These instructions are written in accordance with the
installation guidelines of NFPA No. 72, STANDARD
FOR AUTOMATIC FIRE DETECTORS.
CAUTION
Detection Device Storage
DO NOT install this detection device until all
construction is completed.
DONOTstorethis detectiondevice whereit can
be contaminated by dirt, dust, or humidity.
DETECTOR PLACEMENT
Locate the 8842 on the ceiling, at least 4 inches from
the side walls. For an ideal, smooth ceiling condition,
place the detectors at a maximum center spacing of
50 feet (2500 square feet), 25 feet from side walls or
room partitions. For FM Approved installaltions this
detector has an RTI rating of QUICK, which allows a
maximum center spacing of 20 feet (400 square feet).
Locate detectors 10 feet from side walls or room
partitions.
Actualjob conditions andsoundengineering judgment
todeterminedetectorspacing.Considerenvironmental
factorsincluding ambient temperaturefluctuation, and
the nature of the fire hazard. Room or area
configuration and ceiling type (sloped or flat, smooth
or beamed) also dictates placement.
Shouldquestions ariseregarding detector placement,
follow the drawings provided and/or approved by
Faraday or by its authorized distributors. This is
extremely important!The detector placements shown
on these drawings were chosen after a careful
evaluation of the area being protected. Faraday's
extensive experience in design of the system assures
the best detector placement by following these
drawings.
Installation/Wiring Instructions
Model 8842 Thermal Detector
SPECIFICATIONS
Environmental
Temperature: 32OF (0OC) to 100OF (38OC).
Humidity: Up to 93% RH, non condensing
Air Pressure: No effect.
Alarm Temp: 135OF (57OC)
Electrical
Voltage: 16-27 VDC
Ripple: 3V peak-to-peak
SupervisoryCurrent: 110µA max
Alarm Current: 17-24mA
Start-up Time: 50 seconds max
DETECTOR WIRING
The 8842 should be connected as shown in Figure 1
usingtheseparatemounting base, Model 8853.Follow
the control panel wiring connection drawing installed
on the inside face of each control panel cover. See
8853 instruction, P/N 315-094193FA, for base
mounting. Duplicate wiring information is also in the
Installation, Operation, and Maintenance Manual
provided with every control panel. Note any
limitations on the number of detectors and
restrictions on the use of remote devices permitted
for each circuit.
INSTALLATION / REMOVAL OF DETECTOR
TO INSTALL:
• Align LED in detector with LED symbol on base
and insert detector into base.
• Rotate detector counterclockwise while gently
pressingonit until the detectordropsfullyinto base.
• Thenrotatethe detector clockwiseuntil it stopsand
locks in place. Insert optional locking screw (Order
P/N 446371).
TO REMOVE:
Loosen locking screw, if installed. Then rotate the
detector counterclockwise until stop is reached. Pull
detector out of base.
P/N 315-095429FA-3
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
Web: www.faradayfirealarms.com
LED INDICATOR OPERATION
The 8842 contains an LED indicator capable of
flashing either one of three distinct colors: green,
yellow, or red. Every seven seconds, the
microprocessor-baseddetector checks thatitscritical
electronics are operating.
Based on the results of these checks, the LED
indicator flashes as follows:
Color Condition
Flash
Interval
(Seconds)
Green Normal supervisory operation. 7
Yellow Detector requires service (repair)
or is operating beyond its
environmental specifications. 7-30
Red Alarm On steady
No
Flashes Detector is not powered, or
requires repair. -
Figure 1 Installation and Wiring Diagram for Conventional Detector
TESTING AND MAINTENANCE
TEST
Testing requires no test equipment. A green flash of
thedetectorLEDabouteverysevensecondsindicates
thatthe 8842is operating properly. Test asfrequently
as required by the Installation andTest Guidelines of
NFPA 72 DETECTORS.
CAUTION: UNDER NO CIRCUMSTANCES
ISTHEDETECTORHEADTO BEDISASSEMBLED.
NOFIELDREPAIRSSHOULD BEATTEMPTED.THE
DETECTORS ARE FACTORY REPAIRABLE ONLY.
DO NOT PAINT
The detector/base plastic is marked DO NOT PAINT.
This is intended to prohibit painting during routine
maintenanceoftheoccupancywhichcanaffectproper
operation of the detector.
TNEMPIUQELORTNOCELBITAPMOC
tnempiuqE reifitnedIytilibitapmoC gniriW/noitallatsnI snoitcurtsnI
104-WL5-AF799590-513N/P
)104-WL(A4-EZWL5-
AF810690-513N/P
)0007-/0006-CPM(50786-AF058430-513N/P reifitnediytilibitapmocehtsirebmunledomrotcetedehT.
P/N 315-095429FA-3
CAUTION:
1.Do not use looped wire under base terminal 5. Break wire
run to provide supervision of connection.
2.When a remote relay is used to control a critical system
function, the relay and its associated detector and optional
module(s) must be the ONLY devices on the initiating circuit.

Other Faraday Security Sensor manuals

Faraday 8710 User manual

Faraday

Faraday 8710 User manual

Faraday 8854 User manual

Faraday

Faraday 8854 User manual

Faraday 8854 User manual

Faraday

Faraday 8854 User manual

Faraday 8840 User manual

Faraday

Faraday 8840 User manual

Popular Security Sensor manuals by other brands

GE SB250 installation manual

GE

GE SB250 installation manual

UTC Fire and Security interlogix VE1120 Series Installation sheet

UTC Fire and Security

UTC Fire and Security interlogix VE1120 Series Installation sheet

Knauer Azura RID 2.1L instructions

Knauer

Knauer Azura RID 2.1L instructions

Smart Sensor AR8100 instruction manual

Smart Sensor

Smart Sensor AR8100 instruction manual

Bosch Blue Line Gen2 ISC-BPR2 installation guide

Bosch

Bosch Blue Line Gen2 ISC-BPR2 installation guide

Honeywell Miller EN 358 Instructions for use

Honeywell

Honeywell Miller EN 358 Instructions for use

Protekt AT 300 instruction manual

Protekt

Protekt AT 300 instruction manual

Tekmar 1873-ESM Installation and adjustment instructions

Tekmar

Tekmar 1873-ESM Installation and adjustment instructions

PRASTEL FT12 manual

PRASTEL

PRASTEL FT12 manual

Bticino HA4619 Instructions for use

Bticino

Bticino HA4619 Instructions for use

SwannOne Motion Sensor quick start guide

SwannOne

SwannOne Motion Sensor quick start guide

ISYGLT BW-03 Technical Data/Instruction Manual

ISYGLT

ISYGLT BW-03 Technical Data/Instruction Manual

DBI SALA EXOFIT NEX Series Specific instructions

DBI SALA

DBI SALA EXOFIT NEX Series Specific instructions

dehn PHE Instructions for use

dehn

dehn PHE Instructions for use

RKI Instruments 35-3001A-10 Operator's manual

RKI Instruments

RKI Instruments 35-3001A-10 Operator's manual

Carestream Focus 35C user manual

Carestream

Carestream Focus 35C user manual

AMC SMILE 18 manual

AMC

AMC SMILE 18 manual

sewerin rmld operating instructions

sewerin

sewerin rmld operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.