
17
Permanent connection (hard wiring)
Units may be hard wired to the power supply.
Theinstaller must provide approved flexible steel conduit,
maximum6ft(1.8m) long. Locate the terminal block on
therear of the unit and remove access cover.
The strain relief bracket orientation must be switched in
order to accommodate for a permanent wiring connection.
This is done by the following:
1 Remove the 4 screws on the bracket.
2 Re-secure bracket with the four screws so that the
1 1/8" (29mm) smaller opening is orientated over the
opening of the back panel.
RDV3 models
Dual Fuel models must be connected to the power supply utilizing one of the following methods. For all methods of connection, the length of the cord or conduit/wiring must allow the
unit to be slid completely out of the cabinet without having to unplug or disconnect the unit from the power supply. Recommended minimum free length of cord or conduit is 4ft (1.2m).
Electricalinstallations and grounding must be in accordance with all local codes and ordinances, and/or the National Electric Code, as applicable.
1 2 3
terminal block
strain relief bracket
ELECTRICAL CONNECTION
zThe conduit must be installed to the terminal block
using an approved conduit connector. The free end
of the conduit must be connected to a junction box
provided in the electrical supply zone.
zMount a strain relief (not provided) into the 1 1/8"
(29mm) diameter hole located below the terminal block.
Wiring for the unit is to be brought into the terminal
block through the conduit and through the strain relief.
The ends of the wiring must have 1/4" faston closed
loop lugs attached. Make suitable connections to the
terminal block provided.
zzSee 4-wire and 3-wire connection on the right.
zzInstaller – show the owner the location of the circuit
breaker. Mark it for easy reference.
Ferrites
Green
Flex
BlackRed White
Ferrites
Green
Flex
BlackRed White
4-Conductor cord
Normally, a unit must be connected to the power
supply with a 3-pole, 4-conductor cord kit rated
125/250 volts, 50 amperes, and marked for use with
ranges.
The cord kit must be attached to the range terminal
block with a strain relief which will fit a 1 – 3/8" (35mm)
diameter hole. If not already equipped, the cord
must also have 1/4"(6mm) faston closed-loop lugs
attached to the free ends of the individual conductors,
preferably soldered inplace.
1 Remove upper nuts only from terminal block studs.
Do not remove lower nuts which secure range
wiring leads. Remove and retain the 2 ferrites.
2 Mount strain relief (not provided with range) into
the 1-1/2” (38mm) diameter hole in the bracket
located below the terminal block. Route the wires
up through strain relief.
3 Route L1 (Black), L2 (Red) and Neutral (White)
wires through ferrites. Ground (Green) wire is not
routed through ferrites. Ensure ferrites are not
touching any electrically live parts.
3-Conductor cord
Where local codes and ordinances permit grounding
through neutral, and conversion of supply to 4 wire is
impractical, unit may be connected to the power supply
with a 3-pole, 3-conductor cord kit rated 125/250 volts, 50
amperes, and marked for use with ranges.
The cord kit must be attached to the range back panel
with a strain relief which will fit a 1 – 1/2" (38mm) diameter
hole. If not already equipped, the cord must also have
1/4"(6mm) faston closed-loop lugs attached to the free
ends of the individual conductors.
1 Remove upper nuts only from terminal block studs.
Do not remove lower nuts which secure range wiring
leads. Remove and retain the 2 ferrites.
2 Mount strain relief (not provided with range) into
the 1-1/2” (38mm) diameter hole in the bracket
located below the terminal block. Route the wires up
through strain relief.
3 Route L1 (Black), L2 (Red) and Neutral (White) wires
through ferrites.
4-Wire connection
1 Secure the Neutral (white) power lead, to the center
stud (silver colored) of the terminal block with nut.
2 Secure the L1 (black) and L2 (red) power leads to
the outside terminal studs (brass colored) with nuts.
3 Secure the Ground (green) power lead to the back
of the range with the screw located beneath the
terminal block.
4 Tighten all connections securely.
5 Reinstall the Terminal Block Cover.
3-Wire Lead connection
1 Secure the L1 (black) and L2 (red) power leads
tothe outside corresponding terminal block studs
(brass colored).
2 Secure Neutral (white), grounded wire of the supply
circuit and reconnect one end of the mounted loop
Ground wire, located beneath the terminal block, up
through the ferrites to the centre stud (silver colored)
of the terminal block with nut.
3 Leave the other end of the Ground wire screwed
intothe back of the range.
4 Tighten nuts securely.
5 Reinstall the Terminal Block Cover.