Every Control FK 203T User manual

Every Control S.r.l. • FK 203T • Sheet 1/2
1 PREPARATIONS
1.1 How to install the instrument
Panel mounting, panel cut out 71 x 29 mm (2.79 x 1.14 in), with
click brackets (they are supplied by the builder) or screw brackets
(by request).
(1) maximum depth with screw terminal blocks (by request)
(2) maximum depth with extractable terminal blocks (standard model).
installation with click brackets (on the left-hand side, they are supplied by the builder)
smart guide
FK
203T
ON-OFF digital controller for ventilated re-
frigerating units
Version 1.02 of December the sixth, 2002
File fk203te_v1.02.pdf
PT
EVERY CONTROL S.r.l.
This Company belongs to
Via Mezzaterra 6, 32036 Sedico Belluno ITALY
Phone 0039-0437-852468 • Fax 0039-0437-83648
and screw brackets (on the right-hand side, by request); if you are using screw brackets,
you have to moderate the clamping torque, in order not to damage the box and screw
brackets.
1.2 Electrical connection
2 OPERATION
2.1 Preliminary information
During the normal operation the instrument shows the cabinet
temperature.
2.2 How to activate the defrost by hand
If you have to activate the defrost by hand:
• press for 4 s
Unless the evaporator temperature is below the defrost end tem-
perature you have set with the parameter d2, the defrost will
not be activated.
3 WORKING SETPOINT
3.1 How to set the working setpoint
If you have to modify the working setpoint value:
• press and or (3)
(3) you can set the working setpoint between the limits you have set with the param-
eters r1 and r2.
ENGLISH

6 ALARMS
6.1 Alarms
CODE
corrupted
memory
data
cabinet
probe
alarm
evapora-
tor probe
alarm
REASONS
there is the corruption
of the configuration
data of the memory of
the instrument
• the kind of cabinet
probe you have con-
nected is not right
• the cabinet probe
plays up
• the connection in-
strument-cabinet
probe is wrong
• the cabinet tempera-
ture is outside the
limits allowed by the
working range of
the instrument
• the kind of evapora-
tor probe you have
connected is not
right
• the evaporator
probe plays up
• the connection in-
strument-evaporator
probe is wrong
• the evaporator tem-
perature is outside
the limits allowed by
the working range
of the instrument
REMEDIES
switch off the power
supply of the instru-
ment: unless the alarm
disappears, you will
have to change the
instrument
• look at the param-
eter /0
• test the integrity of
the probe
• test the instrument-
probe connection
• test the temperature
close to the probe (it
has to be between
the limits allowed by
the working range)
• look at the param-
eter /0
• test the integrity of
the probe
• test the instrument-
probe connection
• test the temperature
close to the probe (it
has to be between
the limits allowed by
the working range)
EFFECTS
• you can not gain
access the setting
procedures
• all outputs will be
forced OFF
• the compressor will
work in accordance
with the parameters
C5 and C6
• if the defrost is run-
ning, it will immedi-
ately end
• the defrost will
never be activated
• if the parameter F7
has value 3 or 4, the
evaporator fan will
work in accordance
with the compres-
sor, except what
you have set with
the parameters F4
and F5
• the defrost will end
by time (parameter
d3)
4 CONFIGURATION PARAMETERS
4.1 How to set the configuration parameters
Configuration parameters are arranged on two levels.
If you have to gain access the first level:
• press and for 4 s : the instrument
will show
If you have to select a parameter:
• press or
If you have to modify the value of the parameter:
• press and or
If you have to gain access the second level:
• gain access the first level
• press or for selecting
• press and or for setting “ -19 “
• press and for 4 s : the instrument
will show
If you have to quit the procedure:
• press and for 4 s or do not op-
erate for about 60 s.
5 SIGNALS
5.1 Signals
LED MEANING
Compressor LED
if it is lighted, the compressor will be ON
if it flashes, a compressor delay will be running (look at the parameters
C0, C1, C2 and C4)
Defrost LED
if it is lighted, the defrost output will be activated
if it flashes:
• a defrost delay will be running (look at the parameters C0, C1, C2 and
C4)
• the dripping will be running (look at the parameter d7)
• the freezing fluid heating will be running (look at the parameter dP)
Evaporator fan LED
if it is lighted, the evaporator fan will be ON
if it flashes, the after dripping evaporator fan delay will be running (look
at the parameter F5)

Every Control S.r.l. • FK 203T • Sheet 2/2
The instrument shows the indications above flashing.
7 TECHNICAL DATA
7.1 Technical data
Box: self-extinguishing grey.
Size: 75 x 33.5 x 81 mm (2.95 x 1.31 x 3.18 in) the model with extractable terminal
blocks (standard model), 75 x 33.5 x 62 mm (2.95 x 1.31 x 2.44 in) the model with
screw terminal blocks (by request).
Installation: panel mounting, panel cut out 71 x 29 mm (2.79 x 1.14 in), with click
brackets (they are supplied by the builder) or screw brackets (by request).
Frontal protection: IP 65.
Connections: extractable terminal blocks with pitch 5 mm (0.19 in, standard model)
for cables up to 2.5 mm² (0.38 sq in, power supply, inputs and outputs) or screw termi-
nal blocks with pitch 5 mm (0.19 in, by request) for cables up to 2.5 mm² (0.38 sq in,
power supply, inputs and outputs), 5 poles single line male connector with pitch
2.5 mm (0.09 in, serial port).
Ambient temperature: from 0 to 55 °C (32 to 131 °F, 10 ... 90% of relative humidity
without condensate).
Power supply: 230 Vac, 50/60 Hz, 1.5 VA (standard model) or 115 Vac, 50/60 Hz,
1.5 VA (by request).
Measure inputs: 2 (cabinet and evaporator probe) for PTC or NTC probes.
Working range: from -50 to 99 °C (-58 to 210 °F) for PTC probe, from -40 to 99 °C
(-40 to 210 °F) for NTC probe.
Setpoint range: from -55 to 99 °C (-55 to 99 °F).
Resolution: 1 °F with unit of measure in Fahrenheit, 1 °C with unit of measure in
Celsius.
Display: one red LED 3-digit display 13.2 mm (0.51 in) high, output status indicators.
Outputs: 3 relays: one 10 A @ 250 Vac relay for one ½ HP @ 230 Vac compressor
control (NO contact), one 8 A @ 250 Vac relay for evaporator fan control (NO contact)
and one 8 A @ 250 Vac relay for defrost system control (change-over contact).
Kind of defrost: electric and hot gas defrost.
Defrost control: defrost interval, defrost end temperature and defrost maximum length
(automatic and by hand).
cabinet
tem-
perature
lower or
upper
tempera-
ture alarm
the cabinet tempera-
ture is outside the limit
you have set with the
parameter A1 or A2
test the temperature
close to the probe
(look at the parameters
A0, A1 and A2)
no effects Serial port: TTL with EVCOBUS communication protocol (for the configurer/cloner
system CLONE and supervision system RICS).
F6 0 1 --- 0 kind of evaporator fan stop temperature (it is important if /A = 1 and F7 = 3 or 4;
0 = absolute evaporator fan stop temperature, 1 = evaporator fan stop temperature relative
to the cabinet temperature) (11)
F7 0 4 --- 4 evaporator fan action during the normal operation (0 = it will be forced OFF, 1 = it will be
forced ON, 2 = it will work in accordance with the compressor, 3 = it will work in accordance
with F1 and F2, 4 = if the compressor is ON, it will work in accordance with F1 and F2, if the
compressor is OFF, it will be forced OFF)
LABEL MIN. MAX. U.M. DEF. SERIAL NETWORK (EVCOBUS)
L1 1 15 --- 1 instrument address
L2 0 7 --- 6 instrument group
L4 0 3 --- 1 baud rate (0 = 1,200 baud, 1 = 2,400 baud, 2 = 4,800 baud, 3 = 9,600 baud)
(4) the unit of measure depends on the parameter /8
(5) once you have modified the value of the parameter, you will have to switch off the power supply of the instrument
(6) if the parameter has value 0, the defrost will end by time (parameter d3); if the parameter F7 has value 3 or 4, the evaporator fan will work in accordance with the compressor,
except what you have set with the parameters F4 and F5
(7) unless the evaporator temperature is below the defrost end temperature you have set with the parameter d2, the defrost will not be activated
(8) if at the moment of the defrost activation the cabinet temperature is below the value “working setpoint + r0” , the instrument will not show temperatures above that value; if
at the moment of the defrost activation the cabinet temperature is above the value “working setpoint + r0” , the instrument will not show the increases of the temperature (if
the increase takes place below the value “working setpoint + r0” , look at the previous case); the instrument restores the normal operation once the after dripping evaporator
fan delay ends and the cabinet temperature falls below the freeze temperature
(9) if at the moment of the defrost activation the compressor is ON since a time lower than the one you have set with the parameter, the compressor will be forced ON for a
time such as to finish the time you have set with the parameter
(10) if the temperature alarm does not disappear at the end of the time you have set with the parameter A3, it will further be excluded for the time you have set with the parameter
A6; if the temperature alarm takes place during the defrost and does not disappear at the end of the time you have set with the parameter A7, it will further be excluded for the
time you have set with the parameter A6
(11) the evaporator fan stop temperature is “cabinet temperature - F1” ; you always have to consider the parameter F1 with positive sign.

8 WORKING SETPOINT AND CONFIGURATION PARAMETERS
8.1 Working setpoint
LABEL MIN. MAX. U.M. DEF. WORKING SETPOINT
r1 r2 °C/°F (4) 0 working setpoint
8.2 First level parameters
LABEL MIN. MAX. U.M. DEF. PASSWORD
PA -55 99 --- 0 password
LABEL MIN. MAX. U.M. DEF. MEASURE INPUTS
/1 -55 99 °C/°F (4) 0 cabinet probe calibration (you have to set eight points for adjusting one degree)
/6 -55 99 °C/°F (4) 0 evaporator probe calibration (it is important if /A = 1, you have to set eight points for adjust-
ing one degree)
LABEL MIN. MAX. U.M. DEF. REGULATOR
r0 1 15 °C/°F (4) 2 hysteresis (differential, it is relative to the working setpoint)
LABEL MIN. MAX. U.M. DEF. DEFROST
dA --- --- °C/°F (4) --- evaporator temperature showing
8.3 Second level parameters
LABEL MIN. MAX. U.M. DEF. MEASURE INPUTS
/0 1 4 --- 1 kind of probe (1 = PTC, 2 = reserved, 3 = NTC, 4 = reserved)
/1 -55 99 °C/°F (4) 0 cabinet probe calibration (you have to set eight points for adjusting one degree)
/6 -55 99 °C/°F (4) 0 evaporator probe calibration (it is important if /A = 1, you have to set eight points for adjust-
ing one degree)
/8 0 1 --- 1 temperature unit of measure (0 = Fahrenheit degree, 1 = Celsius degree)
/A 0 1 --- 1 evaporator probe presence (and its functions; 1 = YES) (5) (6)
LABEL MIN. MAX. U.M. DEF. REGULATOR
r0 1 15 °C/°F (4) 2 hysteresis (differential, it is relative to the working setpoint)
r1 -55 r2 °C/°F (4) -50 minimum value you can assign to the working setpoint
r2 r1 99 °C/°F (4) 50 maximum value you can assign to the working setpoint
LABEL MIN. MAX. U.M. DEF. COMPRESSOR PROTECTION
C0 0 240 min 0 minimum delay between you turn the instrument ON and the first compressor activation
C1 0 240 min 5 minimum delay between two compressor activation in succession
C2 0 240 min 3 minimum delay between the compressor gets OFF and the following activation
C4 0 1 --- 0 fixed delay since the compressor gets ON and OFF (1 = YES, for 3 s)
C5 1 240 min 10 cycle time for the compressor activation during the cabinet probe alarm
C6 0 100 % 50 percentage of C5 the compressor is ON during the cabinet probe failure
LABEL MIN. MAX. U.M. DEF. DEFROST
d0 0 99 h 8 defrost interval (7) (0 = the defrost will never automatically be activated)
d1 0 1 --- 0 kind of defrost (0 = electric defrost, 1 = hot gas defrost)
d2 -55 99 °C/°F (4) 2 defrost end temperature (evaporator temperature, it is important if /A = 1)
d3 0 240 min 30 defrost maximum length (0 = the defrost will never be activated)
d4 0 1 --- 0 defrost activation every time you turn the instrument ON (1 = YES) (7)
d5 0 99 min 0 delay between you turn the instrument ON and the defrost activation (it is important if
d4 = 1)
d6 0 1 --- 1 freeze of the temperature showed by the instrument during the defrost (1 = YES) (8)
d7 0 15 min 2 dripping time
d9 0 1 --- 0 compressor protections cleaning at the moment of the defrost activation (it is important if
d1 = 1; 1 = YES)
dA --- --- °C/°F (4) --- evaporator temperature showing (it is important if /A = 1)
dP 0 99 min 0 minimum time the compressor must have been ON at the moment of the defrost activation
in order that the defrost can be activated (it is important if d1 = 1) (9)
LABEL MIN. MAX. U.M. DEF. ALARMS
A0 1 15 °C/°F (4) 2 hysteresis (differential, it is relative to A1 and A2, it is important if A1 and/or A2 ≠0)
A1 -55 0 °C/°F (4) -10 lower temperature alarm threshold (it is relative to the working setpoint, 0 = it will never be
activated)
A2 0 99 °C/°F (4) 10 upper temperature alarm threshold (it is relative to the working setpoint, 0 = it will never be
activated)
A3 0 240 min 120 temperature alarm exclusion time since you turn the instrument ON (it is important if A1
and/or A2 ≠0)
A6 0 240 min 5 temperature alarm exclusion time (it is important if A1 and/or A2 ≠0) (10)
A7 0 240 min 15 temperature alarm exclusion time since the end of the after dripping evaporator fan delay
(since the end of F5, it is important if A1 and/or A2 ≠0)
LABEL MIN. MAX. U.M. DEF. EVAPORATOR FAN
F1 -55 99 °C/°F (4) -1 evaporator fan stop temperature (evaporator temperature, it is important if /A = 1 and
F7 = 3 or 4); look at F6 as well
F2 1 15 °C/°F (4) 2 hysteresis (differential, it is relative to F1, it is important if /A = 1 and F7 = 3 or 4)
F4 0 2 --- 0 evaporator fan action during the defrost and dripping (0 = it will be forced OFF,
1 = it will be forced ON, 2 = it will work in accordance with F7)
F5 0 15 min 2 after dripping evaporator fan delay
Popular Controllers manuals by other brands

LAE electronic
LAE electronic CDC123T1R3G Instructions for installation and use

SAMES KREMLIN
SAMES KREMLIN LP 6 - 0.5/4 Translation from the original manual

Intersil
Intersil ISL6539 Application note

GE
GE EV100 LX instructions

Penn
Penn MR5 Series Product bulletin

Carbolite
Carbolite Gero 132 Installation, operation and maintenance instructions