FATEK P2043S User manual

R
1
T
hank you for purchasing FATEK HMI. Before installing or operating the unit, pleas
e
r
ead this installation guide carefully to ensure correct use.
1
. Safety Precautions
(Read these precautions before use.
)
1.1 General
Unpack and check the delivery for transportation damage. If any damage o
r
deformation is found, please notify the supplier.
The supplier is not responsible for the disassembled, altered or modifie
d
device.
Never allow fluid or any conductive particles to enter into the HMI.
Otherwise, it may damage the HMI, cause fire or malfunction.
Only qualified personnel may install the HMI, perform maintenance an
d
inspection.
The liquid crystal inside the LCD panel is a hazardous substance. If the pane
l
is damaged, avoid contact with the leaked liquid crystal. If the liquid crysta
l
spills on clothing or skin, use soap and wash off thoroughly. In case of ey
e
contact the liquid, hold the eye open, flush with plenty water and get medica
l
attention as soon as possible.
Do not touch any terminals while the power is on. Otherwise, it may caus
e
injury due to electrical shock.
Disconnect the power supply before installing the HMI, do wiring operation
,
perform maintenance or inspection. Otherwise, it may cause damage o
r
electrical shock.
1.2 Installation
The installation may be carried out by qualified personnel only.
Install the HMI according to the installation procedures.
Check the power source voltage is within the specified range and the polarit
y
is correct before connecting the HMI.
Keep signal and power supply cables away from high-voltage, large-curren
t
carrying cables.
P2043S HMI Installation Guide

Recommended Prohibited
No Connected
HMI
unit
Other
equipment
GOOD BAD
DC24V
+
-
FG
DC24V
+
-
FG
2
Caution
Please use solid wires between 22AWG and 12AWG.
Maximum 300V and rated temperature to 105°C for input
power pins.
Caution
Make sure the HMI is properly grounded to prevent electrical
shock, fire or malfunction.
HMI unit and other equipment should have the same electrical groundin
g
(reference voltage level), otherwise communication errors may occur.
HMI
unit
Other
equipment
1.3 Operation
Do not use sharp objects or excessive force to press the touch screen. This
may damage the touch screen.
Do not use the output signal of the device as any safety function or system
emergency stop. It may result in personal injury or equipment damage if a
malfunction of the touch occurs.
1.4 Maintenance and Service
The agreed guarantee applies.
Only qualified personnel should make repairs and perform maintenance.
Disconnect the device from the power supply before carrying out cleaning or
maintenance.
Clean the front panel with a soft cloth and mild detergent.
Please use original replacement spare parts or accessories.

3
3
456
1
2
W
H
D
W 128.0 mm
H 102.0 mm
D 38.1 mm
2.
①
②
③
④
⑤
⑥
Power Indicator Light
Mounting Hole
Power Connector
COM1/COM2 DB-9
Male Connector
USB Connector
Mini USB Connector
Part Names and Dimensions

4
3. Specifications
Model
P2043S
UL 61010-1
Technical
Consideraon
Type of item tested
Control
Product Descripon
Operator Panel
Connecons to mains
supply
Permanent
Overvoltage category
II
Polluon degree
2
Means of Protecon
Class III
Environmental condions
Operating Temp. 0~50°C
Storage Temp. -20 ~ 60℃
For use in wet locaons
No
Equipment mobility
Built in
Operang condions
Continuous
Overall size
128.0 x 102.0 x 38.1 (mm)
Weight 215 (g)
Marked degree of
protecon
Front panel: IP65 / Rear Case: IP20
to IEC 60529
Type 1 to UL 50E
Equipment classificaon
Industrial, Professional, Commercial
Equipment class
Class III
Equipment type
Permanently connected, Fixed
I/O Port
Serial 1
Connector: D-Sub 9-Pin
COM1: RS-232 (TXD, RXD)
COM2: RS-422/485
Choose one for usage
Serial 2
---
LAN
---
USB USB2.0 Type-A (Host)x1
USB2.0 Type mini-B (Device)x1
Micro SD
---
Audio ---
PLC Extension ---
Terminaon
Switch
---
Power
Power Input
24VDC±20%
Consumpon
280mA@24VDC
Insulaon
50MΩat 500VDC
Environment
Relave Humidity
10%~90%@ 40°C (non-condensing)
Withstand Voltage
AC500V/20mA/1 Min. (between charger & FG terminals)
Vibraon
5 to 9Hz Half-amplitude: 3.5mm
9 to 150 Hz Constant acceleraon: 19.6m/s2 (2G)
3 direcons of X, Y, Z: 10mes (IEC61131-2 complaints)
Noise Suppression 1000Vp-p, width 1us, rising me 1ns
Grounding Resistance
Below 100Ω
Dimension
Cut-out
118.5 x 92.5 (mm)

4.
FATEK HMI x1
Hook and Screw x4
A4 Double-side Installation Guide
x1
Power Connector x1
5.
Push the HMI into the cotout until the
waterproof ring contacts the plate.
Insert a hook into each mounting hole
on the HMI, and then tighten the
screws evently with a moderate torque.
Failure to tighten the screws may
cause the HMI to fall, malfunction or
short-circuit. Excessive tightening may
cause deformation. The necessary
torque is about 0.16N∙m.
5
Unpacking the Unit
Installation Procedures

6.
Be sure to connect the ground FG
terminal to a class-3 ground (Ground
resistance should not exceed 100Ω).
Try to make the ground wire as short
as possible
7.
DB- 9
Male Connector
PIN#
COM1
[RS-232]
COM2
[RS-422]
COM2
[RS-485]
1
NC
*1
TX+
DATA+
2
RX
NC
NC
3
TX
NC
NC
4
NC
RX+
NC
5
GND
GND
GND
6
NC
TX-
DATA-
7
NC
NC
NC
8
NC
NC
NC
9
NC
RX-
NC
*1 NC: No Connection
6
DC24V
+
-
FG
Power Connection
Pin-out of COM Ports
Use 22–12 AWG (0.5–1.5 mm ) wire
for the power connections.
2

TEL
:+886-2-2808-2192
FAX :+886-2-2809-2618
E-mail
Website :
www.fatek.com