prelter frame creating a 0.11” (2.80 mm) overlap between the wheel and the venturi ring. When reinstalling the assembly,
align the plate to insure that the leads will reach the electrical box.
WARNING
DISCONNECT THE UNIT FROM THE ELECTRICAL
POWER SOURCE BEFORE ATTEMPTING
ANY SERVICE.
WARNING
ELECTRICAL SERVICE SHOULD ONLY
BE PERFORMED BY LICENSED ELECTRICIANS OR
AUTHORIZED ENVIRCO SERVICE TECHNICIANS.
Figure 7: RSRE Motor Replacement
Innovators in Clean Air Technology | www.envirco.com | Installation, Operation, & Maintenance
MOTOR MOUNTING BRACKET
CABLE TIE (FOR MOTOR CABLE)
MOTOR/BLOWER ASSEMBLY
MOTOR/BLOWER ASSEMBLY CONNECTOR
MOTOR BRACKET MOUNTING HARDWARE (4X)
#10-32 x 1/2 PHP SCREW
#10 LOCKWASHER
MOTOR MOUNTING HARDWARE (4X)
M6x16mm PHP SCREW
M6 LOCKWASHER
NOTE ORIENTATION OF MOTOR/BLOWER ASSEMBLY
AND MOTOR MOUNTING BRACKET, CABLE IS ORIENTED
AT NOTCH IN MOTOR MOUNTING BRACKET AND CABLE
TIED TO SIDE OF THE MOTOR MOUNTING BRACKET.
PREFILTER BRACKET
Figure 9.2 - Motor Replacement

11
Installation, Operation, & Maintenance Manual
MAC 10®LEAC
Fan Filter Unit
Innovators in Clean Air Technology | www.envirco.com | Installation, Operation & Maintenance
■Unit Control Box
ON/OFF Switch - Speed/Airow Adjustment
All MAC 10 units are equipped with a three-position rotary switch, which is located on the side of the electrical box. (See Figure 8.)
Recommended fan speed during initial start-up and operation is the “LOW” speed. As airow eventually decreases due to lter
loading, fan speed may be increased by moving the rocker switch to the top or “MEDIUM” position, and nally to the “HIGH”
position. Periodic airow velocity readings (Per I.E.S. T. Specications) should be conducted to determine the lter condition and
appropriate fan speed setting.
Figure 8: 3 Speed Switch Adjustment
3 SPEED SWITCH
ELECTRICAL ENTRANCE
ON/OFF SWITCH
Figure 3 - Speed/Airflow Adjustment
LOW
MEDIUM HIGH

12
Installation, Operation, & Maintenance Manual
MAC 10®LEAC
Fan Filter Unit
■Troubleshooting
UNIT IS NOT ADJUSTABLE
Verify that rotation of the knob on the visual speed control does not change the RPM or Flow Index display on the unit. If
rotating does nothing, remove the electrical box cover and remove the 4-pin connector from the Visual Speed control and
install in 180 degrees rotated. Again adjust the knob. The 4 pin connector is on the 18” (31.8 mm) white conductor.
LOW AIR VELOCITY
Step 1. Check prelter media; replace or clean as necessary.
Step 2. Adjust visual speed control for higher blower output.
Step 3. Check power supply for proper voltage, amperage and distribution frequency.
Step 4. Replace HEPA lter if the air velocity remains low.
HIGH AIR VELOCITY
Adjust visual speed control for lower blower output.
NON-LAMINAR FLOW AND/OR EXCESSIVE CONTAMINATION
Step 1. Ensure that no large obstructions are upstream of airow pattern.
Step 2. Determine that no other air-moving devices are operating in or around cleanroom which disrupt room’s airow pattern.
Step 3. Check air velocity and, if low, conduct the “Low Air Velocity” procedure outlined above.
Step 4. Conduct smoke and photometer test on HEPA lter. Seal or replace HEPA lter as necessary.
Contact Technical Support at:
ENVIRCO
101 McNeill Road
Sanford, NC 27330, USA
Tel: (800) 884-0002
Fax: (800) 458-2379
Email: [email protected]
Innovators in Clean Air Technology | www.envirco.com | Installation, Operation, & Maintenance

13
Installation, Operation, & Maintenance Manual
MAC 10®LEAC
Fan Filter Unit
■MAC 10 LEAC Wiring Diagram
Figure 9: Wiring Diagram
Innovators in Clean Air Technology | www.envirco.com | Installation, Operation & Maintenance

14
Installation, Operation, & Maintenance Manual
MAC 10®LEAC
Fan Filter Unit
■MAC 10 LEAC Replacement Parts List
ACLE PARTS PART #
Grommet 63271
Motor 120V 63764-001
Motor 220V 63764-002
Motor 277V 63764-003
Motor Mount Clip 38511-001
Venturi Ring 64115
Blower Wheel 64015
Motor/Blower Assy
120V 24511-001
220V 24511-002
277V 24511-003
Capacitor 61485
Capacitor Boot 60126
Rocker Switch 63739-002
3 Spd Switch 63775
Foam Pre-lter (20x20) 62981-038
30/30 Pre-lter (20x20) 64125-001
All lter part numbers are based on the standard MAC 10 sizes (2x4 – 23.63x47.63).
If the unit in question is not this size or the part number includes a “Z”, contact the factory for replacement lter information.
STANDARD FILTERS PART NUMBERS
• 69600S-001HAPXX FILTER - HEPA 2X4 9” FRAME
• 69600S-001UAPXX FILTER - ULPA 2X4 9” FRAME
WELDED RSR GEL SEAL
• 69601-001H FILTER - HEPA 21X45X3.5 GEL SEAL
• 69601-001U FILTER - ULPA 21X45X3.5 GEL SEAL
Optional Accessories:
• Fluorescent lighting
• Ionizing bar
• ULPA Filter (Standard and RSR)
• A/C intake collar: 20x20 (10” /254mm)
• 20x20 (12” /304.8mm)
• 20x20 (14” /355.6mm)
Innovators in Clean Air Technology | www.envirco.com | Installation, Operation, & Maintenance

15
Installation, Operation, & Maintenance Manual
MAC 10®LEAC
Fan Filter Unit
■Limited Warranty
LIMITED WARRANTY: Unless otherwise expressly
stated in ENVIRCO’s published specications for the
Goods, ENVIRCO warrants that Goods are free from
defects in material and workmanship, except for services
which are warranted to be performed in a competent and
diligent manner in accordance with any mutually agreed
specications. The foregoing warranty shall apply for
eighteen (18) months from the date of shipment from
ENVIRCO’s facility, except for services for which the
warranty shall apply for ninety (90) days from the date
of performance (the “Warranty Period”). Provided Buyer
informs ENVIRCO in writing of any breach of warranty
prior to the expiration of the applicable Warranty Period,
ENVIRCO shall, as its sole obligation and Buyer’s sole
and exclusive remedy for any breach of this warranty,
repair or replace/re-perform the Goods which gave rise
to the breach or, at ENVIRCO’ option, refund the amounts
paid by Buyer for the Goods which gave rise to the breach.
Any repair, replacement or re-performance by ENVIRCO
hereunder shall not extend the applicable Warranty Period.
The parties shall mutually agree on the specications of
any test to determine the presence of a defect. Unless
otherwise agreed upon by ENVIRCO in writing, Buyer shall
bear the costs of access, de-installation, re-installation
and transportation of Goods to ENVIRCO and back to
Buyer. These warranties and remedies are conditioned
upon (a) the proper storage, installation, operation,
and maintenance of the Goods and conformance with
the proper operation instruction manuals provided by
ENVIRCO or its suppliers or subcontractors, (b) Buyer
keeping proper records of operation and maintenance
during the applicable Warranty Period and providing
ENVIRCO access to those records, and (c) modication
or repair of the Goods only as authorized by ENVIRCO.
ENVIRCO does not warrant the Goods or any repaired
or replacement parts against normal wear and tear or
damage caused by misuse, accident, or use against the
instructions of ENVIRCO. Any modication or repair of any
of the Goods not authorized by ENVIRCO shall render
the warranty null and void. EXCEPT AS EXPRESSLY
SET FORTH HEREIN, ENVIRCO MAKES NO OTHER
WARRANTIES, EXPRESS OR IMPLIED, INCLUDING,
BUT NOT LIMITED TO, ANY IMPLIED WARRANTIES
OF MERCHANTABILITY, NON-INFRINGEMENT OR
FITNESS FOR A PARTICULAR PURPOSE WHICH ARE
HEREBY DISCLAIMED TO THE EXTENT PERMITTED
BY APPLICABLE LAW.
■Testing
Each MAC 10 LEAC lter unit is thoroughly tested at
the factory before shipment. However, because of the
“rigors” of shipping, ENVIRCO encourages its re-test
after installation. Additional, for large installations it
is recommended to bench test 5% of the units prior to
installation.
ENVIRCO recommends that the customer contact an
independent organization, with technicians trained and
experienced in performance evaluation and maintenance
of clean air equipment.
Some of the testing procedures performed on the MAC
10 LEAC include PSL challenge of HEPA/ULPA lters
to assure specied performance, along with air velocity
measurement and adjustment tests. No DOP is used on
MAC 10 Filters, unless requested.
Innovators in Clean Air Technology | www.envirco.com | Installation, Operation & Maintenance

Clean air solutions built for you.
MORE INFORMATION AVAILABLE AT WWW.ENVIRCO.COM
ENVIRCO MAC 10 is a registered trademark of ENVIRCO, USA. Specications subject to modications or changes without notice. US patents 4,560,395 and 5,470,363. Other patents issued and pending in foreign countries.
Copyright © 2017 ENVIRCO. All Rights Reserved.
Form P/N #: 268571 Rev. 02/17
Industrial
Cleanroom Products
»MAC 10®Original
»MAC 10®IQ™
»MAC 10®IQ™ LAF
»MAC 10®LEAC™
»MAC 10®LEAC2™
»MAC 10®LEDC™
»Ducted Ceiling Module:
DCM & RSR
»AC or DC Control Systems
»MAC-T Ceiling Grid System
Hospital & Healthcare
Hospital & Healthcare
»IsoClean®and IsoClean
with Ultraviolet Light
»AirCeil®
»Hospi-Gard®Room
Pressure Monitor
Enviramedic Products
»HOR Horizontal Flow
Enclosure
»HCF Horizontal Flow
Surgery Room
»VOR Vertical Flow Surgery
Isolator
Pharmaceutical
Pharmaceutical &
Medical Device
»Unimodule M2 Vertical
Laminar Flow Workstation
»METD 100% Exhausted
Vertical Flow Workstation
»Laminar Downow Module
Laboratory & Research
Laboratory & Research
»100-Plus Horizontal or
Vertical Flow Clean Bench
»Unidirectional Flow
Horizontal Flow Bench (LF)
»TT Table Top Horizontal
Flow Clean Bench
»EnviraLab Sterility Module:
ESM
ENVIRCO®
101 McNeill Road | Sanford, NC 27330, USA
tel: 919.775.2201 | toll free: 800.884.0002 | fax: 800.458.2379
Table of contents
Other Envirco Water Filtration System manuals
Popular Water Filtration System manuals by other brands

Waterco
Waterco Gemini Fitting and operating instructions

Pure-Pro
Pure-Pro ERS-106UV user manual

ThePondguy
ThePondguy ClearSolution 120800 Installation & maintenance

Pure-Pro
Pure-Pro RS-106M user manual

KEBCO
KEBCO COMBILINE manual

MASTER PNEUMATIC-DETROIT, INC.
MASTER PNEUMATIC-DETROIT, INC. L29D Installation and Maintenance