a rate of 1-3 inches (2.5-7.5cm) per second.
3 Once the SCL2 indicates a change in concen-
tration (audible beep), note the spot on the
lineandkeepthetipmovingpastthepotential
leak to refresh the air space within the SCL2
with clean air. (Note: If the SCL2 wand moves
throughaveryhighconcentrationofrefriger-
ant, you may need to use it in fresh air for 4
seconds before moving to step 4 in order to
clear the refrigerant within the SCL2.)
4 Return the tip back across the spot rst in-
dicated. When the SCL2 indicates a second
change, note the spot on the line.The source
oftheleakwillbe near the midpoint between
the two noted spots of indication.
5 Very high concentrations of refrigerant can
cause an overload which can take a few sec-
onds to clear.
Quick Start
1 Charge the SCL2 (see charging instructions
on page 14 for details).
2 Power on SCL2 and allow a 30 second warm
up to complete in well ventilated ambient air
away from suspected leak.
3 Select the sensitivity using the L/M/H button.
4 Point the tip of the wand at suspected leak
locations(seeFindCO2Leakssectionon page
4 for details).
Quick Tips
1 Keep the wand tip moving slowly past sus-
pected leak locations.
2 Once a leak is detected, sweep the wand back
over to pinpoint.
3 To pinpoint larger leaks adjust sensitivity.
Certifications
C-Tick (N22675)
CE
WEEE
RoHS Compliant
Meets SAE Standard
Description
The SCL2 is a portable CO2 (R-744) leak
detector with a superior combination of
sensitivity, speed, sensor life, battery life,
portability, and ease of use.
Find leaks on commercial refrigeration
systems, restaurant soda machines, or any other
system using R-744. Pinpoint tiny leaks in high
concentration CO2 environments with ease.
Gas is pumped through the tip of the wand
into the sensor within the SCL2 body. The sensor
detects changes in concentration, not absolute
concentration, allowing the SCL2 to dierentiate
CO2 concentrations higher than concentrations
normally found in ambient air.
The SCL2 detects leaks as small as 6 grams/
yr (0.2 oz/yr). The SCL2 has three sensitivity
settings to keep false triggering to a minimum.
A quick and automatic 30 second self-calibration
upon power-up ensures optimal performance.
The SCL2 comes with a wall and car charger
for its ultra-compact lithium-ion battery
which powers the SCL2 for 8hrs of continuous
operation before a recharge is needed. That's
long enough to last your entire workday.
A built-in replaceable lter blocks moisture
and harmful particulates.
Find CO2 Leaks
Keep the SCL2 away from any areas of
potential refrigerant leakage until the warm-up
and calibration period is over.The warm-up and
calibration sequence lasts about 30 seconds
after powered on. Allow the SCL2 to fully warm-
up before searching for CO2 leaks to avoid false
triggering.The meter defaults to high sensitivity.
The most likely points for refrigerant leaks
are at the soldered joints in refrigerant lines
and changes in the cross section or direction
of these lines.
The SCL2 detects changes in concentration of
CO2, not the absolute concentration.This helps
you to detect CO2 leaks in places that may have
lots of CO2, such as a refrigerator leaking into
an enclosed space. Because you are detecting
a change in concentration, you should use the
"double-pass" method detailed below.
1 Thetipof thewand shouldbe closetotheline.
You may need to be within 1/4” (0.63cm) of
a small leak to detect it. In this case, using a
secondhandtoguidethetipalong refrigerant
lines may be helpful. See Figure 1.
2 Keep the tip moving along refrigerant lines at
Fieldpiece
Carbon
Dioxide
Leak
Detector
OPERATOR'S
MANUAL
Model SCL2
Buttons
ON/OFF Protection
To turn on/o the SCL2 press and hold
SCL2
Carbon Dioxide
Leak Detector
SENSITIVITY
H
M
L
PEAK
LOW-BATT
PRESS FOR
1 SECOND
BATTERY
CHECK
ON/OFFMUTE
PEAK
L/M/H
for one second.This slight delay protects against
your meter turning on when stored. If you forget
to turn it o it will turn o automatically in 10
minutes.
L/M/H Sensitivity
Setthesensitivitylevelbypressing
SCL2
Carbon Dioxide
Leak Detector
SENSITIVITY
H
M
L
PEAK
LOW-BATT
PRESS FOR
1 SECOND
BATTERY
CHECK
ON/OFFMUTE
PEAK
L/M/H
.Low(L),medium(M),
or high(H) sensitivity will be indicated by their respective LED.
The higherthe concentration of refrigerantin the ambientair,
thelowerthe sensitivitysetting should be tominimize false trips.
Mute and Battery Check
Pressing
SCL2
Carbon Dioxide
Leak Detector
SENSITIVITY
H
M
L
PEAK
LOW-BATT
PRESS FOR
1 SECOND
BATTERY
CHECK
ON/OFFMUTE
PEAK
L/M/H
toggles the sound of the SCL2
on and o. In addition, holding the MUTE button
for one second will display the remaining
percent of battery charge on the LED bar graph.
Peak Mode
To activate Peak mode, press
SCL2
Carbon Dioxide
Leak Detector
SENSITIVITY
H
M
L
PEAK
LOW-BATT
PRESS FOR
1 SECOND
BATTERY
CHECK
ON/OFFMUTE
PEAK
L/M/H
. When
activated, the highest LED will stay lit when
gas is detected. The Peak function holds the
highest change in concentration sensed while
continuing to detect leaks. This is useful when
detecting around corners when the LED bar
graph is not visible. To deacviate, press PEAK
button again. The last peak measured will be
cleared.
Turbo Mode
The TURBO function is an additional 4th
sensitivity that pushes the SCL2 to it highest
possible sensitivity. This feature is activated by
pressing
SCL2
Carbon Dioxide
Leak Detector
SENSITIVITY
H
M
L
PEAK
LOW-BATT
PRESS FOR
1 SECOND
BATTERY
CHECK
ON/OFFMUTE
PEAK
L/M/H
four times in succession, and can
only be activated while on the high(H) sensitivity
level.
When in TURBO mode the rst green LED on
SCL2 will strobe, and the audio detection sound
will be a solid tone.
To exit the TURBO mode, press the PEAK
button again four times in succession, or switch
from high(H) to one of the other sensitivities
levels.
Beware: While in TURBO mode the SCL2 is
extremely sensitive and will more easily trigger
on abrupt or violent motions as well as very
small changes in refrigerant levels. Handle with
care when in TURBO mode.
LED Indicators
LED Bar Graph Display
The eight segment LED display indicates the degree of change
in refrigerant concentration. As the concentration of refrigerant
in the air increases, so does the number of lit bars on the display.
Low-Batt LED
1 While detector is in use, the Low-Batt LED will turn solid red
indicating approximately 1 hour of battery life left.
2 While detector is charging, the Low-Batt LED will ash red on
and o indicating the meter is charging.
3 When detector is fully charged, the Low-Batt LED will turn o
indicating the meter is fully charged.
H/M/L LEDs
High (red), medium (amber) , or low (green)
LED will turn solid indicating what sensitivity
is selected.
Peak LED
Light solid amber when Peak mode is
activated.
SCL2
Carbon Dioxide
Leak Detector
SENSITIVITY
H
M
L
PEAK
LOW-BATT
PRESS FOR
1 SECOND
BATTERY
CHECK
ON/OFFMUTE
PEAK
L/M/H
SCL2
Carbon Dioxide
Leak Detector
SENSITIVITY
H
M
L
PEAK
LOW-BATT
PRESS FOR
1 SECOND
BATTERY
CHECK
ON/OFFMUTE
PEAK
L/M/H
SCL2
Carbon Dioxide
Leak Detector
SENSITIVITY
H
M
L
PEAK
LOW-BATT
PRESS FOR
1 SECOND
BATTERY
CHECK
ON/OFFMUTE
PEAK
L/M/H
!
WARNING
!
DO NOT operate the SCL2 in the presence
of gasoline, natural gas, propane, or in other
combustive atmospheres.
DO NOT use the SCL2 without the proper
lter correctly installed.
99 Washington Street
Melrose, MA 02176
Phone 781-665-1400
Toll Free 1-800-517-8431
Visit us at www.TestEquipmentDepot.com

11
16
12
17
13
18
14
19
15
20
Specifications
Sensing element:Enhanced infrared photo optics
Sensor life: Up to 10 years
Refrigerants: R-744 Carbon Dioxide (CO2)
Sensitivity Levels:
High: Up to 6 grams/yr (0.2oz/yr)
Medium: Up to 14 grams/yr (0.5oz/yr)
Low: Up to 28 grams/yr (1oz/yr)
Response time: 1 second
Recovery time: ~4 seconds
Auto o: 10 minutes after no activity
Battery: 3.7VDC(nominal), rechargeable lithium
ion user-replaceable battery.
Battery life: 8 hours continuous use prior to
needing a charge. Degradation (30%) after
500 charge/discharge cycles or two years,
whichever comes rst.
Low battery LED: Lights when approximately 1
hour of battery life remains.
Charge time: Less than 4 hours (either charger)
Operating environment: 32ºF (0°C) to 104ºF (40°C)
at <75%RH (non-condensing)
Storage environment: <80%RH meter and batt.
For 80% battery recovery:
-4ºF (-20°C) to 140ºF (60°C) less than 1 month
-4ºF(-20°C)to113ºF (45°C) lessthan 3months
-4ºF (-20°C) to 68ºF (20°C) less than 1 year
Included Accessories
Use model RRE2 when detecting in tight
spaces, such as through a condenser grille.
Model RFE2 extends the wand to 25.5” (65cm).
The blow molded case, model holds accessories
and chargers.
All accessories shown are included with the
SCL2.
Lithium Battery Care
The SCL2 contains a very powerful lithium
ion battery. For a long battery life and safe
operation, you must observe the following:
Cautions
1 Do not expose the battery to temperatures
higher than 140ºF (60°C).
2 Donot charge the battery in or nearby heated
places, such as re, hot vehicles, or direct
sunlight.
3 Do not solder directly onto the battery.
4 Do not expose the battery to direct impact or
throw it.
5 Do not get the battery wet.
6Do not deform or pierce the battery in any way.
7 If there is any battery leakage, do not touch
the battery. In the case that electrolyte gets
into the eyes, ush with fresh water, do not
rub, and see a physician immediately.
8 Replace immediately if there is any deformity,
badsmell,colorchange,orotherabnormality.
9The battery is user-replaceable and can be
purchased at most electronic stores. The fol-
lowing batteries are known to be compatible
withtheSCL2:FujiFilm:NP-120,PENTAX:DLI-7,
RICON: DB-43
Charging
Two chargers are included with the SCL2.
The AC charger plugs into a wall outlet and the
car charger plugs into a car cigarette lighter DC
plug.
1 The battery is partially charged when pack-
aged. Fully charge the battery before rst use.
2 The LOW-BATT LED will light red when the
battery is low.
3 To recharge the SCL2, plug one end of the
charger into the top of the SCL2 and the
other into the power source. LOW-BATT
will blink while charging until the battery is
fully charged. When the SCL2 battery is fully
charged, LOW-BATT turns o.
4Charge within operating environment speci-
ed in the Specications section on page 11.
5Avoid frequent full discharges. Several partial
dischargeswithfrequentrechargesarebetter
for lithium-ion batteries. Unlike nickel-based
batteries they have no charge memory, and
donotneedtobe dischargedbeforecharging.
Storage
The battery should have a 40%-50% charge
during prolonged storage of a month or longer.
See Specications section in this manual for
proper storage environment.
Battery life is dramatically reduced if the
battery is stored fully charged and/or at high
temperatures.
Maintenance
Clean the exterior with a dry cloth. Do not
use liquid.
Filter Assessment & Replacement
The filter blocks moisture and other
contaminants from the sensor. When it gets
wet, it constricts ow of air and will have to be
replaced. Unscrew the sensor tip and replace
the white filter so that the rounded end is
closest to the tip of the wand. Use only the
Fieldpiece supplied lter.
You can order extra bags of replacement
parts (Part# RFL2) from your local distributor.
Limited Warranty
This meter is warranted against defects
in material or workmanship for one year
from date of purchase from an authorized
Fieldpiece dealer. Fieldpiece will replace or
repair the defective unit, at its option, subject
to verication of the defect.
This warranty does not apply to defects
resulting from abuse, neglect, accident,
unauthorized repair, alteration, or unreasonable
use of the instrument.
Any implied warranties arising from the sale of
a Fieldpiece product, including but not limited
to implied warranties of merchantability and
tness for a particular purpose, are limited to
the above. Fieldpiece shall not be liable for loss
of use of the instrument or other incidental or
consequential damages, expenses, or economic
loss, or for any claim of such damage, expenses,
or economic loss.
State laws vary. The above limitations or
exclusions may not apply to you.
Obtaining Service
Email Fieldpiece warranty department at
price repair service. Send check or money
order made out to Fieldpiece Instruments for
the amount quoted. If your meter is under
warranty there will be no cost for the repair/
replacement. Send your meter, freight prepaid,
to Fieldpiece Instruments. Send proof of date
and location of purchase for in-warranty service.
The meter will be repaired or replaced, at the
option of Fieldpiece, and returned via least cost
transportation.
For international customers, warranty for
products purchased outside of the U.S. should
be handled through local distributors. Visit our
website to nd your local distributor.
More from Fieldpiece
Model SMAN460
Wireless 4-Port Manifold
with Micron Gauge
Model SDP2
Dual In-duct Psychrometer
Model RRE2
9" (23cm) Needle tip probe
Model RFE2
9" (23cm) Flex extension
Model ADMK3
Blow molded case
Model RCA2
Car Charger
Model RWA2
Wall Charger
Model RFL2
Replacement lters (10)
and O-rings (5)
80
80
Test Equipment Depot - 800.517.8431 - 99 Washington Street Melrose, MA 02176
TestEquipmentDepot.com
Other Fieldpiece Security Sensor manuals
Popular Security Sensor manuals by other brands

Eberle Design
Eberle Design LMA-1200-120 operating instructions

Tyco
Tyco Visonic TOWER-20 PG2 installation instructions

LST
LST OH-13001 Specification sheet

Bosch
Bosch D-tect 120 Professional instructions

PCB
PCB 2302-01A Installation and operating manual

B.E.G.
B.E.G. LUXOMAT net PD4N-LTMS-RR Installation and operating instruction