Technical Data: LBC160-2503PSNME AC-22(160A AC-23)
Enclosed Door Interlocked Load Break Switches
Important Safety Notice
It is the responsibility of the person installing the electrical equipment to ensure that the installation meets the
requirements of the IET wiring regulations and is therefore ‘fit for purpose'. Factors such as correct selection
of components, cable sizing, protective devices and Earth bonding are all critical and should be checked prior to
full testing and power-up. Any other regulations applicable to the equipment being installed such as the Machinery
Directive and current health and safety legislation must also be adhered to.
Terminals, including factory fitted, should be checked periodically to ensure correct tightness.
DO NOT USE POWER TOOLS ON THESE PRODUCTS
RKEMA Certified REN 60947-1 & 3 Compliant RIP65
Data Range Units LBC1603PSNME LBC2003PSNME LBC2503PSNME
Rated thermal current Ith at 40°C Amps A 160 200 250
Rated insulation voltage UiVolts V 1000 1000 1000
Rated dielectric strength Volts kV 4 5 5
Rated impulse voltage Uimp Volts kV 8 8 8
Rated operational current Ieat 400V AC-22 Amps A 160 200 250
Rated operational current Ieat 400V AC-23 Amps A 160 160 160
Rated operational power Peat 400V AC-23 Watts kW 89 89 89
Rated breaking capacity Amps A 1280 1280 1280
Rated making capacity Amps A 1600 1600 1600
Rated short circuit making capacity (peak value)
Icm Amps kA 13 13 13
Rated short-time withstand current (1 sec)
rms Icw Amps kA 7 7 7
Minimum number of mechanical operations - Cycles 10,000 10,000 10,000
Minimum number of electrical operations @
400V AC-22 - Cycles 1,000 1,000 1,000
Terminal Capacity (rigid copper cable) - mm² 95 120 120
Lug bolt size - - M10 M10 M10
Maximum size of busbar connection - mm 5x30 5x30 5x30
Tightening torque - Nm 13 13 13