  9. Fike Twinflex Hipoint User manual

Fike Twinflex Hipoint User manual

Document No. 26-0378 Issue 13
Subject to change
This document is only intended to be a guideline and is not applicable to all
situations. Information subject to full disclaimer at www.ke.com/disclaimer
INSTALLATION AND MAINTENANCE
INSTRUCTIONS
http://www.ke.co.uk/
resource-downloads/twinex/
302-0004 TWINFLEX HIPOINT
General Description
The Twinex Hipoint unit allows for audible indication when the system enters an
alarm condition. This device is compatible with the Twinex 2-wire range of Fire
Alarm equipment and comprises a 2-wire zone-powered sounder. This device may be
installed on the same zone as the Multipoint detector/sounder and associated Twinex
devices.
Before Installation
The Sounder must be installed in compliance with the control panel installation manual.
The installation must also meet the requirements of any local authority.
Spacing
Fike recommends spacing of sounders in accordance with any local authority.
Device Installation
Fix the back box in a suitable position using at least two screw holes/slots, remembering to allow enough cable length
for installation. All wiring must be installed in compliance with the recommendations laid out by any local authority as
well as any special recommendations documented in the control panel installation manual.
Connections
The cabling used should be of a 2-core 1.5mm2 screened, re resistant type (e.g. FP200
or equivalent), and is to be wired in the form of a screened 2-core radial circuit (with no
spurs) from the control panel, terminating at the last (“End of Line”) device.
No screen connection is allowed for within the device. Incoming and outgoing cable
screens must therefore be connected through using a suitable connector. It is important
to maintain the screen continuity in order to protect against data corruption from
interference.
Once all testing has been carried out on the cabling and continuity & insulation has been
proven, the Hipoint front may be tted. The Hipoint front is tted by locating the rubber
seal in the groove on the back box and then pushing the front unit gently home. The four
xing screws may then be tightened as required.
Remember that the device at the end of the line must have its EOL signal activated using the relevant DIL
switch. Do not use a resistor or capacitor (or another manufacturer’s End of Line device) as the end of line, as
this may prevent correct operation of the zone.
Document No. 26-0378 Issue 13
Subject to change
Twinex Hipoints can be mixed on the same zone as other types of Twinex device
(eg. Twinex Multipoint Detectors). The above diagram shows how to make the
zone positive, zone negative and screen connections between the control panel
and Twinex Hipoints. Refer to the instruction leaets supplied with other Twinex
devices for their equivalent wiring/terminal labelling details.
Please note that the cable screens should only be connected to each other (and not to the building earth) at the Hipoints.
The cable screen is connected to earth at the panel end only, via the zone “SCRN” terminal (or EARTH terminal on the
Twinex V3 2/4/8 Zone panels).
DIL SWITCH SETTINGS
1 2 3 4
End of line Enabled ON
Disabled OFF
Sound Levels High ON
Low OFF
Sound Patterns Sound OFF ON ON
Dual Tone UK Evacuate – 800 & 970 Hz ON OFF
Slow Whoop Up - 500 to 1200 Hz sweep up OFF OFF
Dual Tone French Warble – 440 & 550 HZ OFF ON
Technical Data
Dimensions Width x........................................................................... 123mm
Height............................................................................. 130mm
Depth.............................................................................. 101mm
Operating Temperature ....................................................................................... -10oC to +50oC
Voltage Ranges DC Output from Mains Powered Panel.......................... 25.5 to 35V DC
DC Output from Battery Powered Panel........................ 20 to 26V DC
Operating Current (Typical) Quiescent........................................................................ 185 uA
End of line ON if applicable............................................
(in addition to Quiescent) 175 uA
Alarm Sounding - Sounder High.................................... 14.5 mA
Alarm Sounding - Sounder Low..................................... 12.6 mA
Loading Units V3 Panel Pro/Pro2Panel
Max Loading Units per zone.......................................... 27 SLU 160 DLU
Sounder High................................................................. 2.5 SLU 14.5 DLU
Sounder Low.................................................................. 2.0 SLU 13.0 DLU
Sounder High................................................................. 90+ dB(A)
Sounder Low.................................................................. 65+ dB(A)
Flammability ....................................................................................... UL94-V2
IP Rating ....................................................................................... IP 55*
Part Code ....................................................................................... 302 0004
* Not EN54-3 compliant
SWITCH OFF
SWITCH ON
1 2 3 4
O N
Fike Safety Technology Ltd
Unit 31, Springvale Industrial Estate
Cwmbran
NP44 5BD
Tel: 01633 865 558 | Email: fstinfo@ke.com Document No. 26-0378 Issue 13
Subject to change
2831
Fike Safety Technology Ltd
Unit 31, Springvale Ind. Est.
Torfaen, NP44 5BD
11
DoP-302-0004
EN54-3: 2001 +A1: 2002 +A2: 2006
Sounder Technical Data: See 26-0747
302-0004
Intended for use in the re detection and re alarm
Systems in and around buildings
Essential characteristics Performance
Nominal activation conditions/Sensitivity, response delay (response time)
and performance under re conditions Pass
Operational reliability Pass
Tolerance to supply voltage Pass
Durability of operational reliability and response delay, Temperature
resistance Pass
Durability of operational reliability, Vibration resistance Pass
Durability of operational reliability, Humidity resistance Pass
Durability of operational reliability, Corrosion resistance Pass
Durability of operational reliability, Electrical stability Pass
Performance under re conditions Pass
Durability of operational reliability, Resistance to ingress Pass
Technical Support
Contact your supplier for technical support on this
product.
Due to the complexity and inherent importance of
a life risk type system training on this equipment is
essential, and commissioning should only be carried
out by competent persons. Fike cannot guarantee the
operation of any equipment unless all documented
instructions are complied with, without variation.
Fike’s policy is one of continual improvement and the
right to change a specication at any time without
notice is reserved. Whilst every care has been taken to
ensure that the contents of this document are correct
at time of publication, Fike shall be under no liability
whatsoever in respect of such contents. E&OE

This manual suits for next models

1

Other Fike Fire Alarm manuals

Fike Quadnet User manual

Fike

Fike Quadnet User manual

Fike DUONET User manual

Fike

Fike DUONET User manual

Fike 313-0001 Sita Soundpoint User manual

Fike

Fike 313-0001 Sita Soundpoint User manual

Fike CIE-A-200 User manual

Fike

Fike CIE-A-200 User manual

Fike 68-140 User manual

Fike

Fike 68-140 User manual

Fike FCP-300 User manual

Fike

Fike FCP-300 User manual

Popular Fire Alarm manuals by other brands

Siemens CERBERUS AlgoRex Series Installation guidelines

Siemens

Siemens CERBERUS AlgoRex Series Installation guidelines

Global Fire Equipment ORION EX MINI-REP installation manual

Global Fire Equipment

Global Fire Equipment ORION EX MINI-REP installation manual

EMS FIRECELL Setup guide

EMS

EMS FIRECELL Setup guide

Notifier 002-439 Installing

Notifier

Notifier 002-439 Installing

Channel Safety Systems Rapidfire instruction manual

Channel Safety Systems

Channel Safety Systems Rapidfire instruction manual

Incite Fire EK-WL8-OS-AU installation guide

Incite Fire

Incite Fire EK-WL8-OS-AU installation guide

Siemens FP-11 FirePrint introduction

Siemens

Siemens FP-11 FirePrint introduction

Honeywell Silent Knight SK318PT Installation and operation guide

Honeywell

Honeywell Silent Knight SK318PT Installation and operation guide

Secutron MRM-800 Series quick start guide

Secutron

Secutron MRM-800 Series quick start guide

Simplex TrueAlarm 4008-9101 Installation, Programming and Operating Instructions

Simplex

Simplex TrueAlarm 4008-9101 Installation, Programming and Operating Instructions

Cooper Notification ET90-24MCWH Series installation instructions

Cooper Notification

Cooper Notification ET90-24MCWH Series installation instructions

Tecnoalarm Tecnofire TFA2-596 Installation

Tecnoalarm

Tecnoalarm Tecnofire TFA2-596 Installation

Faraday MPC-6000 Programming manual

Faraday

Faraday MPC-6000 Programming manual

ESP SCP-1 manual

ESP

ESP SCP-1 manual

Cooper Notification E60H-24MCCH installation instructions

Cooper Notification

Cooper Notification E60H-24MCCH installation instructions

E2S D1xB2XH1 instruction manual

E2S

E2S D1xB2XH1 instruction manual

Potter FFT-1000 installation manual

Potter

Potter FFT-1000 installation manual

E2S IS-CP4B-PB instruction manual

E2S

E2S IS-CP4B-PB instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.