DriSteem Vapor-logic 4 User manual

Vapor-logic®4
Humidifier Control System
Installation and
Operation Manual
Important: Read and save these instructions.
UPDATE
VL4-IOM-1008-UpdateEnglish.pdf 1 4/21/2010 1:31:14 PM

After a system prompt appears, type in ipconfig and then hit
Enter. The current IP address of the computer should appear.
If the first three segments of that IP address are different
than the first three segments of the humidifier’s default IP
(192.168.1.xxx), you must change either your computer or
Vapor-logic4’s IP address such that they match each other.
Field wiring:
Communication connections
3. Change the IP address of your humidifier or computer if
necessary.
a. Change the IP address of the humidifier to match your
computer.
The most straightforward way to change the IP address of the
humidifier using Vapor-logic4 is to use the keypad/display.
Go to Setup/Communications/Network IP address on the
keypad/display and change the IP address such that the first
three segments of the computer’s settings match the network
address. Make sure the last digit of the IP address is different
between the humidifier and the computer. Cycle power of
Vapor-logic4 board for address change to take effect.
b. Change the IP address of your computer to match the
humidifier.
Changing the IP address of the computer being used will
likely require administrative privileges for your company’s
network. Please consult your IT department for this task.
Figure 2-1:
Checking your IP address
1BHFt6QEBUFEUPSFQMBDF1BHFJOUIF%3*45&&.7BQPSMPHJD*OTUBMMBUJPOBOE0QFSBUJPO.BOVBM
VL4-IOM-1008-UpdateEnglish.pdf 2 4/21/2010 1:31:22 PM

Table 3-1:
Diagnostics menu
Menu item Minimum
value
Maximum
value Notes
Download data
Alarm history -- --
Download system data here. Select individual data sets or select “Download all” to download
all data sets.
RH history -- --
Temperature history -- --
RH and temp history -- --
Message history -- --
Water converted -- --
Energy used -- --
Download all data -- --
64#CBDLVQSFTUPSF
Back up settings No Yes
Humidifier settings can be backed up to or restored from a USB flash drive.
Restore settings No Yes
Humidifier info
Factory string -- -- Displays as-shipped configuration string
Current string -- -- Displays current configuration string
Serial number -- -- Displays humidifier serial number
Firmware version -- -- Displays current firmware version of Vapor-logic4 control board
Test outputs
Fill valve -- --
Cycles output to verify operation.
Drain valve -- --
Fan control -- --
Programmable triac -- --
Dry contact relay -- --
Note: Your system may not have all of these parameters. .PSFPOUIFOFYUQBHF
The Diagnostics screen
6QEBUFEUPSFQMBDF1BHFJOUIF%3*45&&.7BQPSMPHJD*OTUBMMBUJPOBOE0QFSBUJPO.BOVBMt1BHF
VL4-IOM-1008-UpdateEnglish.pdf 3 4/21/2010 1:31:22 PM

The Alarms screen
Table 4-1:
Alarms menu
"MBSNMBCFM Description Does alarm
BVUPDMFBS
Tank temp sensor failed Tank temp sensor has failed. No
RH signal out of range RH signal is out of range. Yes
Dew point sig. out of range Dew point signal is out of range. Yes
Demand signal Demand signal is out of range. Yes
Duct RH signal out of range Duct RH signal is out of range. Sensor my be faulty. Yes
Aux temp sens out of range Auxiliary temp sensor signal is out of range. Yes
Water probe miswired Water probe head is miswired or faulty. Yes
Faulty water probe Water probe readings are suspect, likely caused by scale on probe. No
Excess fill time Fill valve has been on too long during initial tank fill. Bottom probe is not in contact with water. Yes
Excess refill time Re-filling is taking too long. Top probe is not in contact with water. Yes
Tank not draining Drain valve has been open for the prescribed amount of time based on the humidifier model, and water is still
touching the low water probe. Yes
Tank overtemp Fault occurs at boiling temperature plus 25 °F (13 °C). All units are put into a keep-cool state where fill and drain
cycles operate to keep tank cool. Note: Resolve issue, then clear alarm, shut down humidifier, and restart. No
Excess water no demand
Humidifier continues to add water when there is no demand, signifying unit continues to make steam. All units
are put into a keep-cool state where fill and drain cycles operate to keep tank water from boiling.
Note: Resolve issue, then clear alarm, shut down humidifier, and restart.
No
No SDU airflow Airflow proving switch in the SDU (space distribution unit, a fan-based dispersion assembly) indicates no airflow.
No steam is produced while alarm is active. Yes
No power vent airflow Pressure switch indicates there is no airflow at the power venter. Yes
No combustion airflow Switch indicates the combustion air damper is closed. Yes
Blocked flue Flue pressure switch indicates positive pressure in flue. GTS will not ignite when this fault is active. Yes
Burner 1, 2, 3, or 4 fault Burner tried one or more times to light and did not succeed. Once this fault is active, Vapor-logic4 locks out the
burner and does not try to light it again until fault is cleared. Other burners can run. No
Ignition mod. 1, 2, 3, or 4 fault Ignition module has not opened the gas valve. Once this fault is active, Vapor-logic4 locks out the ignition module
and does not try to start it again until fault is cleared. Other ignition modules can run. No
Blower 1, 2, 3, or 4 fault Blower is turning at less than the specified minimum RPM. Unit not allowed to run. Yes
Gas valve 1, 2, 3, or 4 fault Gas valve is on when it should be off. Unit not allowed to run. Yes
Low water Low water probe is in contact with water and low water sensor is not in contact with water. Yes
Low input signal current Demand signal by others current is below minimum threshold. Yes
Notes:
t 4FFUIFUSPVCMFTIPPUJOHTFDUJPOJOUIJTNBOVBMGPSBMBSNQPTTJCMFDBVTFTBOESFDPNNFOEFEBDUJPOT
t 5IF"MBSNT-PHEJTQMBZTBMBSNOBNFEBUFBOEUJNFPGPDDVSSFODFQMVTw"DUJWFww$MFBSFEwPSw"VUPDMFBSFEw
t "DUJWFBMBSNTEJTQMBZGJSTUJOUIF"MBSNT-PHGPMMPXFECZDMFBSFEBMBSNTBVUPDMFBSFEBOEPSNBOVBMMZDMFBSFEMJTUFEJOPSEFSPGPDDVSSFODF
t 5IF"MBSNT-PHEJTQMBZTNBYJNVNBMBSNT$MFBSFEBMBSNTMFBWFUIFMPHGJSTU
t *GBOBMBSNFWFOUPDDVSTBOEJTOPUNBOVBMMZPSBVUPDMFBSFEEVSJOHVOJUPQFSBUJPOUIFBMBSNXJMMTUBZUIFSFVOUJMUIFSFJTEFNBOEBOEUIFVOJUJTSVOOJOH
1BHFt6QEBUFEUPSFQMBDF1BHFJOUIF%3*45&&.7BQPSMPHJD*OTUBMMBUJPOBOE0QFSBUJPO.BOVBM
VL4-IOM-1008-UpdateEnglish.pdf 4 4/21/2010 1:31:22 PM

6QEBUFEUPSFQMBDF1BHFJOUIF%3*45&&.7BQPSMPHJD*OTUBMMBUJPOBOE0QFSBUJPO.BOVBMt1BHF
Security, downloading data, and
data backup and restore
4FDVSJUZQBTTXPSE
To control who can change Vapor-logic4 settings, enable the
security function and define a password in the Setup menu. Enter
four digits, numbers only, and define the time-out period (minutes
of inactivity before Vapor-logic4 reverts to read-only mode). The
Web interface and the keypad/display can have separate passwords.
Important: Write down this password and keep in a secure
location.
%PXOMPBEJOHIJTUPSJDBMEBUB
Vapor-logic4 retains the following data sets:
t 3)IJTUPSZTFWFOSPMMJOHEBZTPGEBUBBDRVJSFEBUPOFNJOVUF
intervals)
t 5FNQFSBUVSFIJTUPSZTFWFOSPMMJOHEBZTPGEBUBBDRVJSFEBUPOF
minute intervals)
t 3)BOEUFNQFSBUVSFIJTUPSZTFWFOSPMMJOHEBZTPGEBUBBDRVJSFE
at one-minute intervals)
t 8BUFSDPOWFSUFEQPVOETLJMPHSBNTPGXBUFSDPOWFSUFEUPTUFBN
since last reset)
t &OFSHZVTFEL8IPVSTPSUIFSNTVTFETJODFMBTUSFTFU
To download data, go to the download data section of the
Diagnostic screen.
%BUBCBDLVQBOESFTUPSF
Vapor-logic4 data can be backed up to a USB flash drive. The
backup file contains all information relative to the humidifier,
including firmware, user settings, model number, serial number,
and the configuration string.
Backup files use the serial number in the backup file name so that
the file is easily matched to a particular humidifier.
To create a backup file:
1. Insert a USB flash drive into the USB port on the Vapor-logic4
board.
2. Go to Diagnostics/USB backup-restore/Back up settings
3. Select Yes. The backup process is complete when LED-2 (see
Figure 61-1) illuminates.
To restore from a backup file:
1. Insert the USB flash drive with that humidifier’s backup file into
the USB port on the Vapor-logic4 board.
(PUP%JBHOPTUJDT64#CBDLVQSFTUPSF3FTUPSFTFUUJOHT
3. Select Yes. Note that the serial number of the humidifier and
backup file must match to complete the restore process.
VL4-IOM-1008-UpdateEnglish.pdf 5 4/21/2010 1:31:22 PM

Figure 6-1:
LED-2 location on Vapor-logic4 board
P1
P2
P3
P4
GV1
AI2 24VACTop Mid Low
BT1
LWFPsw
lsw
TT
LED-1 (power indicator)
LED-2
1BHFt6QEBUFEUPSFQMBDF1BHFJOUIF%3*45&&.7BQPSMPHJD*OTUBMMBUJPOBOE0QFSBUJPO.BOVBM
Firmware updates
Firmware updates
1. Obtain the rmware update le from your %3*45&&.
representative or distributor. e update le will be titled
VL4_update.zip or similar. Save this le and note the location
where you have saved the le.
2. Locate the le just saved and double click on the le
(VL4_update.zip); Windows Explorer should unzip the le
and open a window that has the rmware update folder titled
VL4_update or similar.
Note: If Windows Explorer does not open when you double-click on
the le named VL4_update.zip, see instructions below about unzip-
ping les.
Important: Do not change the name of this folder.
3. Copy the unzipped folder (VL4_update) to the root directory of
a USB ash drive (do not place within another folder).
Important: If the USB ash drive already has a folder named
VL4_update, either delete the folder or rename it prior to saving the
latest update folder on the USB. Do not overwrite its contents.
4. Place the humidier system in Standby mode.
5. Insert the USB ash drive loaded with the rmware update
folder into the USB port on the Vapor-logic4 board.
6. Disconnect power to the Vapor-logic4 board.
3FDPOOFDUQPXFSUPUIF7BQPSMPHJDCPBSE
8. Wait for LED-2 (the LED light closest to P1 on the Vapor-logic4
board) or the display to illuminate on and o, and then remove
the USB ash drive. e update has now been loaded on to the
Vapor-logic4 board.
CAUTION! %0/053&.07&5)&64#'-"4)%3*7&#&'03&
-&%035)&%*41-":*--6.*/"5&40/"/%0''%PJOH
so can corrupt the update and may render the control board useless.
If in doubt, check the version number on the display (when avail-
able) or wait ve (5) minutes from when the power was turned on to
remove the USB ash drive.
Important: 3FNPWFUIF64#ĘBTIESJWFBęFS-&%PSUIFEJTQMBZ
illuminates on and o. If power is cycled again while the USB is in-
serted, the upgrade process repeats and must be allowed to complete
before the USB is removed.
9. Verify tIFĕSNXBSFVQEBUFJTDPNQMFUFCZHPJOHUPUIF)VNJEJ-
er info section of the Diagnostics screen on the keypad/display
or Web interface. Firmware version should now be 1.1.0
10. Update the clock/calendar to today’s date.
How to unzip a file
If you are using Windows XP, then your operat-
ing system has built-in support for Zip files,
and the instructions above should work for
unzipping a file. If the above instructions do
not work for opening the VL4_update.zip file,
then you may need to install a special applica-
tion. One application that has a free down-
MPBEJTBWBJMBCMFBUIUUQXXXXJO[JQDPN
prod_down.htm
VL4-IOM-1008-UpdateEnglish.pdf 6 4/21/2010 1:31:22 PM

Modbus, BACnet, LonTalk
interoperability
Table 7-1:
Interoperability variable and object names
7BSJBCMFOBNFBOE
#"$OFUPCKFDUOBNF
3FBE0OMZ
30PS
3FBE8SJUF
38
.PECVT
register
OVNCFS
#"$OFU
0CKFDU
5ZQFBOE
Instance
-PO5BMLWBSJBCMF
names
Description Units 3BOHF
I-P units SI units I-P units SI units
3FBEPOMZBOBMPHWBSJBCMFT
Space_RH RO IR-1 "* nvoSpaceRH
Read the relative
humidity content of the
air in the space being
humidified.
%%UP UP
Space_dew_point RO IR-2 "* nvoSpaceDewPoint
Read the dew point of
the air in the space being
humidified.
ºF ºC UP -6 to 26
Duct_RH RO IR-3 "* nvoDuctRH
Read the relative
humidity content of the
air in the duct.
%%UP UP
Steam_demand_mass RO IR-4 "* nvoSteamDmndMass
Read the steam demand
in pounds or kilograms
per hour.
MCTIS LHI UP
UP
Steam_demand_percent RO IR-5 "* nvoSteamDemand%
Read the steam demand
as a percentage of the
humidifier’s total capacity.
%%UP UP
Aux_temp RO IR-6 "* nvoAuxTemp
Read the temperature of
the auxiliary temperature
sensor.
ºF ºC UP UP
Tank_temp RO IR-7 "* nvoTankTemp
Read the temperature
of the water in the
humidifier’s evaporating
chamber.
ºF ºC UP
265
-151 to
129
Steam_output_mass RO *3 AV-1 nvoSteamOutMass
Read the estimated
amount of steam the
humidifier is producing
in pounds or kilograms
per hour.
MCTIS LHI UP
UP
Steam_output_percent RO IR-9 AV-2 nvoSteamOutput%
Read the estimated
amount of steam the
humidifier is producing
as a percentage of the
humidifier’s total capacity.
%&UP UP
Water_until_ADS RO *3 AV-3 nvoWaterUntilADS
Read the pounds or
kilograms of water
remaining to be
converted to steam
before the next automatic
drain sequence (ADS)
cycle.
lbs kg UP
UP
Water_until_service RO IR-11 AV-4 nvoWaterTilSrvc
Read the pounds or
kilograms of water
remaining to be
converted to steam
before the next service
cycle.
lbs kg UP
UP
More on the next page >
6QEBUFEUPSFQMBDF1BHFJOUIF%3*45&&.7BQPSMPHJD*OTUBMMBUJPOBOE0QFSBUJPO.BOVBMt1BHF
VL4-IOM-1008-UpdateEnglish.pdf 7 4/21/2010 1:31:22 PM

Modbus, BACnet, LonTalk
interoperability
Table 8-1:
Interoperability variable and object names
7BSJBCMFOBNFBOE
#"$OFUPCKFDUOBNF
3FBE0OMZ
30PS
3FBE8SJUF
38
.PECVT
register
OVNCFS
#"$OFU
0CKFDU
5ZQFBOE
Instance
-PO5BMLWBSJBCMF
names
Description Units 3BOHF
I-P units SI units I-P units SI units
4FUVQWBSJBCMFT
Run_mode
Write HR-1 .47 nviRunMode
Set the current mode of
the unit or system. The
defined options are:
1 Auto
2 Local standby
3 System standby
4 Manual drain
-- -- 1 to 4 1 to 4
Read HR-1 .47 nvoRunMode
Read the current mode
of the unit or system. The
defined options are:
1 Auto
2 Local standby
3 System standby
4 Manual drain
5 Test outputs
6 Test run
-- -- 1 to 6 1 to 6
Space_RH_set_point
Write HR-2 "7 nviSpaceRHsetPt Set or read the humidity
set point for the space
being humidified.
%%UP UP
Read HR-2 "7 nvoSpaceRHsetPt % % UP UP
Space_dew_point_set_point
Write HR-3 "7 nviSpaceDewPtSP Set or read the dew point
set point for the space
being humidified.
ºF ºC UP -6 to 26
Read HR-3 "7 nvoSpaceDewPtSP ºF ºC UP -6 to 26
Duct_high_limit_set_point
Write HR-4 "7 nviDuctHLsetPt Set or read the duct high
limit set point.
%%UP UP
Read HR-4 "7 nvoDuctHLsetPt % % UP UP
Fieldbus_demand_mass Write Only HR-5 "7 nviFbusDemndMass
Set the steam output
(as demanded via the
fieldbus) as a percentage
of the humidifier’s total
capacity.
MCTIS LHI UP
UP
Fieldbus_demand_% Write Only HR-6 "7 nviFldBusDemand%
Set the steam output (as
demanded via fieldbus)
in pounds or kilograms
per hour. If the request
exceeds the unit’s
capacity, the unit will run
BUDBQBDJUZ
%%UP UP
PID_band RW HR-7 "7 nciPIDband Set the PID band. % % UP UP
PID-Kp RW )3 AV-11 nciPIDkp Set the PID-Kp
(proportional gain) factor. -- -- UP UP
PID-Ki RW HR-9 AV-12 nciPIDki Set the PID-Ki (integral
gain) factor. -- -- UP UP
PID-Kd RW )3 AV-13 nciPIDkd Set the PID-Kp (derivative
gain) factor. -- -- UP UP
More on the next page >
1BHFt6QEBUFEUPSFQMBDF1BHFJOUIF%3*45&&.7BQPSMPHJD*OTUBMMBUJPOBOE0QFSBUJPO.BOVBM
VL4-IOM-1008-UpdateEnglish.pdf 8 4/21/2010 1:31:22 PM

Modbus, BACnet, LonTalk
interoperability
Table 9-1:
Interoperability variable and object names
7BSJBCMFOBNFBOE
#"$OFUPCKFDUOBNF
3FBE0OMZ
30PS
3FBE8SJUF
38
.PECVT
register
OVNCFS
#"$OFU
0CKFDU
5ZQFBOE
Instance
-PO5BMLWBSJBCMF
names*
Description Units 3BOHF
I-P units SI units I-P units SI units
3FBEPOMZEJHJUBM*0
Airflow_proving_switch RO DI-1 #* nvoAirflowSwitch 0QFO$MPTFE -- -- -- --
Duct_HL_switch RO DI-2 #* nvoDuctHLswitch 0QFO$MPTFE -- -- -- --
Safety_interlock RO DI-3 #* nvoSafetyI-lock 0QFO$MPTFE -- -- -- --
Combustion_air_damper_
(GTS) RO DI-4 #* nvoCombustAirDmp %BNQFS$MPTFE
%BNQFS0QFO -- -- -- --
Flue_pressure_switch_(GTS) RO DI-5 #* nvoFluePressurSw 0QFO$MPTFE -- -- -- --
Power_vent_switch_(GTS) RO DI-6 #* nvoPowerVentSwch 7FOU0GG7FOU0O -- -- -- --
Low_water_sensor_ (GTS) RO DI-7 #* nvoLowWaterSensr /P8BUFS8BUFS -- -- -- --
Fill_valve RO %* #0 nvoFillValve $MPTFE0QFO -- -- -- --
Drain_valve RO DI-9 #0 nvoDrainValve /PU%SBJOJOH
%SBJOJOH -- -- -- --
Faults and alarms
Active_messages_exist RO DV-1 #7 nvoMessages Flags all active messages -- -- -- --
Active_auto_cleared_alarms_
exist RO DV-2 #7 nvoAlarms1 Flags all auto-cleared
alarms -- -- -- --
Active_manually_cleared_
alarms_exist RO DV-3 #7 nvoAlarms2 Flags all manually cleared
alarms -- -- -- --
Clear_all_faults RW DV-4 #7 nviClearAllFaults When set will clear all
active faults -- -- -- --
Alarm_tank_temp_sensor_
failed RW DV-5 #7 nvoAlrmTnkTmpSen See Alarms menu. -- -- -- --
Alarm_tank_overtemp RW DV-6 #7 nvoAlrmOvertemp See Alarms menu. -- -- -- --
Alarm_RH_signal_out_of_
range
RW DV-7 #7
nvoAlrmRHsignal See Alarms menu. -- -- -- --
Alarm_dew_pt_sig_out_of_
range nvoAlrmDewPtSgnl See Alarms menu. -- -- -- --
Alarm_demand_sig_out_of_
range nvoAlrmDemndSgnl See Alarms menu. -- -- -- --
Alarm_duct_RH_sig_out_of_
range RW %7 #7 nvoAlrmDuctRHsig See Alarms menu. -- -- -- --
Alarm_aux_temp_sens_out_
of_rnge RW DV-9 #7 nvoAlrmAuxTemp See Alarms menu. -- -- -- --
Alarm_water_probe_miswired RW %7 #7 nvoAlrmProbeWire See Alarms menu. -- -- -- --
Alarm_water_probe_failed RW DV-11 BV-11 nvoAlrmProbeFail See Alarms menu. -- -- -- --
Note:
* OWJ-PO5BML4/75TBSFXSJUFPOMZOWPBSFSFBEPOMZ
More on the next page >
6QEBUFEUPSFQMBDF1BHFJOUIF%3*45&&.7BQPSMPHJD*OTUBMMBUJPOBOE0QFSBUJPO.BOVBMt1BHF
VL4-IOM-1008-UpdateEnglish.pdf 9 4/21/2010 1:31:22 PM

Modbus, BACnet, LonTalk
interoperability
Table 10-1:
Interoperability variable and object names
7BSJBCMFOBNFBOE
#"$OFUPCKFDUOBNF
3FBE0OMZ
30PS
3FBE8SJUF
38
.PECVT
register
OVNCFS
#"$OFU
0CKFDU
5ZQFBOE
Instance
-PO5BMLWBSJBCMF
names*
Description Units 3BOHF
I-P units SI units I-P units SI units
'BVMUTBOEBMBSNTDPOU
Alarm_excess_fill_time RW DV-12 BV-12 nvoAlrmFillTime See Alarms menu. -- -- -- --
Alarm_excess_refill_time RW DV-13 BV-13 nvoAlrmRefilTime See Alarms menu. -- -- -- --
Alarm_tank_not_draining RW DV-14 BV-14 nvoAlrmNoDrain See Alarms menu. -- -- -- --
Alarm_excess_water_no_
demand RW DV-15 BV-15 nvoAlrmXessWater See Alarms menu. -- -- -- --
Alarm_no_SDU_airflow RW DV-16 BV-16 nvoAlrmNoSDUair See Alarms menu. -- -- -- --
Alarm_no_power_vent_airflow RW DV-17 BV-17 nvoAlrmPrVentAir See Alarms menu. -- -- -- --
Alarm_no_combustion_airflow RW %7 #7 nvoAlrmNoCombAir See Alarms menu. -- -- -- --
Alarm_blocked_flue RW DV-19 BV-19 nvoAlrmBlockdFlu See Alarms menu. -- -- -- --
Alarm_burner_1_failed RW %7 #7 nvoAlrmBurner1 See Alarms menu. -- -- -- --
Alarm_burner_2_failed RW DV-21 BV-21 nvoAlrmBurner2 See Alarms menu. -- -- -- --
Alarm_burner_3_failed RW DV-22 BV-22 nvoAlrmBurner3 See Alarms menu. -- -- -- --
Alarm_burner_4_failed RW DV-23 BV-23 nvoAlrmBurner4 See Alarms menu. -- -- -- --
Alarm_ignition_module_1_
failed RW DV-24 BV-24 nvoAlrmIgnitMod1 See Alarms menu. -- -- -- --
Alarm_ignition_module_2_
failed RW DV-25 BV-25 nvoAlrmIgnitMod2 See Alarms menu. -- -- -- --
Alarm_ignition_module_3_
failed RW DV-26 BV-26 nvoAlrmIgnitMod3 See Alarms menu. -- -- -- --
Alarm_ignition_module_4_
failed RW DV-27 BV-27 nvoAlrmIgnitMod4 See Alarms menu. -- -- -- --
Alarm_blower_1_failed RW %7 #7 nvoAlrmBlower1 See Alarms menu. -- -- -- --
Alarm_blower_2_failed RW DV-29 BV-29 nvoAlrmBlower2 See Alarms menu. -- -- -- --
Alarm_blower_3_failed RW %7 #7 nvoAlrmBlower3 See Alarms menu. -- -- -- --
Alarm_blower_4_failed RW DV-31 BV-31 nvoAlrmBlower4 See Alarms menu. -- -- -- --
Alarm_gas_valve_1_failed RW DV-32 BV-32 nvoAlrmGasValve1 See Alarms menu. -- -- -- --
Alarm_gas_valve_2_failed RW DV-33 BV-33 nvoAlrmGasValve2 See Alarms menu. -- -- -- --
Alarm_gas_valve_3_failed RW DV-34 BV-34 nvoAlrmGasValve3 See Alarms menu. -- -- -- --
Alarm_gas_valve_4_failed RW DV-35 BV-35 nvoAlrmGasValve4 See Alarms menu. -- -- -- --
Alarm_low_water RW DV-36 BV-36 nvoAlrmLowWater See Alarms menu. -- -- -- --
Alarm_low_signal_current RW DV-37 BV-37 nvoAlrmDrivemA See Alarms menu. -- -- -- --
Note:
* OWJ-PO5BML4/75TBSFXSJUFPOMZOWPBSFSFBEPOMZ
More on the next page >
1BHFt6QEBUFEUPSFQMBDF1BHFJOUIF%3*45&&.7BQPSMPHJD*OTUBMMBUJPOBOE0QFSBUJPO.BOVBM
VL4-IOM-1008-UpdateEnglish.pdf 10 4/21/2010 1:31:22 PM

Modbus, BACnet, LonTalk
interoperability
Table 11-1:
Interoperability variable and object names
7BSJBCMFOBNFBOE
#"$OFUPCKFDUOBNF
3FBE0OMZ
30PS
3FBE8SJUF
38
.PECVT
register
OVNCFS
#"$OFU
0CKFDU
5ZQFBOE
Instance
-PO5BMLWBSJBCMF
names*
Description Units 3BOHF
I-P units SI units I-P units SI units
Messages
Message_replace_contactors RW %7 #7 nvoMsgReplCntctr See Messages menu. -- -- -- --
Message_service_unit RW DV-39 BV-39 nvoMsgSrviceUnit See Messages menu. -- -- -- --
Message_drain_pending RW %7 #7 nvoMsgDrainPend See Messages menu. -- -- -- --
Message_no_duct_airflow RW DV-41 BV-41 nvoMsgNoDuctAir See Messages menu. -- -- -- --
Message_interlock_open RW DV-42 BV-42 nvoMsgIlockOpen See Messages menu. -- -- -- --
Message_freeze_prevent_
draining RW DV-43 BV-43 nvoMsgFreezDrain See Messages menu.
Message_end-of-season_active RW DV-44 BV-44 nvoMsgEOSactive See Messages menu. -- -- -- --
Message_temp_comp_on RW DV-45 BV-45 nvoMsgTempCompOn See Messages menu. -- -- -- --
Message_clean_probes RW DV-46 BV-46 nvoMsgCleanProbe See Messages menu. -- -- -- --
Message_duct_HL_trip RW DV-47 BV-47 nvoMsgDuctHLtrip See Messages menu. -- -- -- --
Message_duct_HL_span RW %7 #7 nvoMsgDuctHLspan See Messages menu. -- -- -- --
Message_insufficient_water RW DV-49 BV-49 nvoMsgH2Ocutout See Messages menu. -- -- -- --
Message_boiling_temp_
calibrated RW %7 #7 nvoMsgBoilTempCl See Messages menu. -- -- -- --
Note:
* OWJ-PO5BML4/75TBSFXSJUFPOMZOWPBSFSFBEPOMZ
6QEBUFEUPSFQMBDF1BHFJOUIF%3*45&&.7BQPSMPHJD*OTUBMMBUJPOBOE0QFSBUJPO.BOVBMt1BHF
VL4-IOM-1008-UpdateEnglish.pdf 11 4/21/2010 1:31:22 PM

4PGUXBSF7FSTJPO
'PSN/P7-*0.6QEBUF
1BSU/P
%3*45&&.$PSQPSBUJPO
"O*40 certified corporation
U.S. Headquarters:
14949 Technology Drive
Eden Prairie, MN 55344
952-949-2415
GBY
European office:
Marc Briers
Grote Hellekensstraat 54 b
#;POIPWFO
Belgium
WPJDF
GBY
E-mail: [email protected]
Continuous product improvement is a
QPMJDZPG%3*45&&.$PSQPSBUJPOUIFSFGPSF
product features and specifications are
subject to change without notice.
DRI-STEEM, GTS, and Vapor-logic are
registered trademarks of DRI-STEEM
Corporation and are filed for trademark
registration in Canada and the European
community.
Product and corporate names used in this
document may be trademarks or registered
trademarks. They are used for explanation
only without intent to infringe.
ª%3*45&&.$PSQPSBUJPO
&YQFDURVBMJUZGSPNUIFJOEVTUSZMFBEFS
'PSPWFSZFBST%3*45&&.IBTCFFO
leading the industry with creative and
reliable humidification solutions. Our focus
on quality is evident in the construction
of the Vapor-logic4, which has a two year
warranty that covers all parts.
For more information
www.dristeem.com
Technical support
'PSUIFNPTUDVSSFOUQSPEVDUJOGPSNBUJPO
WJTJUPVS8FCTJUFXXXESJTUFFNDPN
5XPZFBS-JNJUFE8BSSBOUZ
%3*45&&.$PSQPSBUJPOi%3*45&&.wXBSSBOUTUPUIFPSJHJOBMVTFSUIBUJUT
products will be free from defects in materials and workmanship for a period
of two (2) years after installation or twenty-seven (27) months from the date
%3*45&&.TIJQTTVDIQSPEVDUXIJDIFWFSEBUFJTUIFFBSMJFS
*GBOZ%3*45&&.QSPEVDUJTGPVOEUPCFEFGFDUJWFJONBUFSJBMPSXPSLNBOTIJQ
EVSJOHUIFBQQMJDBCMFXBSSBOUZQFSJPE%3*45&&.TFOUJSFMJBCJMJUZBOEUIF
purchaser’s sole and exclusive remedy, shall be the repair or replacement of the
EFGFDUJWFQSPEVDUPSUIFSFGVOEPGUIFQVSDIBTFQSJDFBU%3*45&&.TFMFDUJPO
%3*45&&.TIBMMOPUCFMJBCMFGPSBOZDPTUTPSFYQFOTFTXIFUIFSEJSFDUPS
indirect, associated with the installation, removal or reinstallation of any defective
product. The Limited Warranty does not include cylinder replacement for electrode
steam humidifiers.
%3*45&&.T-JNJUFE8BSSBOUZTIBMMOPUCFFGGFDUJWFPSBDUJPOBCMFVOMFTT
there is compliance with all installation and operating instructions furnished by
%3*45&&.PSJGUIFQSPEVDUTIBWFCFFONPEJGJFEPSBMUFSFEXJUIPVUUIFXSJUUFO
DPOTFOUPG%3*45&&.PSJGTVDIQSPEVDUTIBWFCFFOTVCKFDUUPBDDJEFOUNJTVTF
mishandling, tampering, negligence or improper maintenance. Any warranty claim
NVTUCFTVCNJUUFEUP%3*45&&.JOXSJUJOHXJUIJOUIFTUBUFEXBSSBOUZQFSJPE
%FGFDUJWFQBSUTNBZCFSFRVJSFEUPCFSFUVSOFEUP%3*45&&.
%3*45&&.T-JNJUFE8BSSBOUZJTNBEFJOMJFVPGBOE%3*45&&.EJTDMBJNT
all other warranties, whether express or implied, including but not limited to any
*.1-*&%8"33"/5:0'.&3$)"/5"#*-*5:"/:*.1-*&%8"33"/5:
0''*5/&44'03"1"35*$6-"3163104&BOZJNQMJFEXBSSBOUZBSJTJOHPVU
of a course of dealing or of performance, custom or usage of trade.
%3*45&&.4)"--/056/%&3"/:$*3$6.45"/$&4#&-*"#-&'03
"/:%*3&$5*/%*3&$5*/$*%&/5"-41&$*"-03$0/4&26&/5*"-
%"."(&4*/$-6%*/(#65/05-*.*5&%50-0440'130'*54
3&7&/6&03#64*/&4403%"."(&03*/+63:501&340/403
1301&35:*/"/:8":3&-"5&%505)&."/6'"$563&035)&64&
0'*54130%6$545IFFYDMVTJPOBQQMJFTSFHBSEMFTTPGXIFUIFSTVDIEBNBHFTBSF
sought based on breach of warranty, breach of contract, negligence, strict liability in
UPSUPSBOZPUIFSMFHBMUIFPSZFWFOJG%3*45&&.IBTOPUJDFPGUIFQPTTJCJMJUZPG
such damages.
#ZQVSDIBTJOH%3*45&&.TQSPEVDUTUIFQVSDIBTFSBHSFFTUPUIFUFSNTBOE
conditions of this Limited Warranty.
&YUFOEFEXBSSBOUZ
5IFPSJHJOBMVTFSNBZFYUFOEUIFUFSNPGUIF%3*45&&.-JNJUFE8BSSBOUZ
for a limited number of months past the initial applicable warranty period and
term provided in the first paragraph of this Limited Warranty. All the terms and
conditions of the Limited Warranty during the initial applicable warranty period
and term shall apply during any extended term. An extended warranty term of
an additional twelve (12) months or twenty four (24) months of coverage may be
purchased. The extended warranty term may be purchased until eighteen (18)
months after the product is shipped, after which time no extended warranties are
available.
Any extension of the Limited Warranty under this program must be in writing,
TJHOFECZ%3*45&&.BOEQBJEGPSJOGVMMCZUIFQVSDIBTFS
mc_051308_0630
VL4-IOM-1008-UpdateEnglish.pdf 12 4/21/2010 1:31:22 PM
Other manuals for Vapor-logic 4
2
Table of contents
Other DriSteem Controllers manuals
Popular Controllers manuals by other brands

CARLO GAVAZZI
CARLO GAVAZZI Sx2WEB Series manual

Bailey
Bailey infi 90 Modular Power System II Instruction

Witt
Witt LEAK-MASTER EASY+ instruction manual

ICI Caldaie
ICI Caldaie ICI Kronos INSTRUCTIONS FOR USER, INSTALLER AND TECHNICAL SERVICE CENTRE

Chauvet
Chauvet CH-751 user guide

Inventronics
Inventronics QBM DALI CONV LI quick start guide