DINLINE ALARM RELAY (DAR)
INSTALLATION INSTRUCTIONS
www.erico.com Page 1 of 2
1. PREPARATION
DANGER: Electrical shock or burn hazard.
Installation of this device should only be made
by qualified personnel. Failure to lockout
electrical power during installation or maintenance can
result in fatal electrocution or severe burns. Before
making any connections be sure that power has been
removed from all associated wiring, electrical panels,
and other electrical equipment.
CAUTION NOTES:
1. The installation of this device should follow all
applicable electrical codes, such as the National
Electrical Code.
2. Check to make sure line voltage does not exceed
DAR275V voltage ratings.
3. Follow all instructions to ensure correct and safe
operation.
4. Do not attempt to open or tamper with the DAR in
any way as this may compromise performance and
will void warranty. No user serviceable parts are
contained.
2. INTRODUCTION
Selected DSD, TDS & TDF DINLINE Surge Protection
Devices include status monitoring circuits which provide visual
status display of device capacity. They may also provide a low
voltage opto-coupler alarm output circuit that can be connect to
the DAR to provide potential free (Form C) change-over
contacts. The DAR alarm contacts may be used to provide
output to external alarm systems or remote monitoring circuits.
One DAR can be used per DSD/TDS/TDF opto-coupler alarm
or up to 16 DSD opto-coupler alarms can be connected in
series to the one DAR to provide a common output. It is
recommended that the DAR be powered from the same
power circuit that feeds the device(s) being monitored,
however the DAR can be powered from other circuits. This
allows for example, one DAR unit to be connected to separate
SPDs that are protecting a three phase circuit.
Note. Depending upon the usage of the DAR output contacts,
failure of power to the DAR may be interpreted as a failure of
one or more of the SPDs being monitored. Visual inspection
of the DAR and SPDs status displays would determine this.
3. MOUNTING
The DAR is designed to clip to 35mm (top hat) DIN rails
(standard EN50022). Unless otherwise mechanically
restrained, use horizontal DIN rails with the DAR module
spring clips to the bottom and the label text the correct way up.
NOTE: The DAR must be installed in an enclosure or panel
that:
•prevents the DAR temperature from exceeding
131°F (55°C)
•provides adequate electrical and safety protection
•prevents the ingress of moisture and water
• allows DAR status indicators to be inspected
4. ELECTRICAL CONNECTION
The interconnecting wiring should:
•be of size #10 to #14 AWG (2.5mm² to 6mm²) solid or
stranded conductor.
•The wire insulation should be stripped back 5/16" (8mm).
•NOTE: Do not use greater than 9inlbs (1Nm) of torque
when tightening the terminals.
CONNECTION TO TELECOMMUNICATIONS NETWORKS
The DAR is approved for use in Australia where the alarm
contacts may be connected to private lines or building cabling
associated with the telecommunications network. NO direct
connection to the public switched network should be made.
MODEL NUMBER
DAR 275V
PRV Switchboard Manual Section 2 - Terasaki Circuit Breakers Installation Instructions Vendor Manual
Q-Pulse Id: VM78
12/11/2012
Page 1 of 2
DINLINE ALARM RELAY
INSTALLATION INSTRUCTIONS
www.erico.com Page 2 of 2 Doc: HBCR1681, Rev: 1
5. INTERCONNECTION
When connecting the DAR to a single opto-coupler output the
+ terminal of the SPD should connect to the + terminal on the
DAR. The – terminal should connect to the -- terminal.
T
o
t
r
a
n
s
i
e
n
t
protected
equipment
T
o
r
e
m
o
t
e
a
l
a
r
m
c
i
r
c
u
i
t
DSD2S/2T
NEPh
DAR
NPh
Voltage free contacts
Opto-coupleroutput
+/- terminal connections are polarity sensitive. Do not reverse.
When connecting the DAR to multiple opto-couplers the opto-
couplers should be connected in series with + terminal of one
connected to the – terminal of the next. The DAR + terminal
should connect to + SPD terminal at one end of the series
connection and the – DAR terminal connect to the – SPD
terminal at the other end of the series connection.
D
S
D
2
S
/
2
T
Upto 16 connectionsperDARmodule
NEPhNEPh
DAR
NPh
Voltage free contact
s
+/- terminal connections are polarity sensitive. Do not reverse.
5. STATUS INDICATION
Normal(green)indicatorOFF
Red indicatorON
Relayisde-energised
Poweris supplied
Normal(green)indicatorOFF
Red indicatorOFF
Relayisde-energised
PowerisOFF
Normal
4
Fault
6
8
Normal
4
Fault
6
8
DSDin alarm mode orpower
toDSDhasbeen removed
PowertoDARremoved
Protection statusunknown
DISPLAY
EXPLANATION
Normal
Fault
6
4
8
Normal(green)indicatorON
Red indicatorOFF
Relayisenergised
Poweris supplied
Normaloperation
Protection Operational
STATUS
Protection AlarmFaultMode
6. FUSING AND ISOLATION
Overcurrent protection must be installed in the upstream circuit
of the power supply to the DAR to provide protection to the
unit itself and the wiring in case of fault conditions.
The fuse rating should be based on the wiring size used to
connect to the DAR Ph & N terminals. Australian regulations
AS3000-1991, Table B2 specifies the following upstream
protection for single phase circuits, unenclosed in air.
Cable Size HRC Fuse or CB Rewirable Fuse
1.5mm2 16A 12A
2.5mm2 20A 16A
4mm2 25A 20A
6mm2 32A 25A
Where overcurrent protection of the appropriate rating or
smaller is already fitted in the upstream circuit, overcurrent
protection at the DAR will not be required
6. MAINTENANCE & TESTING
Before removing a DAR unit from service, ensure that the
power has been removed. Maintenance, testing and
replacement should only be undertaken by qualified personnel.
Testing of a DAR unit which is connected to a fully functional
DSD unit can be accomplished by removing power to the DSD
only. The DAR Status indication and output contacts should
alter from the Normal to Fault condition.
Testing of the DAR unit alone may be accomplished by
disconnecting the + / -connections to the unit. When power is
applied the DAR “Fault” Status Indicator should be illuminated.
By connecting the + / - terminals together, the “Normal” Status
Indicator should be illuminated. The output contacts should
alter to the appropriate state.
7. USE OF OTHER INTERFACES
Only DAR units are recommended for the interfacing of
equipment to the DSD, TDS & TDF opto-coupler alarm output
circuit(s). The direct connection of other equipment to these
opto-coupler alarm outputs may not provide sufficient isolation
or exceed the opto-coupler specifications. This may damage
the SPD and/or the connected equipment. Warranty may be
voided under such circumstances.
NOTE: In connecting to the SPD opto-coupler alarm
output(s), do not reverse the +/-connections as
damage may occur
LNE
(4-6mm)
Bundle/twisttogether
Supply
Keep as short as practical
See section 8for fusing details
NL
PRV Switchboard Manual Section 2 - Terasaki Circuit Breakers Installation Instructions Vendor Manual
Q-Pulse Id: VM78
12/11/2012
Page 2 of 2

Popular Relay manuals by other brands

Combustion and Energy 600-IFD-140-SRS Operation and maintenance manual

Combustion and Energy

Combustion and Energy 600-IFD-140-SRS Operation and maintenance manual

jablotron AC-160-C quick start guide

jablotron

jablotron AC-160-C quick start guide

Trane Relay Panel installation guide

Trane

Trane Relay Panel installation guide

Remak STE T10B Installation and operating instructions

Remak

Remak STE T10B Installation and operating instructions

Weidmüller TFIS 12-240VUC 1CO M7C Assembly and installation instruction

Weidmüller

Weidmüller TFIS 12-240VUC 1CO M7C Assembly and installation instruction

Circutor WRU-10 RAL manual

Circutor

Circutor WRU-10 RAL manual

BEA LO-21 quick start guide

BEA

BEA LO-21 quick start guide

Mikro x20 user manual

Mikro

Mikro x20 user manual

Elk Products ELK-912 instructions

Elk Products

Elk Products ELK-912 instructions

Pilz P2HZ X1 operating manual

Pilz

Pilz P2HZ X1 operating manual

Siemens SIRIUS 3TK2821 operating instructions

Siemens

Siemens SIRIUS 3TK2821 operating instructions

MULTISPAN VPR 3P manual

MULTISPAN

MULTISPAN VPR 3P manual

SICK ReLy MULT1 operating instructions

SICK

SICK ReLy MULT1 operating instructions

GE Multilin 489 instruction manual

GE

GE Multilin 489 instruction manual

Westinghouse KQS instructions

Westinghouse

Westinghouse KQS instructions

Gira 5403 00 operating instructions

Gira

Gira 5403 00 operating instructions

Pilz PMUT X1P operating manual

Pilz

Pilz PMUT X1P operating manual

Greystone Energy Systems GT-AR4 Series installation instructions

Greystone Energy Systems

Greystone Energy Systems GT-AR4 Series installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.