
Main Control Unit
The main control unit powers the sensors and continuously monitors their output
state, ensuring a fast response to any possible diaphragm failure. If the main
control unit detects a failure from either sensor the red LED on the front panel will
flash. Simultaneously the solenoid output is de-activated and the connected
solenoid valve, (customer supplied), stops the air flow to the pump thus stopping
the pump.
The main unit latches in the alarm condition until the failure has cleared and the
unit is reset by pressing the front panel mounted Reset button. If the failure mode is
still present, i.e. pumped media still contaminating the sensors, the unit will not be
able to be reset until the failure has been rectified.
If there is a power failure to the main unit, the default pump operation mode is off
and the pump will be stopped. Upon power supply being restored the unit will stay
in the pump off condition until the Reset button is pressed.
The main control unit will alarm and set to fail condition if the sensors are not
connected or if the sensors fail to operate within their normal parameters.
There is a volt free relay connection that can be wired for either normally open or
normally closed configurations upon an alarm state. This connection can be used
to either monitor the unit’s state, i.e. running or fault, or to control another piece of
equipment that depends on a particular pump state. NOTE – This connection is a
volt free relay connection with a maximum rating of 1A @ 30V.
NOTE:
To fully comply with the 3A standard there must be a solenoid valve connected to
the main control unit to enable the pump to be stopped once a failure mode is
detected.
The solenoid valve needs to be fitted to the air pipe supplying the pump. See
Technical Data section for solenoid specifications.