Evinox ModuSat SP Cooling Unit User manual

2551988D
ModuSat SP Cooling Unit
ModuSat SP Heating Unit
Installation Manual

2551988D
TABLE OF CONTENTS
GENERAL INFORMATION ...........................................................................................1
TECHNICAL FEATURES................................................................................................3
INSTALLATION ...........................................................................................................7
Water treatment ..................................................................................................... 13
Electrical Connections.............................................................................................. 15
5.2.1 RJ45 Connections..........................................................................................................16
SETTING INTO OPERATION / COMISSIONING............................................................ 19
6.3.1 Pressure independent control valve (PICV) ..................................................................20
6.3.2 Pump.............................................................................................................................21

2551988D
SPH/SPC SERVICING AND INSPECTION ..................................................................... 23
WARRANTY ............................................................................................................. 24
KIWA CERTIFICATE................................................................................................... 26

1 2551988C
GENERAL INFORMATION
Application
The Evinox ModuSat Single Plate heating/cooling units have been designed to provide
heating/cooling for dwellings served by a communal or district system. The heating/cooling is
supplied via primary water, which is provided by centralised plant. The Evinox ModuSat SPH/SPC
units require electrical supply to function.
Symbols
IMPORTANT NOTE REGARDING CORRECT INSTALLATION
WARNING REGARDING PERSONAL SAFETY
WARNING OF DANGER OF ELECTRIC SHOCK
Warning
Follow the instructions. These instructions must be read and observed carefully before
installing and operating the ModuSat unit. Failure to read and follow the instructions
provided within this document may cause a safety hazard or/and failure of the equipment.
Qualified personnel only. The Evinox cooling unit must be installed, commissioned and
maintained by a qualified and competent personnel in accordance with this document as
well as national regulations and standards.
Warning of transport damage. Always check to ensure that the ModuSat unit has not been
damaged during the transport.
Warranty. Any modifications or adjustments carried out without Evinox Energy official
authorisation will invalidate the warranty and absolve Evinox Energy from any liability.
Product modifications. Evinox Energy reserves the right to make changes or modifications to
the products without prior notice.

2 2551988C
Safety instructions
The Evinox heating/cooling interface unit must be installed, commissioned and maintained by a
qualified and competent personnel in accordance with this document as well as national regulations
and standards.
Risk of Electric shock.
Disconnect the electricity supply before starting any works on the unit.
Qualified personnel.
Electrical installation must only be carried out by technical personnel. .
In the case of water leak.
Slowly close the isolation valve at the top of the unit
Contact Evinox Energy
Maintenance requirements
We recommend the unit is checked at least every 24 months by an authorised maintenance
engineer. If the unit is subject to excessively heavy usage or non domestic installations (for example
in a light commercial environment), we recommend having it checked more than every 24 months.

3 2551988C
TECHNICAL FEATURES
Typical ModuSat Heating/Cooling Unit
Note: The product may look different from the image shown.
Function and operation
District or communal system –the primary heating/cooling water flow is used to produce
secondary heating/cooling.
Apartment heating/cooling –when the space heating/cooling demand is requested by the
end user controller, the heating/cooling operation is started. The electronically controlled
PICV is used to modulate the primary flow rate to match the heating/cooling demand. The
unit has an integrated circulation pump which is switched on when the heating/cooling is on.

4 2551988C
Typical Schematic (All Top Connections)
Note: Other connection arrangements may be used.
Components
APrimary circuit flow
BPrimary circuit return
EDwelling flow
FDwelling return
G Connection for safety
discharge
Primary Circuit Side
1Insulated plate heat exchanger
2Pressure Independent
Control Valve (PICV) with
actuator
3Heat meter
Cooling Secondary Side Circuit
4Expansion vessel
5Low pressure switch
6Safety relief discharge
7 Pressure gauge
8Dwelling circulation pump
Controls & Other Items
9Electronic control board
10 Room controller
11 Flushing Bypass kit
12 Filling loop (External)
S1 –Primary flow temperature sensor
S2 –Primary return temperature
sensor
S4 –Dwelling flow temperature sensor
S5 –Dwelling return temperature
sensor

5 2551988C
Technical Parameters
Electrical
Electric supply
220 / 240 Volt (AC)
Frequency
50 Hz
Current absorption
0,6 Amps
Hydraulic connections
SPH/SPC-R20 …
SPH/SPC-R60
SPH/SPC-R70 …
SPH/SPC-B40
SPH/SPC-B50 …
SPH/SPC-B70
Primary circuit supply
A
3/4 ”
1”
1 ¼ ‘’
Primary circuit return
B
3/4 “
1”
1 ¼ ‘’
Apartment circuit supply
E
3/4 “
1’’
1 ¼ ‘’
Apartment circuit return
F
3/4 “
1’’
1 ¼ ‘’
Safety discharge
G
1/2 “
1/2 “
1/2 “
Hydraulic characteristics
Pipework material
Copper
Plate heat exchanger material
Stainless steel 316L
Operating medium
Water
Primary circuit max pressure
16 bar Optional
Primary minimum differential pressure
50 kPa* (0.5 bar)
*may vary depending on the required output
Primary maximum differential pressure
400 kPa* (4 bar)
*may vary depending on the required output
Secondary circuit recommended cold fill
pressure
1.5 bar
Secondary maximum pressure
3 bar
Apartment heating and cooling
expansion vessel size
SPC/SPH-R20 … SPC/SPH-R70
SPC/SPH-B30 … SPC/SPH-B70
5
8
Weight
Dry (kg)
Wet (kg)
SPH/SPC R20
33.0
34.0
SPH/SPC R30
33.7
34.8
SPH/SPC R40
34.2
35.6
SPH/SPC R50
34.8
36.4
SPH/SPC R60
35.4
37.2
SPH/SPC R70
43.1
46.6
SPH/SPC B30
45.8
50.5
SPH/SPC B40
47.2
52.8
SPH/SPC B50
53.9
60.9
SPH/SPC B60
55.2
63.2
SPH/SPC B70
56.6
65.5

6 2551988C
Typical Dimensions
These dimensions are for both SPC and SPH units.
Minimum space requirements for access and servicing: Top: 190 mm should be allowed for the
flushing bypass kit on the top of the unit with 3/4 “ connections and 250 mm for the units with 1”
connections, Front: 700 mm, Side: 50 mm, Bottom: Sufficient space to connect the drain.
Please Note: Flushing bypass to be installed on primary connections A & B.

7 2551988C
INSTALLATION
The ModuSat interface units must be installed, commissioned and maintained by qualified and
competent personnel in accordance with this document as well as national regulations and
standards.
Handling
The unit should be moved into position before lifting still within its packaging to prevent any
damage whilst being positioned. Only once it is safely situated, the unit should be removed
from its packaging and lifted into position.
The ModuSat unit may have been transported and handled many times prior to the
installation, therefore it is vitally important that all unions and connections are checked and
tightened as required. In case of damage please contact Evinox Energy on 01372 722277
immediately.
Packaging materials must be disposed in accordance with the requirements of the
construction site or the property.
Lifting.
Take care when lifting this appliance. It is recommended that at least two people
perform the lifting.
Leave caps over the connections.
Ensure that the protective cover (caps) over the ModuSat pipe connections are
kept in place to prevent ingress of any debris.
Positioning
The ModuSat units should be installed in a sheltered environment and are not suitable for outdoor
installation. It is recommended that the surrounding environment conditions do not exceed 40 °C
with the relative humidity from 15% to 85%.
Note: As the unit contains water in order to operate, it is recommended not to place electrical
devices, such as control boards and other devices, underneath the unit in the case of a water leak.
The manufacturer cannot accept any responsibility for goods damaged in such a way.
Maintenance space.
It should be ensured that a sufficient space around the unit is provided to allow
the future maintenance and servicing of the unit. The removal of the HIU panels
should not be restricted.

8 2551988C
Hydraulic connections
Connection arrangement.
Ensure that the hydraulic connections of the pipework piped up to the unit are
correct and follows the hydraulic schematic. The manufacturer cannot accept any
responsibility for any damage caused to the unit due to crossed connections.
Any Evinox engineer callout/visit due to this issue will be chargeable.
The ModuSat unit is designed to be wall mounted with
the typical primary and secondary connections as
shown below.
The Evinox Energy flushing by-pass valve kit should be
installed prior to connecting the unit and the valves
left in an isolated position.
The whole system should be cleaned and flushed
before installing the cooling interface unit to ensure
the ModuSat unit is not damaged.
Wall fixing
The ModuSat unit is designed to be wall mounted. There are drillings on the back plate of the unit
that ensure mounting with the wall fixing bracket.
Wall fixing
Installer must ensure that appropriate fixings are used.

9 2551988C
Use of Pre-installation Rig
A pre-installation rig is available upon request. It consists of a back panel constructed of steel. This
will enable the installer to arrange the piping entering and leaving the unit during first fix prior to the
unit being delivered / installed. The configuration of the pre-installation rig will be as per the unit
being supplied and the project requirements.
HOW TO INSTALL PRE-INSTALLATION RIG
STEP1: Securely fix the mounting
bracket to the wall in the required
position. Hang the ModuSat SPC Pre-
Installation Rig on the wall fixing
bracket. Then slide down by 15mm and
across to the right by 30mm, as
indicated in diagram.
STEP2: Fit the Evinox Energy Flushing
Bypass & Valve Kit to the rig and then
make final connections to the pipework
running to the ModuSat.
STEP3: Shut off isolation valves,
pressure test pipework and then
disconnect the valve unions.
STEP4: To remove the pre-installation
rig slide the rig to the left taking all
connections off centre, slowly lift and
remove.
Maintenance Space
In order to remove the ModuSat cooling interface unit, ensure that 30 mm gap is
left between the hook and the edge of the cutout in the pre-installation rig as
shown in the image below.
30 mm gap

10 2551988C
Evinox Flushing By-pass Kit
Evinox flushing by-pass kit allows to isolate HIU from the network during cleaning and flushing the
system. The kit includes an H shape by-pass with inbuilt isolation valve, 1 strainer and 3 isolation
valves.
Evinox FLUSH-KIT-C01-SS for ModuSat SPC
Evinox FLUSH-KIT-SP1-SS for ModuSat SPH
Close valves
Before connecting flushing by-pass kit to the HIU ensure all isolation valves are
closed. Valves can be opened after the system has been flushed.

11 2551988C
Flushing Primary Circuit
The whole primary system should be cleaned and flushed in
accordance to BG29/2012 before filling ModuSat® heat
interface unit.
To open the by-pass:
Ensure both isolation valves are in the closed position as
shown in the picture.
Use a suitable screwdriver or other tool to twist the
screw on the H-shape by-pass valve into the open
position.
Close the bypass after flushing is complete.
Provide isolation valves and a strainer.
If Evinox valve kit is not used, it must be ensured that there are isolation valves
provided. Strainers on the primary and secondary heating inlets are required to ensure
the components in the unit are protected from debris and sediments.
Tighten the connections.
When connecting the ModuSat® heat interface unit, ensure that all the connections are
tightened to avoid any leaks.
First fill of the HIU
Clean and flush the system before connecting the unit.
Filling the system should be performed only after the system has been fully
flushed and clean. Poor water quality may cause failure of the operation of the
unit.
Water quality.
It is recommended that the flushing and cleaning of the primary circuit, domestic
water circuit and secondary heating circuit is performed by a qualified person in
accordance with current standards, regulations and BSRIA guidelines.
In the case of a water leak.
Take caution of hot water
Slowly close the isolation valves at the top or bottom of the unit
Contact Evinox Energy
The ModuSat® pump should not be used for flushing.
The pump is integral to the unit and should not be used for flushing and cleaning
the system. Failure to meet this requirement will invalidate the warranty.

12 2551988C
Filling the primary circuit
Please take care when filling the ModuSat® unit.
Make sure that the by-pass valve is
in closed position
Slowly open the isolation valves on
the primary circuit.
Visually check that there are no
leaks. Tighten the connections of
the valve kit if necessary.
If there is a leak internal to the unit,
ensure the isolation valves are left
in a closed position.
First fill of apartment heating or cooling system
The ModuSat unit is fitted with a manometer gauge that is mounted in the front panel. This gauge
reading should be used when filling the secondary circuit.
An external filling loop should be used for filling the secondary
circuit with the mains water.
Open the isolation valves slowly when filling the system.
Cold fill should be done to about 1.5 bar in a single story
dwelling. The pressure required will depend on the head of
the system (difference between the lowest and highest point).
Once the required pressure is reached, close the filling loop
ball valve, vent the system and repeat it again.

13 2551988C
Water treatment
The quality and cleanliness of the water within both the primary and secondary circuits is vitally
important, to prevent damage to the ModuSat components and to ensure that the efficiency and
service life of the unit is maintained.
It is therefore necessary to fully flush and treat both primary and secondary circuits using suitable
water treatment chemicals.
Water treatment in accordance to these instructions.
Please confirm with the water treatment consultants that the chemicals used and
cleaning method statement complies with the requirements set out in this
section.
Water quality may damage the unit.
Poor water quality may damage the components used in the unit and invalidate
the warranty. The manufacturer cannot take responsibility for any damage of the
unit caused by poor water quality.
Chemical cleaning and dosing.
Chemical cleaning and dosing of the system should be in line with the current
regulations, standards and guidelines. Which are, but are not limited to:
BSRIA Application Guide BG29/2012
BS7593:2006
Requirements of Thames Water Utilities
The Water Industry Act 1991, Section 119
HSE The Control of Legionellosis 1991
HSC Approved Code of Practice and Guidance HSG274, Part 2
Water Quality Guidelines
TH - Total hardness is caused by calcium
and magnesium.
pH –this measures the alkalinity of the
water, neutral alkalinity is pH7. Heating
systems require an alkaline pH. Lower
pH will increase the corrosion risk.
TDS –. dissolved solids in the system
and is a measure of the cleanliness of
the water. (satisfactory level should be
within TDS of 10% of the mains water) .
Conductivity –this is the measure of the
ability of water to pass an electrical
current.
Free copper –the level of copper in the
system.
Total Iron and Manganese –this
measures iron concentration in mg/litre.
These are strong oxidants and may
increase the risk for corrosion.
Recommended
Hardness (TH)
Up to 150 mg/l (as CaCO3)
Chlorides (Cl-)
Up to 150 mg/l
PH
7.5 –9.0
Resistivity
>2000 Ohm/cm
Sulphate (SO42-)
Up to 70 mg/l
Conductivity
200 crs
TDS
0-200 ppm
Free carbon dioxide
(CO2)
Up to 5 mg/l
Manganese (Mn)
Up to 0.1 mg/l
Iron (Fe)
Up to 0.2 mg/l (or 5ppm)
Copper
Up to 1 mg/l
Typical Water Quality Guidelines

14 2551988C
Visual inspection should be carried out ensuring that the water is clear, bright and free from
particulate matter. The system must be fully vented, pressurised and dosed with anti-corrosion and
anti-bacteria growth inhibitor.
Dosing Secondary System
Once the system is cleaned and flushed the inhibitors should be added to the secondary side to
prevent the corrosion or bacteria growth.
A suitable long term corrosion inhibitor and inhibitor for preventing the bacteria should be
introduced in a proportion of the system volume.
Excessive filling of the secondary circuit with untreated water may lead to scale
build up and corrosion. This may damage the ModuSat unit or reduce the
performance.
Please confirm with the water treatment consultants that the chemicals used and
cleaning method statement complies with the requirements set out in this
section.
Evinox Energy do not take responsibility for approving inhibitors used for dosing
the system.
Warranty due to Water Quality
The warranty of the ModuSat unit is strictly related to the instructions and procedures indicated in
this manual and the warranty does not cover any damage caused by scale and/or corrosion resulting
from poor water quality.
The components and materials used in the system assembly should also be checked to ensure they
do not contribute to dissolved oxygen that can cause corrosion.
Also:-
Ensure there is no air in the system
Ensure there are no “dead” legs in the system
Remove gas permeable parts and materials
Ensure the expansion vessels are properly sized and the pre-charge pressure valve in order to
guarantee positive pressure, with respect to the ambient pressure, throughout the circuits.

15 2551988C
Electrical Connections
Risk of Electric shock.
Disconnect the electric supply before starting any works on the unit.
Qualified personnel.
Electrical installation must only be carried out by technical personnel.
Overvoltage or lightning.
The ModuSat unit has no protection against lightning or other overvoltage shocks.
Power supply via un-switched double pole fused connection.
The ModuSat requires a 220/240V (AC) 50Hz mains supply connection through an
un-switched fused connection fitted with a 3 Amp fuse (to BS1632). Extension
cords, multiple plugs, and other adapters must not be used. The device must be
earthed.
Follow the instructions
Any damage caused by an incorrect connection will invalidate the warranty.
Evinox Energy cannot accept any responsibility for incorrect wiring.
The ModuSat wiring board is located within the ModuSat itself under a removable metal cover. To
access the connection board, the full front case cover should be removed. The connection board is
found in the centre of the unit to your left. To take off the cover the retaining screw should be
removed and the cover lifted off.
Removing the Front panel
To access the wiring board, the front panel must be removed.
The front panel is fixed with four screws –two at the top of the unit and
two at the bottom as shown with are.
Untighten the screws and remove the panel pushing it upwards firs and
then removing it towards yourself.
The panel is powder coated stainless steel. Take care when removing and
placing the front panel to ensure the surface is not damaged. Ensure
After the works are finished, place the panel on the unit and tighten the
screws.

16 2551988C
ModuSat Wiring Connections
The ModuSat wiring board is located within the ModuSat itself under a removable metal cover
To access the connection board take off the cover the retaining screw should be removed and the
cover lifted off. The connection board will then be accessible and all required connections can be
made simply using the clearly labelled screw down terminal connections. Guides for the various
connection applications and requirements are detailed in the wiring principle drawings shown at the
back of this manual.
The Control Board
The control board is located next to the connection board on your right hand side. The
control board cover must not be removed. Doing so may invalidate the warranty.
Connection Terminations
Evinox Energy strongly recommend in accordance with best practice that all wiring
connections to the board, especially the BUS and room controller are terminated using
‘bootlace ferrule’ connectors. These connectors ensure a good connection and that the
whole cross sectional area of the wiring is intact.
5.2.1 RJ45 Connections
If the TCP/IP network is used, instead of the BUS termination the RJ45 can be connected to the
control board. The RJ connection can be found at the bottom of the control board as shown below.
Cable glands are fitted at the bottom of the ModuSat case as shown in below:

17 2551988C
ModuSat Connection Board
Please Note: When
connecting external
valves or pumps to the
ModuSat control board, it
must be ensured that
each connection does not
exceed 1amp @
220/240V (AC).
This manual suits for next models
1
Table of contents
Popular Water System manuals by other brands

Graco
Graco ProMix Auto Service parts

Everpure
Everpure Exubera EV9318-60 Specification sheet

Avidity Science
Avidity Science GENO20 manual

Mueller
Mueller Hydro-Guard HG-3 Operating instructions manual

ZeroWater
ZeroWater Filter Bottle owner's manual

RPI
RPI WATER-MIZER RPA466 Installation, operation and maintenance manual

Kenmore
Kenmore 625.385560 UltraFilter 650 owner's manual

VacPak-It
VacPak-It SVC280 quick start guide

AmeriWater
AmeriWater 00HC-4090 Operation & maintenance manual

Apec Water
Apec Water Instant Hot Installation instructions & owner's manual

Xylem
Xylem Lowara ecocirc S Additional Installation, Operation and Maintenance Instructions

Waterite
Waterite Fusion 2 Owner's manual addendum