fafnir VISY-X Guide

Technical Documentation
Edition: 11/2009
Version: 7
Artikel No.: 207064
FAFNIR GmbH Bahrenfelder Str. 19 22765 Hamburg, Germany Tel.: +49/ 40/ 39 82 07-0 Fax: +49/ 40/ 39 06 339
VISY-X
VISY-View

Page 2/34 VISY-View

VISY-View Page 3/34
Content
1Characteristic features of the VISY-View.......................................................4
2Safety instructions...........................................................................................5
3Structure and mode of operation...................................................................5
3.1 Display screen ................................................................................................................6
3.2 Operation elements........................................................................................................ 7
3.3 Power LED .....................................................................................................................9
3.4 Interfaces .......................................................................................................................9
3.5 Alarm signalizing..........................................................................................................10
4Putting into operation ..................................................................................11
5Operation.......................................................................................................13
5.1 Configuration ..............................................................................................................13
5.2 Retrieving tank data ..................................................................................................... 22
5.3 Retrieving filling operation data....................................................................................23
5.4 Retrieving wireless data................................................................................................25
5.5 Alarm messages ........................................................................................................... 25
6Menu structure ..............................................................................................30
7Technical data ................................................................................................33
8Table of figures..............................................................................................34
© Copyright:
Reproduction and translation only with the written consent of the FAFNIR company. FAFNIR reserves the
right to carry out product alterations without prior notice.

Page 4/34 VISY-View
1Characteristic features of the VISY-View
The VISY-View display is an optional component of the VISY-X system (volume
information system).
The VISY-X system can be used to carry out precise, continuous filling level measurements
of up to 16 tanks directly at the filling station. At the same time, the product temperature
and the water level at the tank bottom are also measured. As an extension, several
environmental measurement sensors can be connected.
The system includes:
control unit VISY-Command
up to 16 measurement sensors VISY-Stick
up to 16 measurement sensors VISY-Stick/-Reed Interstitial
up to 16 measurement sensors VISY-Stick/-Reed Sump Manhole
up to 16 measurement sensors VISY-Stick/-Reed Sump Dispenser
up to 8 VISY-Input 8 to connect external systems
up to 8 VISY-Output 4
configuration software VISY-Setup
VISY-View can be used to evaluate and show the tank data alternatively to the filling
station computer.
The display VISY-View serves the purpose of indicating recent tank data, delivery data and
various alarm messages provided by the control unit VISY-Command (see separate
instruction manual "VISY-Stick and VISY-Command").
The appliance is equipped with a four line display screen. VISY-View makes use of an LED
and a buzzer to signal alarm statuses, a serial interface to enable printing alarm and tank
data via a printer, two potential-free outputs to control external devices when selectable
alarm statuses are activated, and one remote input for the connection of a switch.

VISY-View Page 5/34
2Safety instructions
The VISY-X system serves the purpose of measuring and evaluating the filling levels in
filling station tanks for mineral oil fuels. Use the system for this purpose only. The
manufacturer shall not be liable for any form of damage resulting from improper use of
this system!
The VISY-View display was developed, manufactured and inspected in accordance with
state-of-the-art technology and with recognised safety rules and regulations. Neverthe-
less, hazards may arise from the use of this unit. Therefore, observe the following safety
instructions:
Do not change or modify the system or add any equipment without the prior
consent of the manufacturer.
Only use the power supply unit included in the scope of supplies in order to
connect the VISY-View display to the power supply system.
Use original replacement parts only. These comply with the technical require-
ments specified by the manufacturer.
The installation, operation and maintenance of the VISY-View display is only
allowed to be carried out by expert, authorised personnel. Specialised knowledge
must be obtained by undergoing regular training.
Operators, installers and service personnel must observe all applicable safety
regulations. This also applies to the local safety regulations and accident preven-
tion regulations not mentioned in these operating instructions.
The VISY-View display is not suitable for outdoor installation. It is intended for
use within the VISY-X system only and the VISY-View unit must always be un-
damaged and clean. The safety instructions in this manual are labelled as follows:
If you do not observe these safety instructions, risk of an accident
exists or the VISY-View unit or the VISY-X system could be dam-
aged.
Helpful information that will guarantee proper function of the system or
facilitate your work.
3Structure and mode of operation
The VISY-View display stands on two nonslip feet in order to ensure unproblematic
operation of the buttons.
The front operator side is screwed at an angle with the feet so that user-friendly
operation is ensured. The operator interface comprises the display screen (1) and five
operator buttons (4–8). For the indication of operating statuses, the VISY-View unit is
equipped with two LEDs (2–3) (see Figure 1)

Page 6/34 VISY-View
Figure 1: VISY-View front
1 Display screen 5 Print out
2 Power LED 6 Return
3 Alarm LED 7 Cursor right / down
4 Alarm 8 Cursor left / up
3.1 Display screen
The display screen (1) represents four lines each with 20 characters. The different data
supplied from the control unit VISY-Command are generated in several submenus (see
chapter "Menu structure") and are shown on the display screen (1). Except for the main
and configuration menus the first line of the screen always shows the relevant tank
respectively probe. The other three lines are used to display the relevant tank data or
alarm messages. By using the two cursors you can recall the various menu functions to
the display.
There are two different cursor forms:
The Up-Down cursor „█“ which moves up and down on the left side in the
display screen and marks specific lines.
The Left-Right cursor "</>" which pages through the menu items at the
beginning of a line.
The cursor is moved using the operator buttons (7 and 8). Regular blinking of the Up-
Down cursor or changing between "<" and ">" indications show the properly running
program.
VISY-View is provided with a protective function that switches off the
display screen automatically following a configurable period of time (1–
60 minutes) without any inquiry via the operator buttons. This function
prevents the free view of data. The display screen is switched on again by
pressing any button.

VISY-View Page 7/34
3.2 Operation elements
3.2.1 On-Off switch
The on-off switch (9) is found on the underside of the device (see Figure 2). After
installing and turning on the device by using the on-off switch, the "Power" LED lights up
green (see section "Power LED" in this chapter).
Figure 2: VISY-View rear
3.2.2 Operator buttons
To page through the various menu items and call up the desired tank data, five operator
buttons (4–8) are available (see Figure 1):
Cursor left / up (8) depending on the cursor form with two functions:
1. By this button the Up-Down cursor is moved upwards. You can select a sub-
menu of the main menu or individual menu items of the submenu. If the cursor is
already positioned in front of the top line, you can go to the superimposed menu
by pressing this button.
2. The Left-Right cursor pages via this button through the various menu items of
the submenus.
Cursor right / down (7) depending on the cursor form with two functions:
1. By this button the Up-Down cursor is moved downwards. You can select a
submenu of the main menu or individual menu items of the submenu.
2. The Left-Right cursor pages via this button through the various menu items of
the submenus.

Page 8/34 VISY-View
Return button (6) has four functions:
1. With the Return button you can change between the two cursor forms.
2. In the main menu only the Up-Down cursor exists. Here you will use the Return
button to confirm the selection of a submenu.
3. In the alarm menu, only the Left-Right cursor exists. Here the Return button is
used to acknowledge an alarm message (the "!" will no longer be shown, the
red Alarm LED changes from flashing to constantly on and the buzzer is switched
off).
4. In case of acknowledged alarm messages, you can also use the Return button
to toggle between the indication "alarm status" and "alarm time".
Print (5)
This button can be used to initiate a data output operation via the printer. It is
possible to print out all data available in the submenus “Tank data”, “History”,
“Configuration” and maybe other submenus that might exist. More information
about the different printouts can be found in the chapters of the individual sub-
menus.
This operator button will only initiate printing operations if the
connected printer has been configured (see section "Printer" within
chapter "Configuration").
With the printer activated, the printing-out of alarm messages and filling
operations is carried out automatically in case of an alarm activation or a
filling operation.
A thermal printer with 32 columns and serial interface has to be used.
This printer is available as an optional equipment unit from FAFNIR.
Alarm (4)
By pressing this button, the alarm menu is called up. In the case of a new alarm,
the alarm initiating tank or probe appears on the display screen, (the red Alarm
LED flashes and the buzzer sounds). Pressing the button repeatedly will display all
the alarm messages that have not been acknowledged yet in successive order.
When all the alarm messages have been acknowledged with the Return button
(5) (see above), the red Alarm LED changes from flashing to permanently on and
the buzzer is switched off. To exit the alarm menu, press the alarm button once
again.

VISY-View Page 9/34
3.2.3 Key switch
Through connection 13 (see Figure 3) an accessible key switch can be mounted for use by
tanker drivers in case the filling station has already closed. Before refilling, a repetitive
turning of the key switch will bring the relevant data of all the tanks one after another
onto the display screen. Which three Tank data for a tank should be displayed are
selected in sub menu "Configuration" under "DspTruck" menu point (see section "Truck
display" in chapter "Configuration").
3.3 Power LED
The green Power LED (2) lights up as soon as the unit is connected to the power supply
system and is switched on by means of the on-off switch (9) (see Figure 2).
3.4 Interfaces
The VISY-View display is equipped with the following interfaces:
Figure 3: VISY-View interfaces
(10) Connection to appropriate power supply unit included in the scope of supplies
(11) Alarm outputs (11a = output 1, 11b = output 2)
The two alarm outputs can be configured so that a potential-free
transistor is closed for a specific alarm status (see chapter "Configura-
tion" and load limits in chapter "Technical data").

Page 10/34 VISY-View
When connecting the alarm outputs the correct polarities must be
observed ("+" for connections 1 or 3). If the poles are confused
then the contact is always closed!
(12) RS-485 interface for connection to the control unit VISY-Command
(13) Remote input for a key switch (see section "Key Switch" in this chapter) or input
for an external alarm (see section "Alarm input" within chapter "Configuration")
(14) Sub-D socket (9-pin) for connection to a printer
A thermal printer with 32 columns and serial interface has to be used.
This printer is available as an optional equipment unit from FAFNIR.
3.5 Alarm signalizing
The VISY-View display is equipped with a red Alarm LED (3) and a buzzer in order to
indicate alarms optically and acoustically. All detected alarms of the VISY-X system are
displayed. Alarms are either coming directly form connected probes or are the result of
exceeding or dropping below alarm thresholds of the control unit VISY-Command, set via
the software VISY-Setup.
The buzzer is switched off as soon as all alarms have been acknowledged in the alarm
menu, using the Return button (see section "Operator buttons" in this chapter). When
acknowledging an alarm the operator confirms that he/she has noticed the alarm. The
alarm menu can only be left after all alarms have been acknowledged. The volume of the
buzzer can be adjusted in the submenu "Configuration" (see section "Loudness buzzer"
in chapter "Configuration").
The alarm signalisation can be in one of the following states depending on the current
alarm situation:
Alarm signalisation Alarm situation
Alarm LED is flashing
Buzzer is on
There is at least one unacknowledged alarm, in this case it is
insignificant if the alarm is still active or not.
Alarm LED is on
Buzzer is off
There is at least one active alarm and all alarms have already
been acknowledged.
Alarm LED is off
Buzzer is off
There is no alarm.
When turning the device on the red Alarm LED lights up for approx. 1
second.
A new alarm is indicated by a flashing Alarm LED while an acknowledged
alarm is indicated by an Alarm LED that is constantly on.

VISY-View Page 11/34
4Putting into operation
In order to put the VISY-View display into service, proceed as follows:
(1) First choose which RS-485 interface of the control unit VISY-Command will be
used to connect the display VISY-View.
The display VISY-View is connected to the host interface of the VISY-Command
when no other host system (e. g. POS system) will be connected.
If the host interface of the VISY-Command is already used by another device
VISY-View must be connected to the extension interface of VISY-Command.
Figure 4: Interface connections of VISY-Command
(2) Use the configuration software VISY-Setup to configure the interfaces of VISY-
Command (see separate operating instructions for VISY-Setup). If the host inter-
face is used to connect VISY-View, enter "108" as host computer. If the exten-
sion interface is used, activate the function "External display" when using VISY-
Setup version up to V2.10, or activate the function "Extension interface" with
version V3.00 and higher.
The required protocol configurations for the VISY-View are described in
section "Protocol", chapter "Configuration".
(3) Connect the RS-485 interface of the VISY-View display to the RS-485 interface of
the control unit VISY-Command using the terminal clamps 5 (B) and 6 (A) of the
VISY-View (see rating plates in Figure 5 and Figure 6).
With devices from no. 525, terminal 7 can be used, if required, to apply
a cable screening or for potential equalisation with the RS-485 interfaces
of connected devices. Terminal 7 may not be connected to earth poten-
tial, as there is the danger of potential equalisation currents which are
too high and could damage the interface.

Page 12/34 VISY-View
Figure 5: Name plate up to serial number 524
Figure 6: Name plate beginning with serial number 525
(4) Connect a printer as required to the 9-pin D-Sub socket.
As printer is a thermal printer with 32 columns and serial interface
intended to be used. This printer is available as an optional equipment
unit from FAFNIR. The required printer configurations are explained in
section "Printer" of chapter "Configuration".
(5) Connect a key switch if required via remote input 13 (see Figure 3).
(6) Connect the VISY-View display via connection 10 (see Figure 3) and the enclosed
power supply unit to the power supply system.
Only use the power supply unit included in the scope of supplies
in order to connect the VISY-View display to the power supply
system.
(7) Turn the VISY-View display on using the on-off switch (9) (see Figure 2).
The VISY-View display is ready for operation now and can be configured as described in
the chapter “Configuration”

VISY-View Page 13/34
5Operation
From the main menu one of the submenus can be chosen. Normally the submenus “Tank
data", "History" and "Configuration" exist. If more submenus are available (e.g.
“Wireless”) this will be indicated by an down directed arrow „“ at the beginning of the
lowest line.
The menu "Wireless" is only available, if the connection of the measure-
ment sensors VISY-Stick to the control unit VISY-Command is done wire-
less.
For the use of the device some basic settings must be carried out via the submenu
"Configuration".
5.1 Configuration
The following configuration may be carried out on the VISY-View display:
Date and time
Language
Protocol
Printer
Loudness buzzer
Switching off – display screen
Disabling alarm signalisation
Alarm selection – alarm output 1
Alarm selection – alarm output 2
Electrical behaviour of alarm outputs
Resetting alarm outputs
Protection of configuration data
Alarm input
Number of history entries
Truck display
All settings (variable menu items), with exception of "Date and time", are
not permanently represented on the display screen but can be made visi-
ble by using the button
or the button
.

Page 14/34 VISY-View
The following described settings are configured within the menu “configuration”, which
you can enter as written below:
(1) In the main menu use the button or the button to select the submenu
"Configuration".
(2) Confirm your selection by pressing the Return button .
The submenu "Configuration" appears on the display screen. To quit the submenu, use
the button to move the Up-Down cursor to the top line and then back to the main
menu.
All changed configurations are stored upon leaving the submenu
"Configuration" and are kept also, if the device is switched off.
5.1.1 Date and time
In order to set the date and time, proceed as follows beginning in submenu "Configura-
tion":
(1) Use the button or the button to select line 1 with the date and time.
(2) Confirm your selection by pressing the Return button . At the left edge of the
display screen, the Left-Right cursor and an additional cursor will then appear in
the line. During the time adjustment procedure the clock remains stopped.
(3) Use the button or the button to position the additional cursor on the
number to be set. The cursor marks the adjustable time data continuously from
left to right.
(4) Press the Return button . At the left edge of the display screen the Up-Down
cursor will then appear.
(5) Use the button or the button to set the new time.
(6) Use the Return button to switch over to the Left-Right cursor. Repeat steps 3 to
6 as required until all the time input operations have been carried out.
If applicable repeat step 3 up to step 6, until all required changes are done.
(7) Use the button or the button to move the additional cursor to the left or to
the right out of the line. The time data are then accepted by VISY-Command.
If the extension protocol is used to communicate with VISY-Command
(VISY-View is connected to the extension interface of VISY-Command)
date and time cannot be changed via VISY-View.

VISY-View Page 15/34
5.1.2 Language
In order to set the language, proceed as follows once in submenu "Configuration":
(1) Use the button or the button to select the menu item Language
(2) Press the Return button . On the left side of the display screen the Left Right
cursor will now appear.
(3) Use the button or the button to set the desired language.
Due to the language selection, the representation of the date and time
as well as the decimal point or comma is automatically set according to
each language.
5.1.3 Protocol
In order to set the protocol, proceed as follows once in submenu "Configuration":
(1) Use the button or the button to select the menu item Protocol.
(2) Press the Return button . On the left side of the display screen the Left Right
cursor will now appear.
(3) Use the button or the button to set the desired protocol.
The following table shows which protocol must be set in accordance with the used VISY-
Command interface:
Connection to VISY-Command via Protocol to be set
Host interface Host-108
Extension interface Ext. Prot.
5.1.4 Printer
In order to set the printer, proceed as follows once in submenu "Configuration":
(1) Use the button or the button to select the menu item Printer.
(2) Press the Return button . At the left edge of the display screen the Left-right
cursor will then appear.
(3) Use the button or the button to activate the printer function.

Page 16/34 VISY-View
5.1.5 Loudness buzzer
In order to set the volume of the buzzer, proceed as follows once in submenu "Configu-
ration":
(1) Use the button or the button to select the menu item Buzzer.
(2) Press the Return button . At the left edge of the display screen, the Left-Right
cursor will then appear.
(3) Use the button or the button to adjust the desired length of buzzer tone.
With each press of a button the newly set length of buzzer tone is sounded by
the buzzer.
Please act with caution when disabling the buzzer as from a
safety point of view the signalisation of alarms is strictly required
in the majority of cases.
5.1.6 Switching off – display screen
In order to set a time period after which the display screen should automatically switch
off, proceed as follows once in submenu "Configuration":
(1) Use the button or the button to select the menu item DispOff.
(2) Press the Return button . At the left edge of the display screen, the Left-Right
cursor will then appear.
(3) Use the button or the button to adjust the desired period of time after
which the display screen is to be switched off (1–60 minutes).
5.1.7 Disabling alarm signalisation
By selecting menu item Alarm it can be configured if alarms are signalised or not.
Normally the alarm signalisation has to be enabled, especially if environmental sensors are
connected to the VISY-X system.
Under the following conditions it could however be reasonable to disable the alarm
signalisation:
there is more than one VISY-View connected to the VISY-Command control unit
and the alarm signalisation should only be done on one VISY-View
the VISY-View is used as a truck display only and alarms can not be acknowl-
edged by the user because of the mounting position (e.g. directly behind a glass
panel)
The following configurations are possible:
enabled alarms will be signalised
disabled alarms will not be signalised

VISY-View Page 17/34
In order to enable or disable the alarm signalisation, proceed as follows once in submenu
“Configuration”:
(1) Use the button or the button to select the menu item Alarm.
(2) Press the Return button . At the left edge of the display screen, the Left-Right
cursor will appear.
(3) Use the button or the button to enable or disable the alarm signalisation.
Please act with caution when disabling the alarm signalisation as
from a safety point of view the signalisation of alarms is strictly
required in the majority of cases.
5.1.8 Alarm selection – output 1 / output 2
By selecting AlrOutp1 and AlrOutp2 menu points the following alarm may be selected,
for which the corresponding alarm output is connected:
disabled no alarm selected, the output is always in the none-active state
ErrorGauge Sensor not connected or defective
ProdctXLOW Product level very low
ProductLOW Product level low
ProdctHIGH Product level high
ProdtXHIGH Product level very high
ProductAll Any alarm concerning the product level
Water HIGH Water level high
WaterXHIGH Water level very high
Ext Alarm External alarm (via key switch input)
All Alarms Any alarm listed above
In order to select the alarm, for which alarm output 1 or 2 should be connected, proceed
as follows once in submenu "Configuration":
(1) Use the button or the button to select the menu item AlrOutp1 or AlrOutp2
as required.
(2) Press the Return button . At the left edge of the display screen, the Left-Right
cursor will then appear.
(3) Use the button or the button to select the alarm to be connected to the
corresponding alarm output (1/2).
Alarms configured for the alarm outputs will only be handled when
coming from sensors of type VISY-Stick mounted in a tank. The alarm
outputs can not be activated by alarms coming from environmental sen-
sors. If alarm outputs for environmental sensors are also needed or a
higher voltage or current has to be switched the component VISY-
Output 4 has to be used.

Page 18/34 VISY-View
5.1.9 Electrical behaviour of alarm outputs
By selecting menu item OutLevel the electrical behaviour of the alarm outputs can be
configured.
The following configurations are possible:
NO Normally Open, in the none-active state the contact of the alarm output
is open
NC Normally Closed, in the none-active state the contact of the alarm
output is closed
In order to configure the electrical behaviour of the alarm outputs, proceed as follows
once in submenu “Configuration”:
(1) Use the button or the button to select the menu item OutLevel.
(2) Press the Return button . At the left edge of the display screen, the Left-Right
cursor will appear.
(3) Use the button or the button to select the desired function.
Selecting NC offers the advantage that a signalisation via the alarm
outputs is also done if the power to the VISY-View is interrupted.
5.1.10 Resetting alarm outputs
By selecting menu item OutReset it can be configured under which condition the alarm
outputs will be reset (set back to the none-active state).
The following configurations are possible:
ack. the alarm outputs will be reset after the user has acknowledged the
alarm
solved the alarm outputs will be reset after the alarm has been solved
In order to configure under which condition the alarm outputs will be reset, proceed as
follows once in submenu “Configuration”:
(1) Use the button or the button to select the menu item OutReset.
(2) Press the Return button . At the left edge of the display screen, the Left-Right
cursor will appear.
(3) Use the button or the button to select the desired function.

VISY-View Page 19/34
5.1.11 Protection of configuration data
By selecting menu item Protect you have the possibility to protect all configuration data
against manipulation. To change the status of the protection a 4 digit pass code of 3982
has to be used.
In order to enable/disable the protection of the configuration data, proceed as follows
once in the submenu "Configuration":
(1) Use the button or the button to select the menu item Protect. The current
protection status will be displayed.
(2) To be able to change the protection status press the Return button . On the left
side of the display screen the Left-Right cursor will now appear.
(3) Use the button or the button to select the value of the highest digit of the
pass code and confirm the selected digit value by pressing the Return button .
Now the next lower digit value can be input.
(4) Repeat step 3 until the complete 4 digit pass code has been entered. After all
digits have been selected and confirmed the Up-Down cursor will appear at the
left edge of the display screen.
(5) If the right pass code has been entered the protection status is changed from
enabled to disabled or from disabled to enabled.
When the protection function has been enabled a selected and protected
menu item is marked with a key on the left side of the display.
5.1.12 Alarm input
By selecting menu item AlrInput you have the possibility to configure the input of VISY-
View to be an alarm input for an external device. Normally the input is used to connect a
key switch that activates the Truck Display.
The following configurations are possible:
disabled the function alarm input is disabled, the input of VISY-View can be
used fort he function truck display
enabled NC the function alarm input is enabled, the input of VISY-View can be
used as alarm input for an external alarm, the alarm will be signal-
ised from the external device via a relay contact (or several relay
contacts wired in series) of type Normally Closed (NC)
enabled NO the function alarm input is enabled, the input of VISY-View can be
used as alarm input for an external alarm, the alarm will be signal-
ised from the external device via a relay contact (or several relay
contacts wired in parallel) of type Normally Open (NO)

Page 20/34 VISY-View
In order to enable or disable the function alarm input, proceed as follows once in the
submenu “Configuration”:
(1) Use the button or the button to select the menu item AlrInput. The current
configuration of the function alarm input will be displayed.
(2) Press the Return button . At the left edge of the display screen, the Left-Right
cursor will appear.
(3) Use the button or the button to select the desired function.
If the function alarm input is enabled this does automatically disable the
function Truck Display. The menu item DspTruck to configure the Truck
Display will show the text disabled.
An alarm signalised via the alarm input will show up as “External Alarm”
in the menu Alarm and on the automatic alarm printout (if a printer is
connected and configured).
If more than one alarm from external systems has to be handled (e.g. oil
layer and overfill alarm from multiple systems monitoring oil separators)
the component VISY-Input 8 should be used instead of the alarm input
of VISY-View. Using VISY-Input 8 has the advantage that detailed infor-
mation about the alarm reason and the system that has detected the
alarm are available in the menu Alarm.
5.1.13 Number of history entries
In order to change the number of filling operation data per tank that are shown in the
submenu History, proceed as follows once in the submenu “Configuration”:
(1) Use the button or the button to select the menu item History. The current
selection for the number of filling operation data will be displayed.
(2) To change the current configuration press the Return button . At the left edge
of the display screen, the Left-Right cursor will appear.
(3) Use the button or the button to select the desired number (1-5) of filling
operation data per tank.
Other manuals for VISY-X
4
Table of contents
Other fafnir Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Draper
Draper Expert 39591 instructions

Novus
Novus NHDR-4104-H1 quick start guide

Weidmuller
Weidmuller Power Monitor 51A quick guide

NUCLEONIX SYSTEMS PRIVATE LIMITED
NUCLEONIX SYSTEMS PRIVATE LIMITED RM704 instruction manual

Compu-Flow
Compu-Flow C6 Operator's manual

Amprobe
Amprobe AT-6000-R quick start guide