
electrical service life AC -14 at 3 A 1 × 105switching cycles,
AC -14 at 0.5 A 2 × 106switching cycles
Common supply conductor P to the output relays maximum
10 A
Note: utilization category AC / DC as per IEC 60947-5-1
For all PQC versions in areas where UL / CSA standards apply:
3 A 250 V AC cos φ= 1 at 85 °C
3 A 30 V DC L/R = 0 ms at 85 °C
Alarm contact Volt-free, normally open,·
AC -14 250 V AC, maximum 3 A or DC -13 30 V DC, maximum
3 A, mechanical service life 2 × 107switching cycles,
electrical service life AC -14 at 3 A 1.5 × 105switching cycles,
AC -14 at 0.5 A 2 × 106switching cycles
Note: utilization category AC / DC as per IEC 60947-5-1
In areas where UL / CSA standards apply:
3 A 250 V AC cos φ= 1 at 85 °C
3 A 30 V DC L/R = 0 ms at 85 °C
Digital outputs PQC version: PQC xxxxxxx-x1:·
Up to 5 × 24 V DC, 100 mA outputs, electrically interconnected
with each other and the temperature input, alternatively usable
as up to 5 × 5 – 24 V DC inputs.
Interfaces
Modbus RTU connection PQC version: PQC xxxxxxx-2x:·
120 Ω terminating resistor required at the end of the bus
system
Connections Via pluggable screw terminals
Instrument power AUX Conductor cross section max. 2.5mm², min. 0.2mm²·
PQC version: PQC xxx240x-xx:
Insulation rating: min. 250 V AC, 80 °C
PQC version: PQC xxx480x-xx:
Insulation rating: min. 500 V AC, 80 °C
Protective earth PE Via 6.3 mm female slide connector·
Conductor cross section at least equal to the largest
conductor cross section of the AUX phases, the voltage
measurement connections, the output relays and the alarm
connections; insulation colour yellow/green
Voltage measurement inputs Conductor cross section max. 2.5mm², min. 0.2mm²·
Insulation rating:
Example 1: 230 V AC, select at least 250 V AC, 80 °C
Example 2: 690 V AC, select at least 750 V AC, 80 °C
Current measurement inputs Conductor cross section max. 2.5mm², min. 0.2mm²·
Insulation rating: min. 250 V AC, 80 °C
Output relays (control outputs, Conductor cross section max. 2.5 mm², min. 0.2 mm²·
PQC version: PQC xx0xxxx-xx: 250 V relays
Insulation rating: min. 250 V AC, 80 °C
PQC version: PQC xx1xxxx-xx: 440 V relays
Insulation rating: min. 500 V AC, 80 °C
L1, L2, L3, N
capacitor stages)
L1, L2, L3, terminals S1 and
S2 in each case