HAI OmniLT Automation User manual

Installation Manual
Document Number 21I00-1 Rev A
October, 2000

Document Number 21I00-1 Rev A
October, 2000
Copyright v
vv
v2000 HAI
All Rights Reserved
www.homeauto.com

CONTENTS
INTRODUCTION.............................................. 5
INSTALLATION............................................... 5
CONTROLLER HOOKUP .............................................. 5
ABOUT SECURITY ZONES ........................................... 7
BURGLAR ZONE HOOKUPS................................... 7
ABOUT FIRE ZONES ...................................................... 9
TWO-WIRE SMOKE DETECTORS.......................... 9
FOUR-WIRE SMOKE DETECTORS ........................ 9
TELEPHONE CONNECTIONS.................................... 12
LCD CONSOLE HOOKUP............................................ 14
CONSOLE SETUP.......................................................... 14
CONSOLE ADDRESS.............................................. 14
SOUNDER ................................................................ 14
KEY CLICK .............................................................. 14
KEY BACKLIGHT ................................................... 14
VIEWING ADJUSTMENT....................................... 14
LANGUAGE ............................................................. 15
EXIT SETUP MODE ................................................ 15
CONSOLE SELF TEST.................................................. 15
BELL OUTPUT ............................................................... 17
CONTROLLER OUTPUTS ........................................... 18
GENERAL PURPOSE SWITCHING
APPLICATIONS ....................................................... 18
SOUNDER TRIGGERING ....................................... 18
COMMUNICATOR OUTPUTS ............................... 18
"ARMED" AND "OK TO ARM".............................. 18
SWITCHED OUTPUT .............................................. 18
HOME CONTROL MODULES .................................... 18
REMOTE ARM/DISARM SWITCH............................. 19
HAI THERMOSTATS .................................................... 20
PROGRAMMABLE ENERGY SAVER MODULES .. 21
OUTDOOR TEMPERATURE, TEMPERATURE
SENSORS ......................................................................... 22
BUILT-IN SERIAL INTERFACE................................. 24
SYSTEM POWER UP PROCEDURE .......... 25
CONSOLE CHECK OUT............................................... 25
TELEPHONE CHECK OUT ......................................... 25
BURGLAR ZONE CHECK OUT.................................. 26
FIRE ZONE CHECK OUT ............................................ 26
HOME CONTROL CHECKOUT ................................. 26
CUSTOMER CHECKOUT ............................................ 26
IN CASE OF TROUBLE ................................................ 27
CONSOLES............................................................... 27
CONTROLLER......................................................... 27
X-10 TROUBLESHOOTING TIPS ............................... 28
DIGITAL COMMUNICATOR...................... 29
DESCRIPTION OF CONTACT ID............................... 29
DESCRIPTION OF 4/2 FORMAT ................................ 29
3/1 FORMAT ................................................................... 30
OPENING AND CLOSING REPORTS ........................ 30
INSTALLER SETUP....................................... 31
SETUP CONTROL..........................................................31
X-10 HOUSE CODE ................................................. 31
X-10 3-PHASE ..........................................................31
OUTPUT TYPES.......................................................31
SETUP ZONES ................................................................32
WIRELESS RECEIVER............................................32
ZONE RESISTORS...................................................32
ZONE RESPONSE TIME .........................................33
ZONE TYPES............................................................ 33
LATCHING ZONE TYPES ......................................33
DESCRIPTION OF ZONE TYPES...........................33
SETUP DIGITAL COMMUNICATOR ........................36
FIRST PHONE NUMBER, FIRST ACCOUNT
NUMBER ..................................................................36
SECOND PHONE NUMBER, SECOND ACCOUNT
NUMBER ..................................................................36
COMMUNICATOR TYPE ....................................... 37
TWO-WAY AUDIO..................................................37
REPORT OPEN/CLOSE ...........................................37
AUTOMATIC TEST TIME ......................................37
ALARM CODES (4/2 and 3/1 Formats)....................37
SETUP TEMPERATURES.............................................38
TEMPERATURE DISPLAY.....................................38
THERMOSTAT TYPE..............................................38
SETUP MISCELLANEOUS...........................................39
INSTALLER CODE ..................................................39
ENABLE PC ACCESS .............................................. 39
PC ACCESS CODE...................................................39
CALL BACK PHONE NUMBER.............................39
OUTSIDE SIREN DELAY........................................39
DIAL OUT DELAY ..................................................40
ALARM RESET TIME .............................................40
ARMING CONFIRMATION.................................... 40
FIRE ALARM VERIFICATION............................... 40
SUPERVISE BELL ...................................................41
ENABLE EMERGENCY KEYS............................... 41
TIME DISPLAY ........................................................41
DATE DISPLAY .......................................................41
AC POWER FREQUENCY ...................................... 41
DEAD LINE DETECT ..............................................41
OFF HOOK DETECT ...............................................41
PICKUP AFTER HANGUP ......................................41
CLOCK ADJUSTMENT ...........................................42
MODEL AND SOFTWARE VERSION ...................42
RESET SYSTEM EEPROM...................................... 42
RESET SYSTEM RAM.............................................42
SETUP EXPANSION ......................................................42
MODULE 1 TYPE.....................................................42
MODULE 2 TYPE - MODULE 4 TYPE ..................43
SERIAL 1 RATE ....................................................... 43
SERIAL 2 RATE ....................................................... 43
OMNILT SPECIFICATIONS........................ 44
UNDERWRITER'S LABORATORIES (UL)
INSTALLATION REQUIREMENTS........... 45

SMOKE DETECTOR INSTALLATION
GUIDELINES .................................................. 46
APPENDIX A – CONTACT ID REPORTING
FORMAT.......................................................... 47
FIGURES
FIGURE 1 – CONTROLLER HOOKUP .......................................................................................................................................6
FIGURE 2 - OVERALL CONNECTIONS DIAGRAM................................................................................................................8
FIGURE 3 – TWO-WIRE FIRE ZONE CONNECTIONS.........................................................................................................10
FIGURE 4 – FOUR-WIRE FIRE ZONE CONNECTIONS .......................................................................................................11
FIGURE 5 - RJ31X JACK CONNECTIONS...............................................................................................................................13
FIGURE 6 - CONSOLE CONNECTIONS...................................................................................................................................16
FIGURE 7 - BELL CONNECTIONS ...........................................................................................................................................17
FIGURE 8 - REMOTE KEYSWITCH CONNECTIONS ..........................................................................................................19
FIGURE 9 - HAI THERMOSTAT CONNECTIONS .................................................................................................................20
FIGURE 10 - PESM CONNECTIONS.........................................................................................................................................23
FIGURE 11 - RS-232 CONNECTIONS........................................................................................................................................24
FIGURE 12 - RS-485 CONNECTIONS........................................................................................................................................24

Page 5
INTRODUCTION
This installation guide is intended as an aid to installing the OmniLT automation system. The installer should also have
thoroughly reviewed and understood the OmniLT Owner's Manual, which has important information regarding final setup of the
system. This manual assumes that the installer has a basic understanding of installing a security system.
This guide applies to the Model 21A00 OmniLT controller. Refer to the Underwriters Laboratories Installation Requirements
section for details in the application of each. Failure to install the OmniLT and its accessories in accordance with the UL
Requirements in this manual and in the Owner's Manual, is a violation of the Listing Mark.
INSTALLATION
Go over your plan with your customer.
1. Install the entire system. Refer to sections in this manual to see how to install various components.
2. Follow the Power-Up and Checkout procedures.
3. Explain the basics to the customer. Deliver all manuals and documentation.
4. Follow up with your customer to keep them satisfied.
CONTROLLER HOOKUP
1. When choosing a place to mount the controller, consider the following:
a. A duplex outlet, preferably on its own circuit, is required to be within 5 feet of the controller for the power transformer and
the X-10 Interface Module (if used).
b. The controller should be protected from weather, temperature extremes, and burglars.
2. GROUND THE CONTROLLER "GND" TERMINAL TO A COLD WATER PIPE OR TO A 4-FOOT GROUND ROD TO
PRESERVE ITS BUILT-IN TRANSIENT PROTECTION. USE 14 GAUGE WIRE. TRANSIENT PROTECTION WILL
NOT WORK IF THE CONTROLLER IS NOT PROPERLY GROUNDED.
3. Connect the 16.5 VAC power transformer to the 16 VAC INPUT terminals.
4. Connect the BLACK battery wire to the minus (-) terminal on the battery. DO NOT connect the red wire at this time. DO
NOT reverse the connections; the battery fuse will blow. Note that the unit will NOT START on the battery alone.
5. If used, plug the X-10 Interface Module into the X-10 modular connector to the right of the PHONE connections. Use the
supplied 4-conductor modular cable to connect the module to the jack on the processor board. The red LED on the interface
module should be on and will blink off when the interface receives a signal from the controller.
6. Refer to FIGURE 1 (CONTROLLER HOOKUP) for this configuration.

Page 6
RED WIRE TO +
BLACK WIRE TO -
TWO - WAY
POWER LINE INTERFACE
4 CONDUCTOR
BATTERY
12V 7AH
COLD WATER PIPE
OR GROUND ROD
GOUNDING METHOD MUST BE IN
ACCORDANCE WITH THE NATIONAL
ELECTRIC CODE, ANSI/NFPA 70.
14 GA. WIRE
POWER TRANSFORMER
16.5 VAC 40 VA
REVERE
P/N RT-1640SL
OR EQUIVALENT
YUASA NP7-12
OR EQUIVALENT
1/4"
SPACING
THE BATTERY IS NON-POWER
LIMITED. THE BATTERY LEADS
MUST BE SEPERATED FROM
ALL OTHER POWER LIMITED
WIRING IN THE ENCLOSURE
BY AT LEAST 1/4".
FIGURE 1 – CONTROLLER HOOKUP

Page 7
ABOUT SECURITY ZONES
Zones 1-8 on the controller and zones 9-24 on the expander may be configured as security zones, fire zones, temperature zones, or
auxiliary inputs. Zones 7 and 8 on the controller and zones 9-16 may also be configured as a PESM. Zone 8 is the only input that
can be configured as a UL Supervised Fire Zone (required for UL installations). Any other zone may be configured as Fire Zone,
however, it is not recognized by UL as a Supervised Fire Zone.
An external 1000-ohm end-of-line zone resistor is required for all zones unless the Setup item ZONE RESISTERS is set to "No".
If the Setup item ZONE RESISTORS is disabled, all zones other than Supervised Fire and Gas will not use an end-of-line
resistor. In this configuration, all zones switches (other than Supervised Fire and Gas) must be normally closed (open for alarm).
If any zone requires a normally open (closed for alarm) switch (other than Supervised Fire and Gas), the Setup item ZONE
RESISTORS must be set to "Yes" and all zones will require and external 1000-ohm end-of-line resistor.
The zone type for each zone is selected through the OmniLT SETUP menu on the console or by using the PC ACCESS software.
The system supports a maximum zone resistance, excluding the end-of-line resistor, of 150 ohms. The default setting for ZONE
RESISTORS is "Yes". The default settings for all zone inputs on an OmniLT controller are configured as Auxiliary inputs.
BURGLAR ZONE HOOKUPS
The OmniLT system supports both normally open and normally closed switches. Most contacts designed for doors, windows,
motion detectors, glassbreak detectors and other security devices meet this requirement. An external 1000-ohm end-of-line
resistor must be used for all zones if ZONE RESISTORS is set to "Yes".
When ZONE RESISTORS are set to "No", only normally closed switches can be used.
1. When using a normally open switch, a 1000-ohm end-of-line resistor must be in parallel with the zone being used. Maximum
loop resistance excluding end-of-line resistor should not exceed 150 ohms. ZONE RESISTORS must be set to "Yes".
2. When using a normally closed switch, a 1000-ohm end-of-line resistor must be put in series with the zone being used if
ZONE RESISTORS are set to "Yes". If ZONE RESISTORS are set to "No", the 1000-ohm end-of-line resistor is not used.
Maximum loop resistance excluding end-of-line resistor should not exceed 150 ohms.
3. Power motion detectors from AUX 12V.
4. Unused zones may be left open, and should be left at the default setting of AUXILIARY zone types.
5. When Zone 8 is configured to anything other than a Supervised Fire or Gas zone, the Zone 8 Jumper (J9) should be set to the
NRM (normal) position.
6. See FIGURE 2 (OVERALL CONNECTIONS DIAGRAM) for configurations of burglary zones.

Page 8
EARTH
GROUND
TRANSFORMER
16.5VAC 40VA
AUXILIARY
12VDC
SOUNDER
CONSOLE(S) ZONE
INPUT INPUT
ZONE REMOTE
CONTROL
THERMOSTAT(S)
OUTPUT
OUTPUT
CONNECT CABLE
TO CONTROLLER,
PLUG MODULAR
END INTO
RJ31X JACK
INPUT
ZONE
INPUT
ZONE
INPUT
ZONE
INPUT
ZONE
INPUT
ZONE
INPUT
ZONE
OUT2
BURGLARY
ZONE
ZONE
(NC)
1K EOL
ZONE
UNIT AND DISCONNECT
Z8
BEFORE SERVICING.
TELEPHONE LINES
4-WIRE FIRE ZONE
EOL
COM
OUT2
SWITCH 12V
WARNING
DE-ENERGIZE THIS
FROM ELECTRIC SHOCK,
TO PREVENT RISK
(NO)
SMOKE
ZN
12V
4-WIRE ZN
1K
12V
SMK
NRMJ9
2-WIRE FIRE ZONE
Z8
ZONE
ZN
SMOKE
2-WIRE
12V
NRM
SMK
J9
AUXILIARY 12V, CONSOLE, AND OUTPUTS ARE INCLUDED IN THE TOTAL DEVICE LOAD, WHICH CANNOT EXCEED 0.5 AMP.
SOUNDERS CANNOT EXCEED 1 AMP. IN UL INSTALLATIONS, SOUNDERS CANNOT EXCEED 350mA.
NOTES:
3.
2.
(OUTPUT)
EOL
1K
(OUTPUT)
SWITCH 12V
ALL CIRCUITS EXCEPT FOR THE BATTERY ARE POWER-LIMITED (CLASS II)
IN UL INSTALLATIONS, THE TOTAL DEVICE LOAD CANNOT EXCEED 200mA.
1.
FIGURE 2 - OVERALL CONNECTIONS DIAGRAM

Page 9
ABOUT FIRE ZONES
The OmniLT system supports normally open (closed for alarm), two-wire or four-wire smoke detectors. Two-wire smoke
detectors can only be connected to Zone 8. Four-wire smoke detectors can be connected to any zone (1-8). An external 1000-
ohm end-of-line resistor must be used for all fire (and gas) zones. When Zone 8 is used as a Supervised Fire (two-wire or four-
wire) or Gas zone, the Zone 8 Jumper (J9) must be in the "SMK" (smoke) position.
1. Smoke detectors must be powered from an Output configured as a SWITCHED POWER OUTPUT.
2. End of line resistor: 1000 ohms. Maximum loop resistance EXCLUDING end of line resistor is a 150 ohms. Use HAI
Model 1503A0011 End of Line Resistor Assembly in UL Listed Installations.
3. Smoke detectors are reset when the security system is armed.
TWO-WIRE SMOKE DETECTORS
OmniLT supports two-wire smoke detectors connected to Zone 8.
1. Use normally open (closed for alarm) two-wire "SYSTEM" type smoke detectors (System Sensor 2100TS or equivalent),
rated 8 - 14 VDC.
2. Smoke detectors must be connected to Zone 8 and configured as a Supervised Fire Zone.
3. An external 1000-ohm end-of-line resistor must be used.
4. Connect to the SWITCHED POWER OUTPUT as shown.
5. The Zone 8 Jumper (J9) must be in the SMK (smoke) position.
4. Refer to FIGURE 3 (TWO-WIRE FIRE ZONE CONNECTIONS) for this configuration.
FOUR-WIRE SMOKE DETECTORS
OmniLT supports four-wire smoke detectors connected to any zone (1-8).
1. Use normally open (closed for alarm) four-wire "SYSTEM" type smoke detectors (System Sensor 2112/24TR or equivalent),
rated 8 - 14 VDC.
2. An End of Line Power Supervision Relay Module (System Sensor A77-716B or equivalent) is required for UL installations.
Install 1000-ohm end-of-line resistor as shown.
3. Power the smoke detector from the SWITCHED POWER OUTPUT as shown.
4. When connected to Zone 8, the Jumper (J9) must be in the SMK (smoke) position.
5. Refer to FIGURE 4 (FOUR-WIRE FIRE ZONE CONNECTIONS) for this configuration.

Page 10
PLATE
ZONE
ZONE
PLATE
ZONE
ZONE
BOTTOM
BOTTOM
SYSTEM SENSOR
MODEL 2100TS
MODEL 2100TS
SYSTEM SENSOR
WHEN Z8 USED
FOR SMOKE, J9
MUST BE IN
THIS POSITION
BE CONFIGURED AS
A SWITCHED OUTPUT
THIS OUTPUT MUST
1K OHM EOL RESISTOR
HAI MODEL 1503A0011
FIGURE 3 – TWO-WIRE FIRE ZONE CONNECTIONS

Page 11
PLATE
ZONE
ZONE
+12V
GND
PLATE
ZONE
GND
+12V
ZONE
BOTTOM
BOTTOM
MODEL A77-716B
EOL POWER
SUPERVISION
RELAY
ZONE POWER
VIOLET
VIOLET
RED
BLACK
YELLOW
BLACK
GREEN
RED
HAI MODEL 1503A0011
1K OHM EOL RESISTOR
BLACK
GREEN
RED
WHEN Z8 USED
FOR SMOKE, J9
MUST BE IN
THIS POSITION
SYSTEM SENSOR
MODEL 2112/24TR
SYSTEM SENSOR
MODEL 2112/24TR
THIS OUTPUT MUST
A SWITCHED OUTPUT
BE CONFIGURED AS
SYSTEM SENSOR
YELLOW
GREEN
RED
BLACK
YELLOW
YELLOW
GREEN
RED
BLACK
FIGURE 4 – FOUR-WIRE FIRE ZONE CONNECTIONS

Page 12
TELEPHONE CONNECTIONS
1. If an RJ31X jack has been supplied by the telephone company, it is probably wired correctly and the controller can be
connected by plugging the supplied 8 conductor telephone cable into the RJ31X jack. The other end of the cable is spaded
(remove the spade connectors from the wires used). The green, red, brown, and gray wires must be connected to the
controller at the designated terminals under the section of the board marked 'PHONE'.
2. If required, install the supplied RJ31X jack as shown in the following diagram. The polarity must be correct for proper
operation of the phone access feature.
3. IT IS IMPERATIVE THAT THE PHONE LINE COMING INTO THE HOUSE BE CONNECTED TO A GROUNDED
SURGE ARRESTOR OUTSIDE THE PREMISES. IT IS THE RESPONSIBILITY OF THE TELEPHONE COMPANY
TO PROVIDE THIS SURGE ARRESTOR.
4. INSPECT THE INCOMING PHONE LINES. THE FIRST THING THAT THEY SHOULD GO TO IS A SMALL BOX
ON THE OUTSIDE OF THE PREMISES. THERE SHOULD BE A HEAVY GROUND WIRE COMING FROM THIS
BOX GOING TO A COLD WATER PIPE OR A SEPARATE GROUNDING ROD.
5. IF THERE IS NO SURGE ARRESTOR OR IF THE GROUND WIRE IS MISSING, HAVE THE CUSTOMER INSIST
THAT THE TELEPHONE COMPANY INSTALL ONE FOR THE SAFETY OF THE CUSTOMER.
6. WHEN WIRING A RJ31X JACK, MAKE SURE THAT THE INCOMING PHONE LINES GO TO THE TELEPHONE
COMPANY SURGE ARRESTOR BEFORE THEY GO TO THE RJ31X JACK.
7. When the RJ31X is installed as shown, locate the green, red, brown, and gray wires from the 8 conductor phone cable and
connect to the section on the OmniLT controller marked 'PHONE'. Plug the modular end of the cable into the RJ31X jack. If
necessary, bend the tab up on the plug to ensure a tight fit that will not fall out.
8. Verify the following if you have trouble during check out: With the system running, the RJ31X jack properly connected and
all phones on-hook (hung up), the PHONE LED, located on the left side of the controller, should be OFF. If it is on, reverse
the RED and GREEN wires to both the house phones and the telephone company wires at the RJ31X jack. When the
receiver is picked up on any phone, the PHONE LED will come on. When the phone line rings, the PHONE LED will light.
9. If the OmniLT is accessed on an in house telephone, the OmniLT will disconnect the phones from the phone company lines
and supply its own talk voltage to the phones. The PHONE LED will be on in this case.
10. Refer to FIGURE 5 (RJ31X JACK CONNECTIONS) for this configuration.

Page 13
GREEN
RED
BROWN
GRAY
BEND TAB UP IF
NECESSARY TO
ENSURE TIGHT FIT
GREEN(+) RED(-)
RED(-)
GREEN(+)
RJ11
HOUSE
PHONE
JACK(S)
TO ALL HOUSE
TELEPHONES,
KSU, AND
COMPUTERS
TO TELCO
INTERFACE AT
SURGE ARRESTOR
SURGE ARRESTOR
MUST BE GROUNDED!
TELEPHONE
NETWORK
INTERFACE
SURGE ARRESTOR
CUSTOMER
ACCESS
FIGURE 5 - RJ31X JACK CONNECTIONS

Page 14
LCD CONSOLE HOOKUP
1. 4 LCD Consoles (Models 11A00-1, 11A00-2, 11A00-9, and 15A00) MAXIMUM per system, subject to power availability.
2. Use 4-conductor 22-gage wire, 1000 feet maximum length. Consoles can be homerun or daisy chained. This length shall be
divided by the total number of consoles at the end of the run. For example, for 4 consoles, the maximum length reduces to
250 feet. All LCD Consoles are connected to the same 4 wires, RED (+12), BLK (Ground), YEL (A), GRN (B).
3. The console should be mounted so that the LCD display is at or slightly above eye level. Consoles should be kept out of the
reach of young children. A good height is approximately 58 inches from the floor to the bottom of the console enclosure.
4. Remove console face from back plate (slots on bottom of console will release back plate, use a screwdriver). Mount the back
plate to the wall. Mounting holes are designed to fit on a single or double gang box, or directly to the wall. Pull the wires
from the wall through the opening in the back plate. Splice the wires to the supplied cable. Connect the cable to the
connector on the console board (J1). Snap the console face on to the back plate. Remove protective film from the LCD lens.
5. Refer to FIGURE 6 (CONSOLE CONNECTIONS) for this configuration.
CONSOLE SETUP
The console has different operating options that can be setup from the console to the user's preference. If more than one console
is being used, it is required that you give each console a different address. You can change the address of a console through the
console setup mode.
To enter the console setup mode, simultaneously press and hold the 4 and up arrow (!) for approximately 1 second. The console
will beep 5 times and enter the setup mode. The top line of the display will indicate what you are doing, followed by the current
setting. The bottom line will show a menu of your options. To the lower right corner of the display is the direction arrow(s).
Where possible, the up (↑), down (↓), and two-headed (↕) arrow characters are shown on the console display to indicate which
arrow keys may be pressed at that time. Press the down arrow (") key to advance to the next item. Press the up arrow (!) key to
go back to the previous item.
CONSOLE ADDRESS
If you are installing more than one console, each console must be set to a different address. The default address setting is (1) -
this is adequate if only one console is being used. The choices at the bottom are 1-16; however, the OmniLT only supports 4
consoles. When making your choice, choose an address between 1-4, then press the # (pound) key.
SOUNDER
If you wish not to hear the beeper in the console for any reason, the sounder option can be turned off. Select (0) for OFF or (1)
for ON, then press the # key.
KEY CLICK
The sounder makes a click every time a key is pressed. This option may also be turned off. Select (0) for OFF or (1) for ON,
then press the # key.
KEY BACKLIGHT
The keys on the console keypad are lit. The keys can be never lit, always lit, or only lit when the LCD display is lit. Select (0)
OFF, (1) for ON, or (2) TIMED, then press the # key.
VIEWING ADJUSTMENT
This option is an adjustment for the viewing angle of the LCD display. This has been set to its best value at the factory, however,
you may wish to tweak it. The display has 20 levels of adjustment. Select (1) for a lower viewing angle, or (2) for a higher
viewing angle.

Page 15
LANGUAGE
This option is to display the 'console setup' text on the LCD display in English, French, Italian, or Spanish. Select one of the
languages, then press the # key.
EXIT SETUP MODE
To exit Setup Mode, press and hold the 4 and up arrow (!) keys simultaneously for about 1 second. The console will return to
normal operation. You may need to press (*) to restore the display.
CONSOLE SELF TEST
Use the self test mode to verify the proper operation of the console.
1. Disconnect the console from the controller. Connect the RED (+12) and BLACK (Ground) wires to a 12-volt source (or a
fresh 9-volt transistor battery). The console beeper will beep twice per second, the LCD backlight and the keypad key will be
lit, and the LCD will display "NO CONTROLLER DATA".
2. Simultaneously press and hold the 7 and the down arrow (") keys for approximately 3 seconds. The beeper will beep 5
times, the LCD backlight and keypad backlight will turn off, and the display will clear. The LED at the top right corner of
the console will start to cycle through its different colors (red, green, yellow, then turns off). At the end of each cycle the
beeper will beep once.
3. Press any key. The LCD backlight and the keypad key backlight will turn on.
4. Press the keys in the following order and verify that the appropriate character fills the screen. 0 - 9, *, #, AWAY (A),
NIGHT (B), DAY (C), OFF (D), !(filled blocks), and "(blanks).
5. If this is successful, the console is good. Simultaneously press and hold the 7 and down arrow (") keys to exit the self test
mode or disconnect power.

Page 16
SUPPLIED CABLE
(PLUGS INTO J1)
CONNECT ENDS OF SUPPLIED
CABLE TO CORRESPONDING
ENDS OF 4-WIRE CABLE
COMING FROM CONTROLLER
BOTTOM PLATE
CONSOLE FACE
(SNAPS ON TO BOTTOM PLATE)
CONSOLE PC BOARD
(MOUNTED TO CONSOLE FACE)
RED
BLACK
YELLOW
GREEN
FOR MODEL NUMBERS
SEE NOTE 1 UNDER
"LCD CONSOLE HOOKUP"
FIGURE 6 - CONSOLE CONNECTIONS

Page 17
BELL OUTPUT
The Bell Output provides 12VDC to power bells, piezo sirens, self-contained sirens, and siren drivers (do not connect speakers to
the Bell Output). Sounders can draw up to 1 amp MAXIMUM - (See Specifications for UL Ratings).
1. Locate interior sounders in a central location. The sounder is very loud. Do not install it in a room where small children or
animals could be trapped if the alarm is activated. Note that the Bell Output defaults to an Interior Sounder Output Type.
2. The Bell Output monitors the wiring to bells and sirens. It will report trouble if an open, short, or other wiring problem is
detected in the supervised bell circuit. It will also make a digital dial out when violated.
3. For UL Listed residential fire alarm applications, the UL Listed Wheelock Model MT-12/24-R Multitone Signal or
equivalent must be used, and the "SUPERVISE BELL" feature must be set to "ON".
4. Refer to FIGURE 7 (BELL CONNECTION) for connections.
RED
BLACK
FIGURE 7 - BELL CONNECTIONS

Page 18
CONTROLLER OUTPUTS
The OmniLT provides 2 programmable hardwired voltage outputs on the controller and 8 voltage outputs on the Expansion
Module. These outputs are programmable for the following output types:
•General Purpose low voltage switching applications (12 VDC)
•Sounder triggering (interior and exterior sounders and voice drivers for BURG and FIRE)
•Communicator outputs (radio, cellular, or any other type of auxiliary communicator)
•'ARMED' and 'OK TO ARM' outputs
•Switched Output (to power smoke detectors and cycle power to latching devices)
Outputs 1 and 2 can supply a maximum of 100 mA total.
GENERAL PURPOSE SWITCHING APPLICATIONS
This output will supply 12 VDC to the output terminal when its corresponding unit is ON.
SOUNDER TRIGGERING
This output can be used as a trigger for siren and voice drivers. When a driver requires a separate input for burglary and fire, you
can configure this output to give a voltage trigger to the driver.
COMMUNICATOR OUTPUTS
This output can be used for radio communications or any other type of auxiliary communications to augment the built-in digital
and voice dialers. Any communications device can be used with the OmniLT, provided that it is powered by 12 VDC, has 12
VDC triggered inputs, and has 2 (or more) channels.
The 'Communicator' outputs are activated 3 seconds before the OmniLT dialer begins to dial, either using its built-in digital dialer
or voice dialer.
The following events will activate the BURG output: Burglar alarms (including panic zones), Auxiliary emergencies, Police
emergencies, and Duress alarms. Fire alarms and the fire emergencies will activate the FIRE output.
"ARMED" AND "OK TO ARM"
ARMED: When the system is armed in any of the security modes (AWAY, NIGHT, or DAY), this output will be active. It is
typically used to activate a red LED to indicate that the system is 'armed'.
OK TO ARM: When all security zones are secure, no zones are bypassed, and the system is in the 'OFF' mode, this output will
be active. It is typically used to activate a green LED to indicate that the system is 'ok to arm'.
SWITCHED OUTPUT
This output is used to cycle power to latching devices when the system is armed. Use this output whenever smoke detectors are
connected to the system. This output will reset the smoke detectors when the system is armed after an alarm.
HOME CONTROL MODULES
If used, install X-10 or compatible modules EXACTLY as described in the instructions that come with each module. Watch the
load ratings and types of load allowed. The OmniLT is designed to send signals to any device compatible with the X-10 power
line carrier protocol

Page 19
REMOTE ARM/DISARM SWITCH
1. If desired, a remote keyswitch, keypad, or hidden arm/disarm toggle can be connected to the system. The device should have
a momentary close type switch.
2. Configure one of the zone inputs as a KEYSWITCH zone. A closure of the switch contacts will toggle the arming mode
between OFF and AWAY (Entry and Exit delays are still active).
3. Configure one of the outputs as an "ARMED" and another output as an "OK TO ARM" output. These outputs are used to
activate a red and a green LED based on the state of the alarm system. The "ARMED" and "OK TO ARM" outputs can
supply a maximum of 100 mA each. These outputs are included in the total DEVICES load, which cannot exceed 500 mA.
MOMENTARY CONTACT
KEYSWITCH
RED GREEN
-
++
GREEN
YELLOW
BLACK
RED
GREEN
YELLOW
BLACK
RED
FIGURE 8 - REMOTE KEYSWITCH CONNECTIONS

Page 20
HAI THERMOSTATS
OmniLT supports up to 2 HAI RC-Series Communicating Thermostats. The controller can send commands to the thermostat to
change mode, cool setting, heat setting, status of fan and hold, and other items.
Run a 3 (or 4) conductor wire from OmniLT to the thermostat location. All thermostats are connected to the GRN (Green), BLK
(Black), and YEL (Yellow) terminals in the section marked "TSTAT" on the OmniLT controller. Connect the red COMM cable
wire with the black COMM cable wire. Make the connections (as shown in Figure 9) using the supplied wire splices.
FIGURE 9 - HAI THERMOSTAT CONNECTIONS
Table of contents
Other HAI Controllers manuals
Popular Controllers manuals by other brands

Mitsubishi Electric
Mitsubishi Electric MELSEC Q Series user manual

Omega Engineering
Omega Engineering DRF-POT user guide

Fisher
Fisher 4194B Series instruction manual

Fly Wing
Fly Wing H1 user manual

NAVITAS
NAVITAS 440A Installation & service manual

Eaton
Eaton Ampgard 720A Instructions for installation, operation and maintenance

Raven
Raven AGCO RoGator Hawkeye C Series installation manual

Auber Instruments
Auber Instruments DSPR400 instruction manual

Unidrive
Unidrive ZoneLogix 301216 Installation and troubleshooting guide

DSEGenset
DSEGenset DSE8660 Operator's manual

Alpine
Alpine CRA-1655RF owner's manual

SEW-Eurodrive
SEW-Eurodrive MOVIPRO PHC2 Series operating instructions