GE RPM 13A User manual

INSTRUCTIONS
TI
MI NG RELAYS
Types
RPM
13A,
138,
130
...
PM15A, 158,
15C
and
150
POWER SYSTEMS MANAGEMENT DEPARTMENT
G-ENERAL
_
ELECTRIC
PHILADELPHIA,
PA.
GEH-2031B
Supersedes
GEH-2031A
I
I
11
.1
i1
;1
i
1
j
I
i

GEH-2031 TimiIl,g
Relays
Type
RPM
TARGETS
INNER
CONTACT
OUTER
CONTACT
Fig. I
(8030298)
REAR
MOUNTING
PINION
PAWL
RPM
Relay, Unit
Withdrawn
From
Cas~
(Front
-View)
MAGNETIC
DAMPING
ELEMENT
SET
SCREW
FOR
COPPER
CYLINDER
FRONT
MOUNTING
PLATE
Left Side
Vi
ew
Fig. 2
(8030297)
FRONT
MOUNTING
PLATE
---f-,'J
DRIVING
ARM
ARMATURE
RESET
SPRING
ROTANOID
TY
RELAY
RPM
Relay, Unit
Withdrawn
From
Case
(Rear
View)
-
MAIN SHAFT
BRACKET
FLEXIBLE
STOP ARM
Right Side
View
,-:----REAR
MOUNTING·
LARGE GEAR
ON
MAIN
SHAFT
DRIVING
SPRING
DRIVING
SPRING
COLLECT
Fig. 3
(800qB23
&
800qB2~)
RPM
Relay
Unit
Subassembly
Between
Front
and
Rear
Mounting
Plates
2
-
•
I
-
•
8
.-~
(
"I
-"--./

7""-'\
I )
,---,
!
-----
!'J
INTRODUCTION
The
RPM
13
and
15
relays
mounted
in
'
an
SI
drawout
case
are
general
purpose
direct
current
operated
auxiliary
timing
relays
having two
cam
operated
closing
contacts.
Each
contact
has
an
independent
adjustable
time
setting
with
the
exception
that
the
contacts
must
always
close
in
the
same, sequenc.e
with
a
minimum
time
of
several
cycles
between
the
closings
of
the
two
contacts.
Sl'!e
the
section
on
CHARAC-
TERISTICS
for'
further
discussion
of
the
minimum
time
between
contact
closings.
Each
contact
has
its
own
target
and
the
relay
has
one
electrically
separate
seal-in
unit
generally
used
with
the
TU-l
contact.
In
addition
the
RPM15
relay
employes
a
telephone
type
relay,
TY,
to
provide
a
con-
tJm!PJ!s
~Qil
n~tJng.
,S.ee
Table
No.
A.
for
different
models.
APPLICATION
These
RPM
relays
can
be
applied
wherever
an
accurate,
direct
current
op-
erated,
timing
d.evice, .
.wJfu_
~_adjustable
timing
ranges
0.1
to
1
second
or
0.15
to
3
seconds
is
required:
-A
typical
application
is
illustrated
in
Fig.
4
where
the
RPM13
relay
is
used
to
provide
a
time
delay
before
the
back-up
fault
relays
b~come
effective.
The
fault
relays
together
with
the
RPM
re-
'lays
are
used
here
to
provide
back-up
protection
for
a
unit
type
generator
installa-
tion
against
P:rolongE!d
multiphase
faults
on
the
adjacent
system.
When
the
fault
relays
operate,
they
start
the
RPM
relay
which
trips
the
main
breaker
after
a
predeter-
mined
time
thru
its
own TU
-1
contact
and
the
fault
relay
contacts.
If
for
some
reason
the
generator
is
still
connected
to
the
fault,
the
fault
relays
will
remain
picked
up
and
when
the
second
RPM
contact
(TU-2)
closes
after
an
additional
predetermined
time
it
will
operate
a
lockout
relay,
Type HEA,
which
shuts
down
the
unit
generator.
Fig.
5 shows
the
RPM15
relay
sub-
stituted
for
the
RPM13
relay
in
a
similar
application.
, Tbe
RP~
re~ay
tripping- cpnt!ict.s
@o:t,Il,c;I:
alwaysOe
used
IIi
senes
WIth
the
lll-
itiating
relay
contacts
in
a
trip
circuit.
In ,this way any
overtravel
which
may
exist
in
:
the
RPM
relay
is.
negated
by
the
opening
of
the-initiating
relay
contacts.
TIMING RELAYS
TYPE'RPM
* TABLE A
TIMING
COILCmCUIT
CONTACT DWELL TIME
RANGE TIME RATING
TU-l
TUc.2
~ODEL---
- -
Seconds Seconds
Cycles
(60 Cycle
Base)
12RPM13All
&
Up
0.15 -
3.0
60
9-15 9-15
12RPMI3B11 &
Up
0.10 -1.0 60 'Maintained 3,.5
12RPM13D11 &
Up
0.15 -
3.0
60 Maintained 9-15.
12RPM15Al '&
Up
0.15 -
3.0
.Continuous
9-15
Maintained
12RPM15Bl1 &
~
0.10 -1.0 Continuous Maintained Maintained
12RPM15CL'&
p
'12RPMl5Dl:
.&'Up
0.15 -3.0 Continuous
Maintained
Maintained
,0.15 -
3,.0,
, COl;ltinuous
Maintained
'Maintained
RATINGS
These
RPM
relays
are
available
with
i
operating
coils
for'
24
to
250
volts
D.C.,
As
indicated
in
Table
A
the
RPM13
relaysl
have
coils
rated
for
one
minute
and
the
RPM15
relays
have
continuously
rated
coils.:
The
target
and
seal-in
units
are
current,
,
operated
devices
with
ratings
of
either
0.2
,
or
1.0
amperes.
The
timing
contacts
TU-1
and
TU-2
are
for
circuit
closing
only. They
will,
carry
a
maximum
of 30
amperes
for
the
time
it
takes
to
trip
a
breaker
and
have no
interrupting
rating.
Since
these
contacts
have
no,
interrupting
rating,
any
control
circuit
involving
these
contacts
must
be
cleared
bya
circuit
breaker
auxiliary
switch
or
other
suitable
means~
The
contact
interrupting
rating
of
the
telephone type
relays
are
shown
in
Table
B.
'The
contact
rating
of
the
seal-in
unit
is
shown
in
Table
C.
CONTACT INTERRUPTING ABILITY
TABLE
:i3
..
'-
TARGET
AND
SEAL-IN UNIT
TABLE C
,1~()'Amp
'0.2 Amp'
~'Tap
Tap
DC
Resistance
O,2;L'ohms ;jl
..
:ohms
Minimum
Operating
l~O,amps
0
•.
2
amps
Carry
Continuously
;2
..
.if:amps 0.35
amps
Carry
30
amps
for
'2
sees.
---------
Carry
10
amps
for
15
secs.
0.2 flecs.
60-cycle
Impedance
:2.0:
ohms
52
ohms
CHARACTERISTICS
OPERATING
PRINCIPLE
The
RPM
relay
operates
on
the
prinCiple
of
using
the
energy
from
a
charged
spr.ing.
The
spring
is
charged
by a
solenoid
called
a
rotonoid
because
of
its
circular
shaped
plunger.
The
energy
of
the
spring
is
diSSipated
through
a
gear
train
at
a
rate
controlled
by a
damping
magnet.
The
timing
contacts
are
operated
by
cams
attached
to,
this
gear
train.
,
The
TX
coii
of the
RPM
relay
has
a
very
low
drop-out
voltage.
This
low
drop-
out
makes
it
possible
for
an
indicating
lamp
in
series
with the, TX
coil
to
keep
that
el~mentpicked
up
after
it
has
operated.
For
thIS
reason
it
is
important
that
caution
be
~xercised
in
the
application
of
the
relays
to
msure
that
there
are
no
sneak
circuits
which
can
permit
the
TX
coil
to
be
sealed
in
through
a
lamp
or
some
other
device.
Volts
Interruption
Current'
(Amps) MINIMUM OPERATING VOLTAGE
Inductive* Non-Inductive
48-DC
1.0
3.0
125-DC 0.5 1.5
250-DC ' 0.25 0.75
115-60
cy.
0.75 2.0
230-60.cv.
0.5 1.0
* Inductance of
Average
Trip
Coil
The
operation
of
,the rotonoid desig.;
nated
as
"Tun
is
controlled
by
the
contacts
of
the
telephone
type
relay
designated
as
"TX". .
Both
this
telephonetype
reia
y
"TX",
and
the
telephone
type
relay
"TY"
which
is
used
in
the
RPM15
relays
will
operate
at
80%
of
rated
voltage
or
above.
These instructions do not purport to cover all details
or
variations
in
equipment nor to provide for every poaib/e
contingency to
be
met
in
connection with installation, operation
or
maintenance. Should further information
be
desired
or should particular problems arise which
are
not covered sufficiently for the purchaser's purpases, the matter should
be
referred to the General
Electric
Company.
3

GEH-2031
Timing
Relays
Type
RPM
4
.........
------~--------
(+)
1
94
7
"-'T
62
62
TU
INDICATmG
lAMP
IF
reED
1-00
SHUI'
DOWN
r---
}
S6
CONTACTS
C
UNrr
-+-------;6--
____
~
(-)
LEGEND
DEVICE
DEVICE
FUNCTION
NO.
TYPE
21
CEB12C
BACK
UP
DT.~.HT~1i'
'R'W,T.A
V
94
HGAJ.4AM
or
.At
AUXILIARY
TRIPPTI7G
RELAY
86 HE!
LOCKOUT
REIAY
62
RPM13A,13B
or
13D
TlMmGRELAY
Fig.
~
(IO~A8985-1)
Typical
Applicaiionof
the
RPM!3
Relay
As
A Timer In A
Unit
Generator
Back
Up
Scheme
.1"\.\
)
/

,'1
J~
<..J
r,
i~~
___
)
.-
......
_.
--
..
--
..
~-.-
-==================
TimiJ\g Relays Type RPM GEB-2031
WHEN
USED
2
1
SI
TX
PROTECTIVE
lY
RELAY
1
lY
lSI
TY
T2
SI
10
4
TO
TO
5
TRIP TRIP
CIRCUIT
CIRCUIT
Fig. 5
(~18A836-1)
Typical
Appl
icatioli
of
the
RPMI5
ReJ'ay
r---~------
__
---,
I
I
I.
I
7 I 9 I,
. I I
~/~/
TEST
PLUG
1l.I2
WHEN
USED
lY
TO
8
TO
TIME
TU-l
TO
10
TO
T.IME
TU-2
TIMER
A.C..
SUPP
Y
TIMER
VOLTAGE
SEAL-IN.
RATING
AMPS.
24
1.0
o 2
4 1 0
48
0.2
1
0.2
D..
c..
CONTROL
SUPPLY
R
OHMS
0
24
120
0
120
600
CAUTION:-
DO
NOT
KEEP
Sl
CLOSED
LONGER
THAN
NECESSARY
TO
OBTAIN
TIME
TEST,
BECAUSE
OF
THE
SHORT
TIME
RATING
OF
THE
ROTONOID.
lY
Fig.
6 (377AI21-1)
Test
Circuit
For Checking
Time
Calibration
of
the
RPM
Relays Covered
By
This
Book.
_______
.
____
.
___
.____
~_
..
_____
.
__
Testl!!!L.!!rminlll
Numbers
Corrllspond iQ.!/1e
ReI!!)'
$J~!l
Numbe.r.s_
5

GEH-2()3~
Timing
Relays
Type
RPM
'rhe
rmmmum
pickup
of
the
rotonoid
i:>
'('leU below
the
pi(~kup
level
of
the
"'IX"
relay
or
about
50%
of
rated
voltage.
THE
TIMING OPERATION
The
maximum
operating
times
of tIlese
RPM
:relays
are
either
"one"
or
"three"
seconds
depending upon tile
nlOdeI.
The
minimum
operating
time
is
in
the
order
of
0.1
seconds.
The
desired
operating
time
is
con~
trolled
by
cams
which
can
be
set
at
any
position
on
the
Ume
dial.
These
cams
as
they
rotate
>.will
close
the
front
and
back
contacts
called
TU-1
and
TU-2
respectively.
The
cams
in
passing
will
hold
the
contacts
closed
for
a
specific
time
called
"DWELL
TIME".
Some of tile
models
have
tile
front
contact
maintaining,
cam
shaped
to
hold
the
contact
closed
through
the
balance
of the
time
range.
The
back
contact
on
the
con-
tinuously
rated relay
is
in
effect
maintainild
by a
contact
of
the
"TY"
r.elay which
seals
around'1;'U-2.
NOTE:
The
"dwell"
time
will
vary
depend-
ing
upOn
the
time
range
and
position
of
the
cam.
See
Table
No. A
for
details.
The
cams
cannot
be
set
togetller
to
operate
their
contacts
at
tile
same
time.
The
time
difference
between
the
closing
of
the
front
contact
and
the
back
contact
with
the
cams
set
as
close
together
as
the
mechanism
will
permit
will
vary
depending
on
the
time
range
and
the
position
of
the
cams
on
the
dial.
Fer
the
one
second
rel;j.y
this
time
difference
range
will
be
between
0.030
and
0.06
seconds.
The
range
for
the
three
second
relay
i~
.08
to
0.12
seconds.
Under
nor!llill
operating
voltage,
the
operr4tingtb:pe
at
the
maximum
dial
setting
will
be
accura.te within
±.
5%.
As
the
dial
scal.e
settings
are
decreased,
the
variation
will
apprqach
a
maximum
of
::,
10%
of.
the
scale
reading.
The
consistency
of
the
op-
erating
time
on
any
specific
setting
will
be
within
±.
2%.
The
resistance
of
the
various
relay
:
components
is
shown
in
Table
D.
CONSTRUCTION
The
general
construction
of
these
re-
lays
is
shown
in
Figs.
1
and
2.
The
basic
elements
are
the
driving
magnet"the
gear
train,
the
damping
magnet
and
the
time
dial
assembly.
The
auxiliary
elements
such
as
the
telephone
type
relay,
targets
and
seal-in
unit
round
out
the
con-
struction.
The
driving
mag;net,
or
rotonoid
charges
two
spiral
springs
as
it
rotates
approximately
180
degrees.
One of
the
springs
located
on
the
rotOnoid.
serves
to
l'eset
tbe
as.sembly.
The
other
in
the
gear
train
drives
the
gearing
and
the
associated
damping
system.
The
gail!;'
train
~s
anacCl!r~t~!y~~I.'1~~
bled
clock
type
mechilnism
mounted
be-
v,veen two
parallel
plates
in
such
a
manner
as
to provi(ie
proper
shaft
.end
play
and
gear
mesh
(see
Fig.
3)
..
The
charged
spring
drives
this
mechanism
at
a
speed
which
is
controlled
by
the
damping
system.
A
ratchet-pawl
assembly
permits
quick
reset:
The
damping
system
consists. of a
copper
cup
mounted
on a
shaft
rotating
in
.
an
annular
gap
across
which
exists
a
permanent
magnE)t
field.
While
the
position
of
the
cup in
the
magnetic
field
will
provide
some
control
of
the
time,
the
main
control
varies
with
thEl.
degree
to whiCh
the
spring
is
charged.
On
the
one
second
relays
the
length
of
the
copper
cup
has
been
repuced
to
provide
less
drag
which.
helps
to
obtain
the
faster
operating
time.
The
time
d'lal
assembly
is
mounted
on
the
out-put
shaft
of
the
gear
train.
The
un~t
consists
of
adjustable
insulated
cams
which Operate
the
TU~l
and
TU-2
contacts.
There
are
pointers
on
the
cams
which
can
be
lined-up
on
the
time
dial
scale.
The
time
dial
scale
on
the
three
second
relays
is
calibrated
in
tenths
of a
second.
The
one
second
relay
is
calibrated
in
cycles
(60
cycle
bases)
with
graduations
of 2.5
cycles
•.
TABLE P
VOLTAGE T RESISTANCE IN OaMS
RATING I TU R1 TX
RS
TY R4
250 I 100 300 5000 5000 7500 7500
220 I 100 250 5000 5000 7500 7500
125 100 100 5000 7500
110 100
75
5000 7500 7500
48
I
7 }'3.5 200 200 425 425
32 7 6 200 70
24 7 3 200 425
CURRENT I RESISTANCE
IN
OHMS
RATING ! TARGET SEAL-IN UNIT
0.2A I 7.5 6.0
1.0A 0.35 0.25
6
The
relays
may
have
either
a
pointed
shaped
cam
in
the
front
position
which
in
passing
closes
the
TU-1contact
momen-
tarily
or
a
contact
maintaining
cam
which
when
engaging
the
TU-1
contact
holds
it.
closed
throughout
the
timing
range.
The
"TX"
and
"TY"
components
are
telephone
type
relays.
The
seal-in
unit
is
a
small
hinged
armature
type
relay
consisting
of a
"U"
shaped
magnet
frame,
fixed
pole
piece,
armature,
and
a
tapped
coil.
The
arma-
ture
carries
a
"T"
shaped
moving
contact
which
bridges
the
two
stationary
contacts.
The
targets
are
hinged
armature
as-
semblies
with
armatures
painted
orange.
When
operated
they
release
a
shield
which
drops
and
exposes
the
orange
colored
sur-
face
of
the
armature.
RELAY CASE
Components
of
each
relay
are
mounted
on a
cradle
assembly
which
can
be
easily
removed
from
the
relay
case.
The
cradle
,is
locked
in
the
case
by
means
of
latches
at
the
top
and
bottom.
The
electrical
con-
nections
between
the
case-block
and
cradle
block
are
completed
through
a
removable
cDnnection
plug.
A
separate
testing
plug
can
be
inserted
in
place
of
the
connection
plug
to
permit
testing
the
relay
in
its
case.
The
cover
is
attached
to
the
front
of
the
case
and
includes
the
target
reset
mecha.-
nism
and
an
interlock
arm
to
prevent
the
cover
from
being
replaced
until
the
con':'
nection
plug
has
been
inserted.
The
case
is
suitable
for
either
semi-
flush
or
surface
mounting.on
panels
up
to
two
inches
thick.
Hardware
is
available
for
all
panel
thickness
up
to
two
inches,
but
panel
thickness
must
be
specified
oil
the
order
to
insure
that
the
proper
hardwar.e
will
be
provided.
Outline
and
panel
drilling
dimensions
are
shown
in
Fig.
14.
RECEIVING,
HANDLING
AND
STORAGE
These
relays,
when
not
included
.as
a
part
of a
control
panel,
will
be
shipped
in
cartons
designed
to
protect
them
against
damage.
Immediately
upon
receipt
of a
relay,
examine
it
for
any
damage
sustained
in
transit.
If
injury
or
damage
resulting
from
rough
handling
is
evident,
file
a
dam-
age
claim
at
once
with
the
transportation
company
and
promptly
notify
the
nearest
General
Electric
Apparatus
Sales
Office.
Reasonable
care
should
be
exercised
in
unpacking
the
relay.
If
the
relays
are
not
to
be
installed
immediately,
they
should
be
stored
in
their
original
cartons
in
a
place
that
is
free
from
mOisture,
dust,
and
metallic
chips.
Foreign
matter
collected
on
the
outside
of
the
case
may
find
its
way
inside
when
the
cover
is
removed
and
cause
trouble
in
the
operation
of
the
relay.
ACCEPTANCE
TESTS
Immediately
upon
receipt
O.f
the
relay
an
inspection
and
acceptance
test
should
be
made
to
insure
that
no
damage
has
been
sustained
in
shipment
and
that
the
relay
calibration
has
not
been
disturbed.

VISUAL INSPECTION
Check the
nameplate
stamping
to
insure
that
the
model
number,
rating
and
calibra-
. tion
range
of the
relay
received
agree
with
the
requisition.
Remove
the
relay
from
its
case
and
check
by
visual
inspection
that
there
are
no
broken
or
cracked
molded
parts
or
other
signs
of'
physical
damage
that
may
have
occurred
in
transit
and
that
all
screws
are
tight.
MECHANICAL INSPECTION
The
essentials
of a
mechanical
inspec-
tion
are
to
determine
that
all
of
the
operating
elements
are
free
from
any tendency to
bind
and
are
in
correct
adjustment
as
specified
below:
.L The rotonoid
-'
The
shaft
end
play
in
this
assembly
is
limited
to
insure
proper
clear-
ances
between
the
armature
and
the
spool
body. The
armature
should
rotate
without
any
tendency to bind.
2.
The
gear
train
-Check
for
end
play
in
all
the
shafts.
Rotate
the
assembly
bythe
roto-
noid
and
note
that
it
moves
with a
steady
motion to the
limit.
of
its
travel.
Permit
the
assembly
to
reset
reasonably
fast
to
check
the
action
of the
ratchet.
See
that
the
pawl
engages
the
gear
teeth
with
positive
action. Check
all
the
set
screws
to
see
that
they
are
tight.
3. The
time
dial
-Check the
action
of
the
cams
as
they engage the
timing
contacts.
They should engage
at
the
"V"
section
on~y,
causing
the
contact
to
deflect
and
close
WIth
about 1/64:" wipe. The
contact
gap
at
the
TU-1
and
TU-2
contact
should
be about
1/16".
" .
4:.
Telephone Type relays. -With
t~l.ephone
relays
in
the
de-energIzed
posibon
all
circuit
closing
contacts
should have a gap
of 0.015" and
all
circuit
opening
contacts
have a wipe of 0.005". Gap
maybe
checked
by
inserting
a
feeler
gage
and
wipe
can
be
checked by
observing
the amount of
de-
flection
on the
stationary
contact
before
parting
the
contacts.
The
armature
should
then
be'
operated
by hand
and
the gap
and
wipe
again
checked
as
described
above.
5.
Seal-In
unit
-
The
seal-in
unit
should
be
checked
as
follows: The
armature
and
seal-
in
contacts
should move
freely
when op-
erated
by hand.
There
should be a
screw
in
only one of the tap
positions
on the
right
stationary
contact
strip.
Operate
the
arma-
ture
by hand and check
that
there
is
at
least
1/32"
wipe on
the
seal-in
contacts.
6.
The
targets
-
Operate
the
armature
and
note
that
when
the
shield
drops
the
armature
will
continue to
travel.
This
indicates.
that
the
shield
will
have adequate
clearance
when
it
falls.
ELECTRICAL TESTS
The
following
electrical
tests
are
recommended
upon
receipt
of
the
relay.
1. Make
time,tests.
2. Check
minimum
operating
value of
telephone
relay.
3. Check
target
and
seal-in
unit
pickup .
values.
Check the
time
calibration
using
the
connections shown in
Fig.
6. Check the
operating
time
:;tt
the
maximu~
time
range
setting
and agaro
at
some
porot about
1/2
of the
time
range.
The
relay
timing
ac-
curacy
should be within the
test
limits
indicated
in the
section
under
CHARAC-
TERISTICS. The
test
circuit
is
arranged
to include the
seal-in
unit
time
which
was
not included in
the
factory
time
setting.
Howe:ver~
since
this
seal-in
wiit
time
is
about 0.01
seconds,
it
will have
little
effect
on the
final
results.
Using connections shown in Fig. 7 the
telephone type
relays
should
pick
up
at
80%
or
less
of
rated
voltage. When
testing
the
RPM15
relays
the
normally
closed
contacts
of the TY
relay
should blocked open
and
the
TU-2
(rear)
contact
should be
closed
manu-
ally.
This
is
to
prevent
the
operation
of
solenoid TU
so
that
the
regulation
of the
test
circuit
will
be adequate to
permit
reliable
test
results.
Using connections shown in Fig. 7
check
the
targets
and
the
seal-in
unit
pickup. to
confirm
that
they
:will
operate.
on
rated
current
or
less.
While
making,
these
.. test!:; the Qperating
cams
caIJ. be
manually held in the
proper
position
to
keep the
desired
contact
closed.
When
seal-in
unit
(SI)
is
picked
up the opening of
switch
"S" should not
de-energize
this
unit.
Connections
can
be
made
to the
relay
studs
but
for
panel-mounted
relays
a
test
plug
can
be
used
to faCilitate the
operation.
Since
the
rotonoid
has
only a one minute,
rating,
the
operator
must
be
sure
that
this
solenoid
is
not
damaged
by overheating.
If
as
a
result
of
these
tests
any
adjustments
are
necessary,
refer
to the
section
on
SERVICING
for
information.
INSTALLATION
PROCEDURE
If
after
the ACCEPTANCE TESTS the
relay
is
held in
storage
before
shipment
to
the
job
site,
it
is
recommended
that
the
visual
and
mechanical
inspection
described
under
the
section
on ACCEPTANCE TESTS
be
repeated
before
installation.
It
is
also
advisable
to
check
the
specific
time
settings
that
are
to be
used.
PERIODIC
CHECKS
AND
ROUTINE
MAINTENANCE
In view of
the
vital
roll
of
protective
relays
in the
operation
of a
power
system
it
is
important
that
a
periodic
test
program
be followed.
It
is
recognized
that
the
interval
between periodiC
checks
will
vary
depending
upon environment, type of
relay
and the
user's
experience
with
periodic
testing.
.Until
the
user
has
accumulated
enough
experience
to
select
the
test
interval
best
suited
to
his
individual
requirements,
it
is
suggested
that
the
followingpointsbe
check-
ed
at
an
interval
of
from
one to two
years.
ELECTRICAL TEST
Using connections shown
in
Fig.
6
check
the
operating
time
of the TU-1 and TU-2
contaCts
at
rated
voltage
and
present
time
Timing
Relays
Type RPM GEH-2031
setting
to
be
sure
they
are
within the
limits
specified
under
ACCEPTANCE TEST and,
that
the
targets
operate
properly.
If
for
any
reason
the
operating
times
are
outside
these
limits,
refer
to
the
SERVICING section.
SERVICING
CONTACT CLEANING
For
cleaning fine
silver
contacts,
a
. flexible burnishing tool should be
used.
This
consists
of a flexible
strip
of
metal
with
an
etched
roughened'surface,
resem-
bling
in
effect
a
superfine
file.
Thepolish-
ing
action
is
so
delicate
that
no
scratches
are
left,
yet
corroded
material
will be
removed
rapidly
and thoroughly. The
flexibility
of the tool
insures
the
cleaning
•of the
actual
points
of contact.
Fine
silver
contacts
should not
be
-cleaned with knives,
files
or
abrasive
paper
or
cloth. Knives
or
files
may
leave
.
scratches
which
increase
arcing
and
de-
terioration
of the
contacts.
Abrasivepaper
or
cloth
may.
leave
minute
particles
of
in-
sulating
abrasive
material
in the coritacts,
thus
prevent
closing. ,
A
burnishing
tool
as
described
above
can be obtained
from
the
factory.
MECHANICAL ADJUSTMENTS
The
specific
adjustments
and
setting
on
this
relay
should
rarely
require
atten-
tion.
If
for
one
reason
or
another
they
have
been
disturbed
the
following
points
should be
observed
in
restoring
them:
1. The gap between the
contact
tips
on
each
set
of
the
timing
unit
contacts
should
be apprOximately
1/16
inch.
Each
contact
brush
should
bear
against
its
respective
scraper
brush.
.2. When
rotated,
the
insulated
cams
should
touch the
inner
contact
brush
at
the "V"
only,
but
high enough on
the
"V"
to
insure
1/64: inch wipe on the 'outer
contact
brush.
These
cams
should not extend beyond the
edge of
their
respective
contact
brush.
3. With the
pointer
'of the
rear
insulated
cam
set
at
the
maximum
time
setting
on
the
scale,
this
cam
should
rotate,
far
enough beyond the apex of the
"V"
in the
contact
brush
to allow
the
contacts
to
re-
,open when the
timing
unit
is
fuily
operated.
4.
There
should be
at
least
1/32
inch
clearance
between the
time
scale
assembly
and the
front
mounting
plate~
5.
There
should be no binding between
the
gear
on the main
shaft
and
the
pinion
on
the
magnetic damping
element
shaft.
6. The pawl of the
ratchet
assembly
on
the magnetic damping
element
shaft
should
'remain
engaged to the
same
tooth when
the
time
scale
is
rotated
from
zero
to 'the
maximum
time
setting
mark
and
should
allow
the
gear
to
slip
when the
scale
is
released.
7. The flexible
stop
arm
at
the
rear
of
the
main
shaft
should
clear
the supporting
bracket
by
at
le::tst
1/32
inch. .
7

GEH-2031 Timing
Relays
Type RPM
8
tc
SLnty
RAlBI
VDlTACE
•
Tl
13
,
15
RElAYS
----I----r
, . ®
r·
L •
rl
TlU•
,.-,
TlU-l
__
RPM
13
,
15
RPM
13
RPM
15
-SEa.
IN--....-
4
TARGET
...
TIIICiET
atIJ
SEa.
IN
lJIIT
TEST
aHECTlatS
F~
RPM
13
&
15
5
Tl
AC
SUPPLY
TIMER
CLUiCH
COIL
At.
INlJII T
1lJRREHT)
/~
\
'I

(J
8. With
the
operating
magnet
in
either
the
de-energized
or
the fully
operated
posi-
tion, the driving,
arm
should
clear
the
cutout
section
of the
main
shaft
supporting
bracket
by
at
least
1/32
inch.
9. The
driving
arm
assembly
should
clear
the
rear
mounting
plate
by
at
least
1/32
inch.
10.
There
should
be
at
least
1/64
inch
clearance
between
the
reset
spring
collet
and
the
rear
bearing
of the rotonoid.
11. The
time
of
operation
for
any
scale
setting
may
be
varied
by
sliding
the
copper
cup
forward
or
backward
on
its
shaft
or
turning
the
driving
spring
collet
on
its
shaft.
Be
Sure
to
tighten the
set
screw
,
after
adjustments
have
been
made.
12. With
the
rotonoid
de-energized,
the
reset
spring
is
prewound
approximately
one-half
revolution-and
the
driving
spring
is
prewound
approximately
three-fourths
of
a
turn.
13.
The
gap of
all
TX and TY
unit
con-
tacts
should be 0.015".
14. The wipe of
all
TX
and
TY
unit
con-
tacts
should be
approximately
0.005 inch.
15. The end of
the
residual
screw
of
the
TX
unit
should
project
at
least
0.002"
beyond the
inside
surface
of
the
armature.
16.
The
seal-in
unit
should have
at
least
1/32"
wipe on
its
contacts,
measured
at
the
end of
the
armature
adjacent
to the
contacts.
If
wipe
is
too
small,
it
can
be
increased
by
lowering
the
position of
the
stationary
contact
members.
In
the
final
adjustment
the
contacts
should
make
ap-
prdximatelyaftlie-same
liistant
whe
-the
armature
is
operated
by hand.
TIME
CALm~ATION
Adjust
the
front
cam
so
that
it
ap-
proaches
the
zero
mark
on the
time
cilal
scale.
The TU-1
contact
should
just
make
when the pOinter
reaches
zero.
Set the
time
dial
at
its
maximum
setting
and with
the
test
cii'cuit
shown iil
Fig. 6
check
the
time
at
rated
voltage.
The
limits
should
be
within
:±:.
5%
of
the
dial
reading.
'If
the
time
is
outside
these
limits
Timing
Relays
Type RPM GEH-2031
it
can
be
corrected
by
sliding
the C JPper
cup
forward
or
backward
on the
magnetic
damping
element
shaft
or
by
turning
the
driving
spring
collet
on
its
shaft.
Moving
the
copper
cup
forward
de-
creases,
the
time
delay and moving
it
backward
increases
the
time
delay.
Never
move
the
copper cup backward enough to
strike
the
rear
plate
of damping
magnet
element.
Turning the
driving
spring
collet
in a
counter
clockwise
direction
(front view)
decrease
the
time
delay and in a clockwise
direction
increase
the
time
delay.
RENEWAL
PARTS
It
is
recomm
ended
that
sufficient
quan-
tities
of
renewal
parts
be
carried
in
stock
to enable
the
prompt
replacement
of
any
that
are
worn,
broken
or
damaged.
When
ordering
renewal
parts,
address
the
n'earest
Sales
Office of the
General
Electric
Company, specifying the quantity
required
and
describing
the
parts
by
cata-
logue
numbers
as
shown in Renewal
Parts
Bulletin
No. GEF-3835.
9
I
I
I
·1
1
j
I
I
1
I
I
I

====,,--,-~~~-~~-~
,-----_
..
-
GBB-2OS1
Timing Relays Type RPM
VOLTS
RES
I
STANCE
TX
TU
RI
VOLTS
RESISTANCE
,
125
!l000
100
10,0
TX
R3
TU
RI
"110
500"0
100
75
.,
211' '
-200
7 3
250
5000
5000
100
300
118
200
200
7
13.5
220
COOO
5000
100
250
32
200
7IJ 7 II
S
..
I 1
R3N
L1
S.L.
'
IX'
- - 1
5,.
L.
Tl
i"
I--
TX
TX
TU
~
s. L.
I I I
-I
II,
"r
,'I'
'I,'
"I,',
1 ,
}-
~
,_'
V "
~
,,
2
'4"
'"
Ii
'
,8_
'10'
l III
~
I{III
2 4
".'
8
10
Fig.
8
(6375892~2)
Internal
Connections
(Front
Ylew) For
~
RFMI3A,
Band
D Relays Rated
2~,
110
or
125
YDC
FIg.
II
(1375893-5)
Internal
Connections
(Front
View) For
The
IPMI3A,
'~d
D Relays Rated 32,
~8,
220or,250,YDC
i
vom
,
RES
I
STAliCE
~
,
...
'IX
R3
TU
Rl
TY
'R4
,VOlTS
REStSTMCE
TX
'TU
'Rl
" 'lY
148
200
200 7 13.5 425 '425 ,24
200
'7
3 425
r
250
5000
5000
100 300 7500 ,
7500
125 5000 100 100 '7500
I 220 5000 5000 100 250 7500 7500 110 5000 100 75 7500
r-
J-~
OR3
tTY
:-
51
,¥TY
,Wl
;:;.51
I
it--
t---
,
'Tl
T2
t-:--
ITX
[}.
TX
TX
';>
~
TU
TY
TV
.---
tTY
IIT~
1_n
-
'51
;
¥-TY
,<
SI
RiO
:
t--
I--'-
TY~
-T1
T2
I--
::-
TX
I
rx
',T"('
TX
?TU
0--
'I
I
3
\
"I
\
\,
~
I I
3
2
Fig.
10
(~3AI8~-2)
Internal
Connections
(Front
View) For The
RPMISA
Relays Rated
~,
220
or
250
VDC
Fig.
II
(IJOSAI83-3)
Internal
Connections
(Front
View) For The
RPMI5A
and C Relays Rated
2~,
110
or
125
'DC
10

r',
'\.
-')'
c)
VOLTS
Rl
TV.
24
j
..
125 100
7!!1!1l
110
7J
7.
SI
51
•
r~.
J
~
I
';g.
12
(!27A9402-1)
W,rn"
COMOOtlS
(F'oot
Vi,w)
Fo,
Th.
!!I'
I
51
6
I
RPM15B
Relays
Rated
24, 110
or
125 VDC
51
r
~
-r
~
5 r
2
l!
6
TI
T2
~
7
1Y
.tlQIE;POLARITY
ON
TX
COILS MUST
BE
THE
SAME,
OTHERWISE
THEY WILL
,.!!l.!QL
*
Fig.
14A (0208A5573-0) Sh.1
Internal
Connections
(Front
View)
For
The
RPM
15DRtHay
_
'<-"ff
*
Denotes
change
smce
supersededllssue.
Timing
Relays
Type
RPM
GEH-2031
RESISTANCE
VOLTS
TX
R3
I
TU
1
Rl·
jW
I
R4
41!
200
200]
7
Il~.5
i42!l I 425
250
5000
5000
,100 I
;:100
1
7500
17500
1220
5000
5000
j 100 I
~"c
7500:
,
7500
'-
51
51
...
--
t----
-Fig.
13
(127A9401-0)
Internal
Connections
(Front
View) Fo!"
The
RPM15B
Relays
Rated
48,220
or
250
'roc
RESISTANCE
VOLTS
TX
TU
!
Pi
I
TY
48 I I
i
125
5K
15K
100
100
I7,5K
I I
250
1 L
...
~
........
*Fig.
14B (020SA5573-0) Sh.2)
Internal
Connections
(Front
View)
For
The
RPM
15D
Relay
11

GEH-2031
Timing
Relays
Type
RPM.
-
m·
606b6
00000
·2
4 6 8
10
Ii)
NUMBE~NG
OF
STUDS
(fRONT
VIEW)
.
PANEL
.DRILLING
FOR
SEMI-FLUSH
.
MOUNTING
(FRONT
VIEW)
PANEL
LOCATION
SEMI-FLUSH
SURFACE
~TG.
..
.
MTG.
"IH11~'
r-
-1
m
V
.:..
.--
1110-32-
~
MTG.
~
8
SCREW
vLl
OUTLINE
r
:I
PANEL
V
U
VIEW
.SHOWINGASSEMBLY
OF
HARDWARE
FOR
SURFACE
Nrc;.
ON
STEEL
PANELS
.
Fig.
I~
(6209271-3) Outline
And
Panel
Drilling
DI.enalons For
The
RPM
Relays Covered
By
This
IIoGk
3-7l
GENERAL
ElECTIIC
COMPANY,
PHILADELPHIA,
PA.
•
This manual suits for next models
6
Table of contents
Other GE Relay manuals