MODENA 80 E
19
3.05 Connecting the central heating and domestic hot water circuits
Connect to the relevant connections as indicated in fig. 1. Connect the pressure relief valve discharge pipe
(15mm) to the outside of the building, where possible over a drain. The discharge must be such that it will not
be hazardous to occupants and passers-by or cause damage to external electric components or wiring. The
pipe should be directed towards the wall. To ensure long life, the heating circuit should be correctly sized and
fitted with all the controls necessary to ensure correct functioning and operation. The differential between
the boiler flow and return pipes should not be more than 20°C. You are advised not to use the boiler with
return temperatures of less than 50°C in order to prevent patches of condensation forming and having a
corrosive effect on boiler components.
3.06Boiler water characteristics
If the water is harder than 18clarke degrees, the water used should be treated to avoid possible scale in the
boiler caused by hard water or corrosion by aggressive water. It should be remembered that as a result of its
low thermal conductivity, even scale of just a few millimetres thickcan lead to considerable overheating of
the boiler walls, resulting in serious problems.
IT IS ABSOLUTELY VITAL THAT THE WATER USED IS TREATED IN THE FOLLOWING CASES:
a) Extensive systems (containing large quantities of water);
b) Frequent additions of water to top-up the system;
c) Domestic hot water circuits
If the system requires partial or total emptying, you are recommended to refill it with treated water.
3.07Filling
When cold, system pressure should be about 1 bar. If while running venting off of air dissolved in the water causes
the pressure of the central heating system to drop below the minimum level described above, the user must utilise
a filling loop to bring it backto the original value. During operation, water pressure in the boiler when hot should
be about 1.5 - 2 bars. After filling, always close and disconnect the filling loop.
Note -If there is a possibility of air pockets forming in certain points of the central heating system flow and return
pipes, you are recommended to fit an air vent valve at these points.
Note -When the boiler is installed below the level of the central heating a system, single checkvalve should be
fitted in the flow to prevent gravity circulation around the heating system.
3.08Gas connection
Gas connection should be carried out using a rigid pipe.
Theflowatthegasmetershouldbesufficientforthesimultaneoususeofallappliancesconnectedtoit.Connectthe
gas supply to the boiler according to current regulations. The diameter of the gas tube leaving the boiler is not the
determiningfactorinchoosingthediameterofthepipebetweentheapplianceandthemeter.Thismustbeselected
in relation to length and pressure drop and in any instance should not be less than 22mm.
The whole ofthe gas installation including the meter should be inspected and tested for soundness and
purged in accordance with BS6891-1988.
N.B. -The filling loop will be fitted by the installer in accordance with water by laws, at the time of installing
the system. It is NOTa part ofthe boiler.
3.09Electrical connection
The boiler must be connected to a single phase 230 V50 Hz electricity supply with a 3Amax. fuse and a bipolar switch with
contact opening of at least 3mm fitted between the boiler and the electricity supply. The boiler must always be connected to
an efficient earth installation. Under the electrical box, there is a 3pole terminal board for connecting the boiler to the mains
(230V50 Hz) anda 2 pole boardforconnectinga roomthermostat (RT).To connect,undo the screwsfixing theterminal board
boxandconnectthewires,ensuringcorrectpolarityoftheterminals.Itshouldbenotedthatthereislowvoltage(24V)between
the room thermostat contacts. When the boiler is connected to an electricity main, it is essential TOOBSERVE CORRECT
POLARITIES (LIVE: brown cable, NEUTRAL: blue cable, EARTH: yellow-green cable).
All wiring must conform to current I.E.E. regulations.