QUICK REFERENCE INSTALLATION GUIDE | PART NO. 25548 REV 0.0
3
Your Information Technology Department is the best source of information if you encounter problems or difficulties in
connecting to or communicating with the dehydrator. The ADH NETCOM Ethernet communications run at 10Base-T and half
duplex. It is recommended that the network interface to the ADH NETCOM be manually set to these parameters and NOT to an
auto-configure mode.
After changing the IP address of your dehydrator to a network other than the default 192.168.52.0 you will not be able to access
the dehydrator from the configuring computer unless that computer is reconfigured for the newly assigned network address.
Temporarily assign computer an IP address in the
192.168.52.0 network range, typically 192.168.52.1,
with the subnet 255.255.255.0
Connect the dehydrator to your computer either
directly or through a network. For direct connections
a cross-over cable or switch may be required for
connecting to an older computer; an Ethernet patch
cable will work in most other cases.
Open a web browser and connect to web interface at
HTTP: //192.168.52.9
1.
2.
3.
IP SETTINGS
Go to Configuration page
If using a fixed IP address, select “Use the following IP
address:” Then set the IP address, mask and gateway.
If using DHCP, select “Obtain IP Address
Automatically.”
Click Submit. You should see a message that the
dehydrator is rebooting.
1.
2.
3.
4.
CONFIGURING IP ADDRESS
Using a web browser, connect to the dehydrator. Go
to the Configuration page
Using the Units pull-down select English (PSI) or SI
(mbar).
To change the operational pressure setting enter the
following:
Low Alarm - The pressure at which Low Pressure
will cause an alarm condition.
Low Limit - The low set point at which the unit will
start pumping.
High Limit - The high set point at which the unit
will stop pumping.
High Alarm - The pressure at which High Pressure
will cause an alarm condition.
Click submit.
1.
2.
3.
4.
CONFIGURING PRESSURE
IP Pressure Parameters Module
Configuration Module