Bronze Series LightSpot - MS1001SM & MS1001F
Only suitably qualified personnel should install this equipment.
Fixing
MS1001SM - The housing may be secured to a hard surface or a BESA box. The detector fits into the housing
with a simple bayonet action.
MS1001F - Supplied with a sinking (dry lining) box for flush fitting. Sinking box fits into an 89mm diameter hole in
ceiling tile or plasterboard ceiling. To avoid damage to ceiling tile, do not overtighten. Depth required behind
ceiling: 62mm from front flange plus an allowance for the minimum bend radius of the cable. No access above
the ceiling is necessary.
Note: Do not position within 25cm of a luminaire.
Connection
LOAD
(Max 6 Amps)
N
E
L
Permanent
or switched
supply
N
E
L
Permanent
or switched
supply
Detector
Detector Detector
VOLT-
FREE
OUTPUT
VOLT-
FREE
OUTPUT
VOLT-FREE
OUTPUT
LIVE IN LIVE IN
LIVE IN
NEUTRAL
NEUTRAL NEUTRAL
EARTH
EARTH EARTH
Multiple Detectors
Single Detector
LOAD
(Max 6 Amps)
W4390A
The LIVE IN
terminals are
internally linked
External Link External Link
External Link
Important Additional Notes
1. Only suitably qualified personnel should install this equipment.
2. All terminals on this product are provided for final connections. It is not intended that the product be used as a junction box
for looping cables.
3. Ameans for disconnection must be incorporated in the fixed wiring in accordance with the current wiring regulations.
4. This equipment switches lights no more frequently than would a responsible human occupant. However, manufacturers of
some lighting types (e.g. ‘2D’luminaires) may specify a maximum number of switching cycles and/or a minimum on-time in
order to achieve a predicted lamp life. Please check with the manufacturer of the luminaires to ensure that they are
compatible with automatic controls in this respect.
*
LIVE IN
*
LIVE IN
*
LIVE IN
*
LIVE IN
* *
*
The LIVE IN
terminals are
internally linked
*
Commissioning
The units are supplied with factory default settings (power-up on, fully automatic operation, 20 minute off delay).
Off Delay
The Off Delay is set to 20 minutes and is non-adjustable. A 10-second Off Delay is available for walk testing the
product.
Walk-test Mode
Walk-test mode is used to check that the detector is operating as required. The short off-delay enables the
installer to check that lights are switching on when movements are made at the edge of the detection zone.
1. Change the programmed Off Delay to 10 seconds using either an HP10 or HP2000. When using the HP10,
just press the white button - switch positions are not recognised for this product. When using the HP2000,
select Utilities from the main menu, then select Walk Test and press OK.
2. Move around the area that is being controlled, stopping for 10 seconds to allow the lights to switch off, before
moving and triggering the lights back on. The Off Delay will reset to its 20 minutes after a five minute period.