The Alarms screen
Table 4-1:
Alarms menu
"MBSNMBCFM Description Does alarm
BVUPDMFBS
Tank temp sensor failed Tank temp sensor has failed. No
RH signal out of range RH signal is out of range. Yes
Dew point sig. out of range Dew point signal is out of range. Yes
Demand signal Demand signal is out of range. Yes
Duct RH signal out of range Duct RH signal is out of range. Sensor my be faulty. Yes
Aux temp sens out of range Auxiliary temp sensor signal is out of range. Yes
Water probe miswired Water probe head is miswired or faulty. Yes
Faulty water probe Water probe readings are suspect, likely caused by scale on probe. No
Excess fill time Fill valve has been on too long during initial tank fill. Bottom probe is not in contact with water. Yes
Excess refill time Re-filling is taking too long. Top probe is not in contact with water. Yes
Tank not draining Drain valve has been open for the prescribed amount of time based on the humidifier model, and water is still
touching the low water probe. Yes
Tank overtemp Fault occurs at boiling temperature plus 25 °F (13 °C). All units are put into a keep-cool state where fill and drain
cycles operate to keep tank cool. Note: Resolve issue, then clear alarm, shut down humidifier, and restart. No
Excess water no demand
Humidifier continues to add water when there is no demand, signifying unit continues to make steam. All units
are put into a keep-cool state where fill and drain cycles operate to keep tank water from boiling.
Note: Resolve issue, then clear alarm, shut down humidifier, and restart.
No
No SDU airflow Airflow proving switch in the SDU (space distribution unit, a fan-based dispersion assembly) indicates no airflow.
No steam is produced while alarm is active. Yes
No power vent airflow Pressure switch indicates there is no airflow at the power venter. Yes
No combustion airflow Switch indicates the combustion air damper is closed. Yes
Blocked flue Flue pressure switch indicates positive pressure in flue. GTS will not ignite when this fault is active. Yes
Burner 1, 2, 3, or 4 fault Burner tried one or more times to light and did not succeed. Once this fault is active, Vapor-logic4 locks out the
burner and does not try to light it again until fault is cleared. Other burners can run. No
Ignition mod. 1, 2, 3, or 4 fault Ignition module has not opened the gas valve. Once this fault is active, Vapor-logic4 locks out the ignition module
and does not try to start it again until fault is cleared. Other ignition modules can run. No
Blower 1, 2, 3, or 4 fault Blower is turning at less than the specified minimum RPM. Unit not allowed to run. Yes
Gas valve 1, 2, 3, or 4 fault Gas valve is on when it should be off. Unit not allowed to run. Yes
Low water Low water probe is in contact with water and low water sensor is not in contact with water. Yes
Low input signal current Demand signal by others current is below minimum threshold. Yes
Notes:
t 4FFUIFUSPVCMFTIPPUJOHTFDUJPOJOUIJTNBOVBMGPSBMBSNQPTTJCMFDBVTFTBOESFDPNNFOEFEBDUJPOT
t 5IF"MBSNT-PHEJTQMBZTBMBSNOBNFEBUFBOEUJNFPGPDDVSSFODFQMVTw"DUJWFww$MFBSFEwPSw"VUPDMFBSFEw
t "DUJWFBMBSNTEJTQMBZGJSTUJOUIF"MBSNT-PHGPMMPXFECZDMFBSFEBMBSNTBVUPDMFBSFEBOEPSNBOVBMMZDMFBSFEMJTUFEJOPSEFSPGPDDVSSFODF
t 5IF"MBSNT-PHEJTQMBZTNBYJNVNBMBSNT$MFBSFEBMBSNTMFBWFUIFMPHGJSTU
t *GBOBMBSNFWFOUPDDVSTBOEJTOPUNBOVBMMZPSBVUPDMFBSFEEVSJOHVOJUPQFSBUJPOUIFBMBSNXJMMTUBZUIFSFVOUJMUIFSFJTEFNBOEBOEUIFVOJUJTSVOOJOH
1BHFt6QEBUFEUPSFQMBDF1BHFJOUIF%3*45&&.7BQPSMPHJD*OTUBMMBUJPOBOE0QFSBUJPO.BOVBM
VL4-IOM-1008-UpdateEnglish.pdf 4 4/21/2010 1:31:22 PM