1. INSTALLATION
INSTALLER
1.1.8. HYDRAULIC CONNECTION
DANGER
Make sure that the tubes of the water and
heating plant are not used as grounding system for
the electrical plant. There are not suitable for such
use.
WARNING
To prevent voiding the warranty and to
ensure the proper operation of the water heater,
please wash the plant (if possible when hot) with
suitable pickling or descaling solutions in order
to remove the impurities coming from tubes and
radiators.
WARNING
If the water heater is installed in a
hydrostatic position lower than those of the user
devices (radiators, fan coils, etc.), mount the shut-off
valves on the domestic water heating circuit to ease
the performance of the maintenance operations if it is
necessary only to empty the water heater.
WARNING
When connecting the equipment to
water supply, avoid excessive bending and recovery
operations from any off axis positioning that may
damage the tubes causing leaks, malfunction or
early wear.
WARNING
In order to avoid any vibrations and noises,
do not use tubes with small diameters or elbows with
small radius and significant cut-off of the passage
sections.
WARNING
Connect the water heater safety drains
to a discharge funnel. The manufacturer is not
responsible for any floods due to safety valve opening
in case of plant overpressure.
In order to prevent limestone build-up and damages
to the domestic water heat exchanger, the hardness
of the domestic supply water should not exceed 15
°f. However, please check the characteristics of the
water used and install suitable treating devices.
The heat exchanger coil cleaning frequency
depends on the hardness of the supply water and on
the presence of solid residues or impurities inside
the water that are often present in case of recently
installed plants. Based on the characteristics of
the infeed water, you should install suitable water
treating devices, for residues presence please
install a line filter.
The pressure of the cold infeed water should be
between 0.5 and 6 bar. In case of greater pressure
values, please install a pressure reducer upstream
from the water heater.
Please note
Because the minimum power of the SF14 Water heater is 10 kW, at low water
flows (i.e., 5 Litres/ minute or less) the temperature may exceed the set
temperature programmed on the unit. This is to avoid continuous shutdowns, it
initially heats the water up to 60°C, within the heat exchanger ( as a by-product this
is good for anti-legionella purposes, as although this is a little volume of
water within the heat exchanger , if the unit hasn’t been used for some time –
it’s good to heat it up to this level ), then a downward output adjustment is
performed by the burner, to adjust to the required power to achieve your desired
temperature.
This can be avoided / overcome by installing a mixing valve on the hot water
outlet – which can limit the hot water temperature to 43C to prevent any scalding
issues.
A TMV (Thermostatic mixing valve) are also good for applications, whereby you
might want lower hot water temperatures than the unit can produce which is 35°C
on the control panel. For example, we supply these units to the equine sector, for
warm washing down of horses etc – in the summer months, they may only
require a temperature °of 30C – by using one of the above valves fitted to the hot
water outlet – you can reduce the temperature down to 30C , as most of these TMV
mixing valves can control the water temperature between 30°C to 50°C.