ESPEC SCP-220 User manual

SCP-220 CONTROLLER
INSTRUCTION MANUAL


PLATINOUS SERIES CONTROLLER MANUAL 1
TABLE OF CONTENTS
Introduction....................................................................................................................................................1
1. Overview ...................................................................................................................................................3
1.1. Setup and Monitor Function Tree.....................................................................................................3
1.2. Operation Interface...........................................................................................................................4
1.3. Screen Layout...................................................................................................................................4
1.4. Touch Screen Operation...................................................................................................................5
2. Monitoring.................................................................................................................................................7
2.1. Chamber Monitor..............................................................................................................................7
2.2. Trend Graph .....................................................................................................................................8
2.3. Detail Monitor: Chamber..................................................................................................................9
2.4. Detail Monitor: Time Signal Monitor ..............................................................................................10
2.5. Detail Monitor: Program Monitor....................................................................................................11
3. Constant Mode Setup ............................................................................................................................13
3.1. Constant Mode Setup.....................................................................................................................13
3.2. Time Signal ON/OFF......................................................................................................................14
3.3. Product Temp. Control (Option) Detail...........................................................................................15
4. Program Mode Setup.............................................................................................................................16
4.1. Program Create..............................................................................................................................16
4.2. Product Temp. Control (Option) Detail...........................................................................................21
4.3. Other Setup ....................................................................................................................................22
4.3. To Quit Program Setup...................................................................................................................24
4.4. Step Insert.......................................................................................................................................25
4.5. Step Copy.......................................................................................................................................26
4.6. Step Delete.....................................................................................................................................28
4.7. Program Delete...............................................................................................................................29
4.8. Program Copy.................................................................................................................................30
4.9. Program View.................................................................................................................................32
5. Chamber Setup......................................................................................................................................35
5.1. Timer Setup ....................................................................................................................................35
5.1.1. Start Timer Setup .....................................................................................................................35
5.1.2. End Timer Setup.......................................................................................................................37
5.2. Timer ON/OFF................................................................................................................................40
5.3. High/Low Limit Alarm Setup...........................................................................................................41
5.4. Sampling Setup and ON/OFF.........................................................................................................43
5.5. Protection........................................................................................................................................44

PLATINOUS SERIES CONTROLLER MANUAL 2
5.6. Defrost Setup (Option)....................................................................................................................46
5.7. Humidity Calculation.......................................................................................................................46
5.8. Alarm Report View..........................................................................................................................48
5.9. ROM Information View....................................................................................................................49
5.10. Service Guide...............................................................................................................................50
5.11. Chamber Configuration.................................................................................................................51
5.11.1. Selecting Maintenance Items.................................................................................................51
5.11.2. E-BUS Setup (Optional) .........................................................................................................53
5.11.3. Power Recovery Setup...........................................................................................................54
5.11.4. Control Attainment Range Setup............................................................................................55
5.11.5. Analog Output Setup..............................................................................................................56
5.11.6. Name Time Signals................................................................................................................57
5.11.7. Date & Screen Saver..............................................................................................................58
5.11.8. Register User Password.........................................................................................................59
5.11.9. Sensor Offset..........................................................................................................................59
5.11.10. Buzzer & Wick Water Supply................................................................................................60
5.11.11. Product Temperature Control (Option) Setup......................................................................62
5.11.12. Service..................................................................................................................................64
6. Operation Modes....................................................................................................................................66
6.1. Restrictions on Operation Control ..................................................................................................66
6.2. Startup in the Constant Mode.........................................................................................................67
6.3. Ending the Constant Mode.............................................................................................................68
6.4. Program Selection..........................................................................................................................69
6.5. Startup in the Program Mode..........................................................................................................70
6.6. Pausing in the Program Mode........................................................................................................71
6.7. Restarting in the Program Mode.....................................................................................................72
6.8. Jump to Next Step..........................................................................................................................73
6.9. Ending in the Program Mode..........................................................................................................74

PLATINOUS SERIES CONTROLLER MANUAL 1
Introduction
This manual has been written for users of the Platinous Sterling Series Chambers and particularly for
technicians. Read it thoroughly to obtain the maximum performance from the chamber.
Safety Symbols
The following safety symbols are used throughout this manual.
Degrees of Danger
!
VERY
DANGEROUS
This mark means extremely dangerous
consequences may arise, with the possibility of
death or serious injury to the user, if the
equipment is handled incorrectly.
!
DANGER
This mark means dangerous consequences
may arise, with the possibility of death or
serious injury to the user, if the equipment is
handled incorrectly.
!
CAUTION
This mark means dangerous consequences
may arise, with the possibility of somewhat
serious injury to the user and/or damage to
equipment and facilities, if the equipment is
handled incorrectly.
Key Words
The following keywords are used in this manual.
Note : Provides information necessary for gaining full performance from the
chamber or to prevent damage to equipment
Procedure :Explains how to operate the chamber on a step-by-step basis.
Reference :Offers supplementary information.
Displays Used in This Manual
This manual is based on temperature & humidity chambers of the Platinous Sterling Series. Graphic screens
displayed on temperature-only chambers will differ in part from those herein. As shown below, they do not
have humidity items.

PLATINOUS SERIES CONTROLLER MANUAL 2
Chamber Monitor for Temperature-Humidity Chambers
Chamber Monitor for Temperature-only Chambers
Document Composition
The user’s manual composition that came with your chamber contains the following reference materials. Use
them as necessary.
Manual Content
Instruction Manual Explains the basics of the Platinous Sterling Series.
SCP-220 Controller Explains operation from the instrumentation panel in
greater detail.
Quick Reference Reorganizes setting procedures into a simple, handy
digest.
Options
- Options (excluding the communication function and
temperature and humidity recorder)
- Communications Option
- Temperature and Humidity Recorder
Explains how to operate optional features. Option
manuals always have priority over the above
reference materials when found in disagreement.

PLATINOUS SERIES CONTROLLER MANUAL 3
1. Overview
The SCP-220 Instrumentation is a graphic interface for operating and monitoring the chamber. The user
moves from menus to monitor and setup screens as he/she prepares and conducts tests. The software is
divided into setup, operation and monitoring functions. This chapter gives an overview of each of them.
1.1. Setup and Monitor Function Tree
Below is a function tree of the setup and monitor interface.
Temperature/Humidity
Trend Graph
Main Menu Detail Monitor Chamber
Time Signal Monitor
Program Monitor
Chamber
Monitor
(Displayed only in
the program mode)
Constant Mode Setup
Constant Setup Time Signal ON/OFF (Option)
Edit
Delete
Copy
Program Setup
View
Timer Setup
Start/End Timer Setup
High/Low Limit Setup
Sampling Setup
Protection ON/OFF
Configuration
E-Bus Setup
GP-IB Setup
RS-232C Setup
Power Recover Setup
Control Attainment Range Setup
Analog Output Setup
Name Time Signals
Date & Screen Saver
Register User Password
Sensor Offset
Buzzer & Wick Water Supply Setup
Product Temperature Control Setup
Service
Defrost Setup (Option)
Humidity Calculation
Alarm Report View
ROM Information View
Chamber Setup
Service Guide
Fig. 1.1. Setup & Monitor Interface

PLATINOUS SERIES CONTROLLER MANUAL 4
1.2. Operation Interface
The operation interface gives the user start and stop control over the constant and program modes. Below is
a function tree of this interface.
OPER./STOP
KEY Stop Operation
Constant Mode START
PGM Selection
Step No.
START
PAUSE
RESTART
Program Mode
NEXT STEP
Fig. 1.2 Operation Interface
1.3. Screen Layout
The instrumentation display is composed of top, middle and bottom areas.
Top Display Area
1. Displays chamber operating status. Also, pressing this box displays the Operation Mode
Selection screen.
2. Flashes when an alarm occurs. Also, pressing this box displays the Alarm Screen, though the
screen is displayed automatically when an alarm is generated.
3. Yellow when the timer is ON. Also, pressing this box displays the Timer Setup Screen.
1
2
Top
Middle
Bottom
3
4
5

PLATINOUS SERIES CONTROLLER MANUAL 5
4. Flashes during communications between the chamber and the PMS-CA(CG) protocol
converter. Also, pressing this box displays the E-BUS setup screen, unless a password has
been registered with the instrumentation.
5. Displays the date and time. Also, pressing this box displays the Date and Screen Saver
Screen, unless a password has been registered with the instrumentation.
Middle Display Area
This is the main display area. The name of the screen is given in the upper left hand corner.
Bottom Display Area
This area displays screen access buttons and a simple guide to working the current screen.
1.4. Touch Screen Operation
This section explains basic elements displayed on the touch screen. Other screen elements are
explained in greater detail in the subsequent chapters.
Processing Buttons
PREV. SCREEN Button :Stops processing in course and returns the display to the previous
screen. If pressed before data changes are entered, a message
confirming whether to suspend the operation or not is displayed.
YES Button :Executes the displayed operation. Read carefully the message
displayed on the screen before pressing this button.
NO Button :Cancels the current operation. Processing is suspended and the
display returns to the previous screen.
SAVE Button :Saves data updates. A message confirming whether to execute the
operation or not is displayed on the screen.
MAIN MENU Button :Returns the display to the main menu.
Selector Boxes
ITEM BOX :Selects the item given in the box. When selected, the box is
highlighted.
lON :Pressing the box selects and deselects the given item.
When selected, the dot is yellow.
Field Boxes
FIELD BOX :When pressed, a keypad is laid over the screen to enable text or
numerical input.
* Other screen elements are inactive while the keypad is displayed.

PLATINOUS SERIES CONTROLLER MANUAL 6
Keypad: Numerical
Input
0 ~ 9 keys :Use for numerical input.
. key :Use to input a decimal point.
--- key :Use to input negative numbers.
CLR key :Clears the value in the text box.
DEL key :Deletes the value left of the cursor.
QUIT key :Cancels the displayed input and returns the display to the original
screen. The input value is ignored.
ENT key :Enters the displayed input and returns the display to the original screen.
Keypad: Text Input Text can be input in Roman Alphabet or Japanese Kana.
CLEAR , DEL , QUIT
ENTER keys :These keys function in the same way as when inputting numerical
values though the names of the keys are slightly different.
SPACE key :Inputs a space.
mCAPS key :Switches between capital and small case letters.
When the dot is yellow : CAPITALS
When dot is black : small case letters
key :Switches between the roman alphabet and kana modes.
When dot is yellow: kana
When dot is black: Roman alphabet.

PLATINOUS SERIES CONTROLLER MANUAL 7
2. Monitoring
2.1. Chamber Monitor
* In the following situations, “- - -“ is displayed in the field boxes.
•If a sensor input error occurs
•If either dry/wet-bulb temperature is outside the 0 ~ 100°C range (for humidity display only)
•When humidity control is OFF (However, humidity is displayed while the chamber is stopped,
even if control is OFF.)
Target
Temperature
Target
Humidity
Monitored
Conditions

PLATINOUS SERIES CONTROLLER MANUAL 8
2.2. Trend Graph
Horizontal Axis
The horizontal axis determines the data sampling interval. The time scale can be selected between
10 minutes and the Max. Rec. time set on the Sampling Setup Screen.
Range Control
Expand :Increases the displayed scale.
Reduce :Decreases the displayed scale.
Display Control The displayed position of the graph can be shifted to the left or right.
ç :Scrolls the data to the left.
è :Scrolls the data to the right.

PLATINOUS SERIES CONTROLLER MANUAL 9
2.3. Detail Monitor: Chamber
Table 2.1. Detail Monitor: Chamber Screen
Process Value Displays the value currently monitored inside the
chamber.
Set Point Displays the current control target setting.
Heater % In temperature-controlled operations: Displays
heater output.
In humidity-controlled operations: Displays
humidifying heater output.
Refrig. Control Indicates refrigerator status. (Running/Stop)
Time Signals Indicate time signal output status.
Temperature
Air/Product Displays the chamber air temperatures if “AIR” is
displayed, displays product temperatures if
“PRODUCT” is displayed. (For details on
air/product temp control, see section 5.11.11.)

PLATINOUS SERIES CONTROLLER MANUAL 10
2.4. Detail Monitor: Time Signal Monitor
Table 2.2. Time Signal Monitor Screen
Specimen PWR CNTL Indicates whether power is being supplied
to specimens or not. Power supply to
specimen is cut when the alarm occurs.
Standard Time Signal (1/2) Indicate whether the user-set time signals
have been output or not.
Ext. Alarm Indicates whether an alarm is currently
active or not.
Options Time Signal
(3 ~ 8) Indicate whether the user-set time signals
have been output or not.
Reference You can create or change Time Signals. For details on naming, see “Name Time Signals” in
“5.11. Chamber Configuration”.

PLATINOUS SERIES CONTROLLER MANUAL 11
2.5. Detail Monitor: Program Monitor
This screen can only be displayed during programmed operations. It contains information on the
program being run.
1. PGM Name
Displays the No. and name of the program being run.
2. Current Step
Displays the No. of the step currently being executed.
3. End Step
Displays the No. of the last step in the program.
4. Temp. SP
Indicated the current target temperature of the step being run. Displays “AIR” below “Temp.” if
air control is active, shows “PRODUCT” below “Temp.” if product control is active. (For details
on air/product temp control, see section 5.11.11)
5. PV
Displays the monitored temperature.
6. Hum. SP
Indicates the current target humidity of the step being run.
(For temperature & humidity chambers only)
7. PV
Displays the monitored humidity.
(For temperature & humidity chambers only)
8. Time to Step End
Displays the time left until the step ends. Time is counted down.
9. Scheduled Test End
Displays the time scheduled for the test to end. The following are not included in the schedule.
•Temperature stabilization time when soak control is ON
•Time gained when jumping to the next step in programmed operations
10. Total Run Time
1
3
8
9
10
11
12
2
4
5
6
7
12

PLATINOUS SERIES CONTROLLER MANUAL 12
Displays the total time the program has run up to the present. Time is counted up and it
includes time lost to alarms and time consumed while the chamber is paused.
11. End Mode
Displays the operating mode the chamber will assume at program end.
12. Counter A/B
Displays repeat range, current repeat cycle and the set number of repeat cycles for each of
the counters. “- -“ is displayed if the counters are OFF.

PLATINOUS SERIES CONTROLLER MANUAL 13
3. Constant Mode Setup
This chapter explains how to set up the constant mode. The constant mode is the basic chamber
operating mode.
3.1. Constant Mode Setup
The following procedure explains how to make control settings for the constant mode.
1. Get the constant setup mode.
Press the Constant Setup box on the main menu.
TEMP.
2. Input the target temperature (& humidity).
Pressing the field box next to Temp. SP and Hum. SP lays a keypad over the screen to
enable input. Make your input from there.
* If OFF is displayed next the Hum. SP, the target humidity cannot be set. Turning humidity
control ON will enable input.

PLATINOUS SERIES CONTROLLER MANUAL 14
3. Turn humidity control ON/OFF as needed. (For temperature-only chamber only).
Press the mON box next to Hum. Control to make the setting.
When the dot is yellow: Humidity control is ON.
When dot is black: Humidity control is OFF.
4. Turn product control ON/OFF as needed. (If the chamber includes product control option).
Press the mON box next to Product Control to make the setting.
When the dot is yellow: Product control is ON.
When dot is black: Product control is OFF.
5. Set refrigerator capacity control.
Select between auto and manual (OFF/20%/50%/100%) control.
Normally, set to auto control.
(Use only OFF or AUTO).
6. Turn the time signals ON/OFF as needed.
Press the mON box next to Time Signal to make the setting.
When dot is yellow: ON Time signal is output.
When dot is black: OFF Time signal is not output.
Reference You can name time signals. For details on naming, see “Name Time Signals” in “5.11. Chamber
Configuration”.
3.2. Time Signal ON/OFF
1. Pressing the Time Signal button at the bottom of screen to get the Time Signal ON/OFF
screen.
2. Turn the time signals ON/OFF as necessary.
Press the mON box next to each time signal to make the setting.
When dot is yellow: ON Time signal is output.
When dot is black: OFF Time signal is not output.

PLATINOUS SERIES CONTROLLER MANUAL 15
Reference You can name time signals. For details on naming, see “Name Time Signals” in “5.11. Chamber
Configuration”.
3.3. Product Temp. Control (Option) Detail
1. Press the P.T.C. Detail button at the bottom of screen to get the product temp. control detail
screen. The P.T.C. Detail button will not be enabled if your chamber does not have the
product temp. control option.
This screen is for setting the plus and minus deviation limits. The deviation limits are the allowable
air temperature deviation from product temperature set point under product temperature control
mode. The "plus" value will be added to the product temperature set point to create the "upper" air
temperature limit. The "minus" value will be subtracted from the product temperature set point to
create the "lower" air temperature limit.
When the product temp. process value is far away from the product temp. set point, the controller
will “drive” the air temperature set point to this maximum upper (or lower) deviation limit. As the
product temp. process value gets closer to the product temp. set point, the air temp set point will
change so that it is less than the maximum upper (or lower) deviation limit.
2. Press the number box next to Max or Min deviation to input the deviation limit values. A
keypad will be overlayed on the screen to enable numeric input.
How to determine the upper and lower deviation limits
If the user is unsure of what value to set for the upper and lower deviation limits, they can use the
following procedure for help in determining the proper temperature offset. (Note: This method
requires the user to have some way of measuring both product and air temperature process
values, such as a recorder or a temperature meter.)
1. Run the chamber with the selected test product to the desired product temp. set point
with product temperature control turned OFF. Run this “test” in constant mode.
2. When the air temperature has reached the desired set point, record the temperature
difference between the product and the air temperature.
3. Use this temperature difference as the deviation limit setting. Enter the value into the
“+” setting for product heat up. Enter the value into the “-“ setting for product cool
down.
4. Execute this procedure for heat up and cooling cycles in order to determine the upper
(“+”) and lower (“-“) deviation limits.

PLATINOUS SERIES CONTROLLER MANUAL 16
4. Program Mode Setup
This chapter explains how to set up the program mode.
4.1. Program Create
Programs are created by inputting or editing target temperature, humidity and time for each program step.
The basic procedure is as follows.
1. Get the program setup mode.
Press the Program Setup box on the main menu.
TEMP.
2. Select a program area in which to create a program.
Press a number box. Existing programs can be selected for editing in the same way. The
name and the number of steps are not displayed for unregistered programs.
* ROM programs are for viewing only.