Frapol Onyx SKY 250 User manual

Operation and Maintenance Manual, OnyX Sky Heat Recovery Units, 2022/01
Frapol Sp. z o.o. reserves the right to introduce changes without any prior notice. Page 1
OPERATION AND MAINTENANCE MANUAL
for Heat Recovery Units

Operation and Maintenance Manual, OnyX Sky Heat Recovery Units, 2022/01
Frapol Sp. z o.o. reserves the right to introduce changes without any prior notice. Page 2
Table of Contents
1. General Safety Principles.......................................................................................................................................................................................3
2. Declaration of the Manufacturer........................................................................................................................................................................4
2.1 Residual hazards ...........................................................................................................................................................................................4
3. General information.................................................................................................................................................................................................4
3.1 Identification and documentation of the Heat Recovery Unit.................................................................................................5
3.2 Intended use and scope of application ...............................................................................................................................................5
3.3 Structure of the Heat Recovery Unit and scope of delivery......................................................................................................5
3.4 External dimensions....................................................................................................................................................................................6
3.5 Capacity range.............................................................................................................................................................................................12
3.6 Efficiency of the heat recovery system and electric power consumption......................................................................14
3.7 Specifications...............................................................................................................................................................................................16
3.8 Product data sheets and energy labels............................................................................................................................................19
4. Transport and storage .........................................................................................................................................................................................23
5. Installation.................................................................................................................................................................................................................23
5.1 Place of installation...................................................................................................................................................................................23
5.2 Assembly procedure.................................................................................................................................................................................23
5.3 Connecting ventilation ducts................................................................................................................................................................24
5.4 Air filters ........................................................................................................................................................................................................24
5.5 Fan.....................................................................................................................................................................................................................24
5.6 Installing the controller ..........................................................................................................................................................................24
5.7 Drainage of condensate...........................................................................................................................................................................37
5.8 Electric heater..............................................................................................................................................................................................38
6. Pre-start check and starting-up.......................................................................................................................................................................40
6.1 Check................................................................................................................................................................................................................40
6.2 Start-up ...........................................................................................................................................................................................................41
7. Operation ...................................................................................................................................................................................................................41
7.1 Filters...............................................................................................................................................................................................................41
7.2 Heat recovery system...............................................................................................................................................................................42
7.3 Electric heater..............................................................................................................................................................................................42
8. Control system.........................................................................................................................................................................................................42
8.1 Scope of delivery ........................................................................................................................................................................................42
8.2 Main screen...................................................................................................................................................................................................43
8.3 Controller operating modes..................................................................................................................................................................49
8.4 Resetting the air filter counter............................................................................................................................................................49
8.5 Temperature setpoint settings............................................................................................................................................................49
8.6 Time schedule..............................................................................................................................................................................................49
8.7 Operating modes........................................................................................................................................................................................50
8.8 Alarm control panel - ECO .....................................................................................................................................................................51
8.9 Heat recovery...............................................................................................................................................................................................51
8.10 Balanced ventilation function..............................................................................................................................................................52
8.11 General Settings..........................................................................................................................................................................................52
8.12 Working with the Internet module. ..................................................................................................................................................53
8.13 Alarms .............................................................................................................................................................................................................55
8.14 Assembly instructions and service settings for the SMART controller ...........................................................................57
8.15 Installer Menu..............................................................................................................................................................................................57
8.16 Description of Installer Menu ..............................................................................................................................................................62
8.17 Specifications ...............................................................................................................................................................................................65
8.18 Operating conditions................................................................................................................................................................................65
9. Disassembly and disposal of the device ......................................................................................................................................................65
10. Terms of warranty.................................................................................................................................................................................................66
10.1 Validity of the Warranty Card..............................................................................................................................................................66
10.2 Exclusions......................................................................................................................................................................................................67
11. Complaints.................................................................................................................................................................................................................67

Operation and Maintenance Manual, OnyX Sky Heat Recovery Units, 2022/01
Frapol Sp. z o.o. reserves the right to introduce changes without any prior notice. Page 3
1. General Safety Principles
RECOMMENDATIONS IN THE MANUAL
Failure to follow the recommendations in the manual may result in property damage and personal injury. The
manufacturer is not liable for any damage resulting directly or indirectly from failure to comply with this manual.
STORING THE MANUAL
Keep this manual and the documentation pertaining to the Heat Recovery Unit in a location easily accessible to
operators and service personnel.
REQUIREMENTS CONTAINED IN SUPPLEMENTARY INSTRUCTIONS
Depending on configuration, additional instructions for the following components may be provided with the unit. It is
essential that you familiarise yourself with the safety requirements specified in:
•Operation and Maintenance Manual for OnyX accessories
PERSONNEL AUTHORISATIONS
Installation, start-up, and operation of the unit must be carried out by personnel having appropriate qualifications
required by the current regulations.
ELECTRICAL CONNECTIONS
Make sure that the mains supply voltage matches the data specified on the nameplate of the unit. The maximum
permissible deviations are:
•Power supply voltage: +/- 6%
•Frequency: +/- 2%
DANGER
Before making any electrical connections or performing any maintenance works, make sure that the supply
voltage is disconnected, and the circuit breaker is in the disconnected position.
Parameters of the power supply line and its necessary protective equipment must be selected and dimensioned by
personnel with appropriate qualifications, regarding designing electrical installations, according to the applicable laws.
TRANSPORT
The unit must be transported to the place of installation in accordance with the applicable safety regulations. Persons
who operate means of transport (a forklift truck, crane, etc.) must have appropriate qualifications. When transporting
the unit, wear personal protective equipment (safety gloves, safety helmets, safety goggles). Never stand under
suspended loads.
OPERATION AND MAINTENANCE ACTIVITIES
Maintenance inspections must be carried out regularly at the intervals specified in the “Operation” section. The goal is
to detect defective or loose parts in advance and avoid breakdowns. Failure to rectify the detected fault increases the
risk of failure, damage, or injury.
CAUTION HOT PARTS
The unit contains components with high surface temperature (e.g., heat exchangers, heaters, motor
housing). Direct contact with them may cause burns or other injuries. Take special care, wear protective
clothing, and perform maintenance works only after their temperature falls below 40°C.
WARNING SHARP EDGES
The unit is designed with sharp edges (e.g., lamellas in heat exchangers). Contact with them may result
in injuries.Wear protective clothing and be particularly careful when performing maintenance works.
WARNING MOVING PARTS
The unit contains moving parts (e.g. fan rotors). Contact with them may result in mutilations or serious
injuries. Maintenance work may only be carried out, when such parts have completely stopped.
DETECTING FAULTS
In case of mechanical damage to the supplied goods, please draw up a damage report with the carrier. The report
is to be drawn up on the day of delivery and it is the basis for acceptance of claims for transport damage. If a fault
or malfunction is detected, switch off the unit and call an authorised service centre.
REPAIRS
All repairs should be carried out by an authorised service centre and using original spare parts.
MODIFICATIONS
Unauthorised (mechanical or electrical) modifications to the equipment are not permitted and void the warranty. The
manufacturer is not responsible for any such actions.

Operation and Maintenance Manual, OnyX Sky Heat Recovery Units, 2022/01
Frapol Sp. z o.o. reserves the right to introduce changes without any prior notice. Page 4
INTENDED USE OF THE UNIT
Operate the equipment according to its intended use and design, as well as within its operating parameters. In the event
of improper use, the manufacturer shall not be held liable for any consequences resulting from such misuse.
PACKAGING
Packaging parts (plastic film, polyester foam, nails, etc.) are hazardous and should be stored away from children, and
disposed of after use in accordance with applicable regulations.
2. Declaration of the Manufacturer
The Manufacturer declares that the equipment meets the safety requirements of the following directives and associated
standards:
•2004/108/EC
•2006/42/EC
•2006/95/EC
•2009/125/EC
The sub-assemblies delivered by suppliers have the appropriate declarations of conformity and/or the CE marking in
accordance with the following directives:
•97/23/EC
In order to meet the basic requirements of EMC 2004/108/EC, the unit must be installed using professional engineering
methods, ensuring electromagnetic compatibility, taking into account information on the use of components for its
intended purpose, and meeting the requirements of the EMC Directive.
This declaration applies only if the unit has been installed in accordance with the Operation and Maintenance Manual
and no changes have been made.
2.1 Residual hazards
In the process of designing and manufacturing the equipment, solutions were applied that minimise possible hazards
to persons and property. However, this does not eliminate all possible risks. Below is the list of some events outside the
control of the manufacturer, which may cause potential risk to human health and security of property:
HAZARDS RESULTING FROM INCORRECT INSTALLATION AND ASSEMBLY
•accumulation and leakage of condensate (damage to property, short-circuit)
•leakage of water from the circuit (damage to property, short circuit)
•falling of the appliance installed on an unsuitable substructure (danger to health and life, damage to
property),
•installation in a place accessible to unauthorised persons (danger to health and life).
HAZARDS RESULTING FROM INCORRECT TRANSPORTING
•falling or overturning of the appliance in transport (danger to health and life, damage to property).
HAZARDS RESULTING FROM INCORRECT ELECTRICAL INSTALLATION
•short-circuit, fire, toxic fumes (danger to health and life, damage to property).
OPERATION WITHOUT PROTECTIVE PANELS AND GUARDS IN PLACE
•contact with moving or hot parts (danger to health and life).
3. General information
This OMM provides information concerning the installation, start-up, operation and maintenance of the FRAPOL OnyX
Heat Recovery Units. Read the instructions and recommendations, before carrying out any operation on the device.
Damage to the unit resulting from failure to observe the instructions –in particular due to improper storage or
transport, incorrect connections and negligence in maintenance –shall not be covered by warranty repairs.
NOTE
The warranty does not cover materials and consumables, in particular: air filters and bearings for fans.

Operation and Maintenance Manual, OnyX Sky Heat Recovery Units, 2022/01
Frapol Sp. z o.o. reserves the right to introduce changes without any prior notice. Page 5
3.1 Identification and documentation of the Heat Recovery Unit
The Heat Recovery Unit has a nameplate which
identifies the most important technical parameters of
the unit. This Operation and Maintenance Manual is
provided to the customer together with the invoice,
warranty and declaration of conformity as well as any
additional manuals. For any contact with the service
department, please indicate the type and the serial
number of the unit.
3.2 Intended use and scope of application
The OnyX Heat Recovery Units (HRUs) are used to prepare air for ventilation and air-conditioning systems in
residential, service, public, and industrial buildings.
The HRUs can be used for air treatment with the maximum dust concentration of 0.5 mg/m3.
The permissible temperature range of the air supplied to the HRU is -20°C to +40°C.
The maximum mixing ratio of the air supplied to the recuperator should not exceed 19g/kg of dry air (at the
temperature of +30°C and relative humidity of 70%).
DANGER
Heat Recovery Units must not be installed in ex zones.
3.3 Structure of the Heat Recovery Unit and scope of delivery
The OnyX Sky Heat Recovery Units are equipped with the following components:
•A counter-current heat recovery system (1) with an automatic bypass system (2)
•Fresh air (3) and exhaust air (4) filters
•Supply (5) and exhaust (6) fans
•An automation system (7) with a main breaker switch and a power socket
•Adjustable fasteners for access panels (8)
•Round connection ports for ventilation ducts (9)
•Duct stubs (10)
Scope of delivery:
•Heat Recovery Unit with an integrated control system
•Control panel
•Power supply cord
•Electric duct pre-heater of the anti-freeze system (if it isn’t mounted inside HRU)
•Trap for condensate drainage system
•O&M Manual

Operation and Maintenance Manual, OnyX Sky Heat Recovery Units, 2022/01
Frapol Sp. z o.o. reserves the right to introduce changes without any prior notice. Page 6
3.4 External dimensions
3.4.1 OnyX Sky 250 –right side
3.4.2 OnyX Sky 250 –left side

Operation and Maintenance Manual, OnyX Sky Heat Recovery Units, 2022/01
Frapol Sp. z o.o. reserves the right to introduce changes without any prior notice. Page 7
3.4.3 OnyX Sky 500 –right side
3.4.4 OnyX Sky 500 –left side

Operation and Maintenance Manual, OnyX Sky Heat Recovery Units, 2022/01
Frapol Sp. z o.o. reserves the right to introduce changes without any prior notice. Page 8
3.4.5 OnyX Sky 750 - right side
3.4.6 OnyX Sky 750 - left side

Operation and Maintenance Manual, OnyX Sky Heat Recovery Units, 2022/01
Frapol Sp. z o.o. reserves the right to introduce changes without any prior notice. Page 9
3.4.1 OnyX Sky 1000 - right side
3.4.2 OnyX Sky 1000 - left side

Operation and Maintenance Manual, OnyX Sky Heat Recovery Units, 2022/01
Frapol Sp. z o.o. reserves the right to introduce changes without any prior notice. Page 10
3.4.3 OnyX Sky 1500 –right side
3.4.4 OnyX Sky 1500 –left side

Operation and Maintenance Manual, OnyX Sky Heat Recovery Units, 2022/01
Frapol Sp. z o.o. reserves the right to introduce changes without any prior notice. Page 11
3.4.5 OnyX Sky 3000 –right side
3.4.6 OnyX Sky 3000 –left side

Operation and Maintenance Manual, OnyX Sky Heat Recovery Units, 2022/01
Frapol Sp. z o.o. reserves the right to introduce changes without any prior notice. Page 12
3.5 Capacity range
3.5.1 OnyX Sky 250
3.5.2 OnyX Sky 500
3.5.3 OnyX Sky 750
0
50
100
150
200
250
300
350
400
450
050 100 150 200 250 300 350
Static pressure [Pa]
Air flow [m3/h]
100% 70% 40%
0
100
200
300
400
500
600
700
800
0100 200 300 400 500 600
Static pressure [Pa]
Air flow [m3/h]
100% 70% 40%
0
100
200
300
400
500
600
700
0100 200 300 400 500 600 700 800 900
Static pressure [Pa]
Air flow [m3/h]
100% 70% 40%

Operation and Maintenance Manual, OnyX Sky Heat Recovery Units, 2022/01
Frapol Sp. z o.o. reserves the right to introduce changes without any prior notice. Page 13
3.5.4 OnyX Sky 1000
3.5.5 OnyX Sky 1500
3.5.6 OnyX Sky 3000
0
100
200
300
400
500
600
700
0100 200 300 400 500 600 700 800 900 1000 1100 1200
Static pressure [Pa]
Air flow [m3/h]
100% 70% 40%
0
200
400
600
800
1000
1200
1400
1600
0200 400 600 800 1000 1200 1400 1600
Static pressure [Pa]
Air flow [m3/h]
100% 70% 40%
0
200
400
600
800
1000
1200
1400
1600
0200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000
Static pressure [Pa]
Air flow [m3/h]
100% 70% 40%

Operation and Maintenance Manual, OnyX Sky Heat Recovery Units, 2022/01
Frapol Sp. z o.o. reserves the right to introduce changes without any prior notice. Page 14
3.6 Efficiency of the heat recovery system and electric power consumption
The temperature efficiency of heat recovery in the HRU OnyX series was determined on the basis of laboratory tests
under the following operating conditions:
- HRS temperature efficiency 1
Fresh air parameters: 7°C, 50%
Exhaust air parameters 20°C, 40%
- HRS temperature efficiency 2
Fresh air parameters: 0°C, 50%
Exhaust air parameters 20°C, 40%
Standard operating mode (anti-freeze system deactivated), with balanced and adjusted ventilation system (fresh air
flow rate = exhaust air flow rate) and clean air filters. The electrical power consumption is determined for the static
pressure of 100 Pa.
NOTE
The manufacturer is not responsible for reduced heat recovery efficiency resulting from improper operation
and imbalance of the ventilation system.
3.6.1 OnyX Sky 250
3.6.2 OnyX Sky 500
0
20
40
60
80
100
120
140
70,0
80,0
90,0
100,0
050 100 150 200 250 300
Power consumption [W]
HRS temperature efficiency [%]
Air flow [m3/h]
HRS temperature efficiency 1 HRS temperature efficiency 2
0
50
100
150
200
250
70,0
80,0
90,0
100,0
0100 200 300 400 500
Power consumption [W]
HRS temperature efficiency [%]
Air flow [m3/h]
HRS temperature efficiency 1 HRS temperature efficiency 2

Operation and Maintenance Manual, OnyX Sky Heat Recovery Units, 2022/01
Frapol Sp. z o.o. reserves the right to introduce changes without any prior notice. Page 15
3.6.3 OnyX Sky 750
3.6.4 OnyX Sky 1000
3.6.5 OnyX Sky 1500
0
100
200
300
400
500
600
700
800
70
80
90
100
110
0100 200 300 400 500 600 700 800 900 1000
Power consumption [W]
HRS temperature efficiency [%]
Air flow [m3/h]
HRS temperature efficiency 1 HRS temperature efficiency 2
0
50
100
150
200
250
300
350
400
450
500
70
80
90
100
0100 200 300 400 500 600 700 800 900 1000 1100
Power consumption [W]
HRS temperature efficiency [%]
Air flow [m3/h]
HRS temperature efficiency 1 HRS temperature efficiency 2
0
200
400
600
800
1000
1200
70,0
80,0
90,0
100,0
0200 400 600 800 1000 1200 1400 1600
Power consumption [W]
HRS temperature efficiency [%]
Air flow [m3/h]
HRS temperature efficiency 1 HRS temperature efficiency 2

Operation and Maintenance Manual, OnyX Sky Heat Recovery Units, 2022/01
Frapol Sp. z o.o. reserves the right to introduce changes without any prior notice. Page 16
3.6.6 OnyX Sky 3000
3.7 Specifications
3.7.1 OnyX Sky 250
Maximum air flow (100 Pa)
m3/h
280
Maximum fan power consumption
W
125
Pre-heater power
W
600 W
Rated supply voltage
230V AC/50Hz
Fuse type
-
C6 overcurrent circuit breaker
External dimensions (width x height x length)
mm
654 x 345 x 880
Dimensions of ventilation connections (diameter)
mm
Ø160
Weight
kg
43
Class of filters used
-
ISO Coarse 65% (G4)
Filter dimensions (W x H)
mm
290 x 230
Protection rating
-
IP 40
Unit insulation class
-
I
Ambient conditions in the technical room
Range of operating temperatures
°C
5-45
Permissible humidity
%
25-90 (no condensation)
Acoustic characteristics:
Operating point: 280 m3/h 100Pa, all components of the HRU clean and dry
63 Hz
125 Hz
250 Hz
500 Hz
1 kHz
2 kHz
4 kHz
8 kHz
Ʃ
dB
dB(A)
Air intake
56
53,9
57,6
58,6
53,6
52,2
46,6
34,7
60
Air supply
65
66,9
68,6
68,6
66,6
64,2
59,6
54,7
71
Exhaust
56
53,9
57,6
58,6
53,6
52,2
46,6
34,7
60
Exhaust vent
65
66,9
68,6
68,6
66,6
64,2
59,6
54,7
71
Housing
54
52,9
49,6
40,6
37,6
43,2
34,6
27,7
51
Operating point: 196 m3/h 50Pa, all components of the HRU clean and dry
63 Hz
125 Hz
250 Hz
500 Hz
1 kHz
2 kHz
4 kHz
8 kHz
Ʃ
dB
dB(A)
Air intake
50,8
48
51,4
52,3
47,1
45,2
38,2
24,5
53
Air supply
59,8
61
62,4
62,3
60,1
57,2
51,2
44,5
65
Exhaust
50,8
48
51,4
52,3
47,1
45,2
38,2
24,5
53
Exhaust vent
59,8
61
62,4
62,3
60,1
57,2
51,2
44,5
65
Housing
48,8
47
43,4
34,3
31,1
36,2
26,2
17,5
44
0
400
800
1200
1600
2000
70,0
80,0
90,0
100,0
0400 800 1200 1600 2000 2400 2800
Power consumption [W]
HRS temperature efficiency [%]
Air flow [m3/h]
HRS temperature efficiency 1 HRS temperature efficiency 2

Operation and Maintenance Manual, OnyX Sky Heat Recovery Units, 2022/01
Frapol Sp. z o.o. reserves the right to introduce changes without any prior notice. Page 17
3.7.2 OnyX Sky 500
Maximum air flow (100 Pa)
m3/h
479
Maximum fan power consumption
W
242
Pre-heater power
W
600 W
Rated supply voltage
230V AC/50Hz
Fuse type
-
C6 overcurrent circuit breaker
External dimensions (width x height x length)
mm
863 x 332 x 1450
Dimensions of ventilation connections (diameter)
mm
Ø200
Weight
kg
77
Class of filters used
-
ISO Coarse 60% (G4)
Filter dimensions (W x H)
mm
400 x 180 x 25
Protection rating
-
IP 40
Unit insulation class
-
I
Ambient conditions in the technical room
Range of operating temperatures
°C
5-45
Permissible humidity
%
25-90 (no condensation)
Acoustic characteristics:
Operating point: 479 m3/h 100Pa, all components of the HRU clean and dry
63 Hz
125 Hz
250 Hz
500 Hz
1 kHz
2 kHz
4 kHz
8 kHz
Ʃ
dB
dB(A)
Air intake
59
60
59
59
56
57
53
42
62
Air supply
68
73
70
68
69
69
66
62
74
Exhaust
59
60
59
59
56
57
53
42
62
Exhaust vent
68
73
70
68
69
69
66
62
74
Housing
57
59
51
40
40
48
41
35
54
Operating point: 335 m3/h 50Pa, all components of the HRU clean and dry
63 Hz
125 Hz
250 Hz
500 Hz
1 kHz
2 kHz
4 kHz
8 kHz
Ʃ
dB
dB(A)
Air intake
54
54
55
56
52
51
46
34
58
Air supply
63
67
66
66
65
63
59
54
69
Exhaust
54
54
55
56
52
51
46
34
58
Exhaust vent
63
67
66
66
65
63
59
54
69
Housing
52
53
47
38
36
42
34
27
49
3.7.3 OnyX Sky 750
Maximum air flow (100 Pa)
m3/h
750
Maximum fan power consumption
W
337
Pre-heater power
W
1800 W
Rated supply voltage
230V AC/50Hz
Fuse type
-
C10 overcurrent circuit breaker
External dimensions (width x height x length)
mm
1100 x 345 x 1520
Dimensions of ventilation connections (diameter)
mm
Ø250
Weight
kg
134 kg
Class of filters used
-
ISO Coarse 60% (G4)
Filter dimensions (W x H)
mm
2x 400 x 180 x 25
Protection rating
-
IP 40
Unit insulation class
-
I
Ambient conditions in the technical room
Range of operating temperatures
°C
5-45
Permissible humidity
%
25-90 (no condensation)
Acoustic characteristics:
Operating point: 750 m3/h 100Pa, all components of the HRU clean and dry
63 Hz
125 Hz
250 Hz
500 Hz
1 kHz
2 kHz
4 kHz
8 kHz
Ʃ
dB
dB(A)
Air intake
56
55
60
60
55
53
49
38
61
Air supply
65
68
71
70
68
65
62
58
73
Exhaust
56
55
60
60
55
53
49
38
61
Exhaust vent
65
68
71
70
68
65
62
58
73
Housing
54
54
52
42
39
44
37
31
52
Operating point: 525 m3/h 50Pa, all components of the HRU clean and dry
63 Hz
125 Hz
250 Hz
500 Hz
1 kHz
2 kHz
4 kHz
8 kHz
Ʃ
dB
dB(A)
Air intake
52
50
55
56
50
47
41
29
56
Air supply
61
63
66
66
63
59
54
49
68
Exhaust
52
50
55
56
50
47
41
29
56
Exhaust vent
61
63
66
66
63
59
54
49
68
Housing
50
49
47
38
34
38
29
22
47

Operation and Maintenance Manual, OnyX Sky Heat Recovery Units, 2022/01
Frapol Sp. z o.o. reserves the right to introduce changes without any prior notice. Page 18
3.7.4 OnyX Sky 1000
Maximum air flow (100 Pa)
m3/h
999
Maximum fan power consumption
W
438
Pre-heater power
W
1800 W
Rated supply voltage
230V AC/50Hz
Fuse type
-
C16 overcurrent circuit breaker
External dimensions (width x height x length)
mm
1400 x 478 x 1305
Dimensions of ventilation connections (diameter)
mm
Ø315
Weight
kg
166 kg
Class of filters used
-
ISO Coarse 60% (G4)
Filter dimensions (W x H)
mm
2x 400 x 180 x 25
Protection rating
-
IP 40
Unit insulation class
-
I
Ambient conditions in the technical room
Range of operating temperatures
°C
5-45
Permissible humidity
%
25-90 (no condensation)
Acoustic characteristics:
Operating point: 999 m3/h 100Pa, all components of the HRU clean and dry
63 Hz
125 Hz
250 Hz
500 Hz
1 kHz
2 kHz
4 kHz
8 kHz
Ʃ
dB
dB(A)
Air intake
65
62
63
62
59
58
53
41
64
Air supply
74
75
74
72
72
70
66
61
76
Exhaust
65
62
63
62
59
58
53
41
64
Exhaust vent
74
75
74
72
72
70
66
61
76
Housing
63
61
55
44
43
49
41
34
56
Operating point: 699 m3/h 50Pa, all components of the HRU clean and dry
63 Hz
125 Hz
250 Hz
500 Hz
1 kHz
2 kHz
4 kHz
8 kHz
Ʃ
dB
dB(A)
Air intake
59
56
56
55
52
50
44
30
57
Air supply
68
69
67
65
65
62
57
50
69
Exhaust
59
56
56
55
52
50
44
30
57
Exhaust vent
68
69
67
65
65
62
57
50
69
Housing
57
55
48
37
36
41
32
23
49
3.7.5 OnyX Sky 1500
Maximum air flow (100 Pa)
m3/h
1498
Maximum fan power consumption
W
1060
Duct pre-heater power (external power supply)
W
max. 4000 W / 230V AC/50Hz
Rated supply voltage
230V AC/50Hz
Fuse type
-
C6 overcurrent circuit breaker
External dimensions (width x height x length)
mm
1670 x 445 x1700
Dimensions of ventilation connections (diameter)
mm
Ø315
Weight
kg
172
Class of filters used
-
ISO Coarse 65% (G4)
Filter dimensions (W x H)
mm
592 x 287 x 200; 592 x 287 x 300
Protection rating
-
IP 40
Unit insulation class
-
I
Ambient conditions in the technical room
Range of operating temperatures
°C
5-45
Permissible humidity
%
25-90 (no condensation)
Acoustic characteristics:
Operating point: 1498 m3/h 100 Pa, all components of the HRU clean and dry
63 Hz
125 Hz
250 Hz
500 Hz
1 kHz
2 kHz
4 kHz
8 kHz
Ʃ
dB
dB(A)
Air intake
60,1
59,5
66
68,3
65,6
65,3
61,9
52,2
71
Air supply
69,1
72,5
77
78,3
78,6
77,3
74,9
72,2
84
Exhaust
60,1
59,5
66
68,3
65,6
65,3
61,9
52,2
71
Exhaust vent
69,1
72,5
77
78,3
78,6
77,3
74,9
72,2
84
Housing
58,1
58,5
58
50,3
49,6
56,3
49,9
45,2
63
Operating point: 1049 m3/h 50 Pa, all components of the HRU clean and dry
63 Hz
125 Hz
250 Hz
500 Hz
1 kHz
2 kHz
4 kHz
8 kHz
Ʃ
dB
dB(A)
Air intake
55,8
54,2
58,6
60,2
57,8
57
52,1
40,3
63
Air supply
64,8
67,2
69,6
70,2
70,8
69
65,1
60,3
75
Exhaust
55,8
54,2
58,6
60,2
57,8
57
52,1
40,3
63
Exhaust vent
64,8
67,2
69,6
70,2
70,8
69
65,1
60,3
75
Housing
53,8
53,2
50,6
42,2
41,8
48
40,1
33,3
54

Operation and Maintenance Manual, OnyX Sky Heat Recovery Units, 2022/01
Frapol Sp. z o.o. reserves the right to introduce changes without any prior notice. Page 19
3.7.6 OnyX Sky 3000
Maximum air flow (100 Pa)
m3/h
2692
Maximum fan power consumption
W
2100
Duct pre-heater power (external power supply)
W
max. 6000 W/ 3x400V AC/50Hz
Rated supply voltage
230V AC/50Hz
Fuse type
-
C6 overcurrent circuit breaker
External dimensions (width x height x length)
mm
2046 x 486 x 1790
Dimensions of ventilation connections
mm
760x360, 940x360
Weight
kg
225
Class of filters used
-
ISO Coarse 65% (G4)
Filter dimensions (W x H)
mm
760 x 400 x 100
Protection rating
-
IP 40
Unit insulation class
-
I
Ambient conditions in the technical room
Range of operating temperatures
°C
5-45
Permissible humidity
%
25-90 (no condensation)
Acoustic characteristics:
Operating point: 2692 m3/h 100 Pa, all components of the HRU clean and dry
63 Hz
125 Hz
250 Hz
500 Hz
1 kHz
2 kHz
4 kHz
8 kHz
Ʃ
dB
dB(A)
Air intake
69,5
66,8
68,5
67,8
65,1
64,3
60,7
50,3
71
Air supply
78,5
79,8
79,5
77,8
78,1
76,3
73,7
70,3
83
Exhaust
69,5
66,8
68,5
67,8
65,1
64,3
60,7
50,3
71
Exhaust vent
78,5
79,8
79,5
77,8
78,1
76,3
73,7
70,3
83
Housing
67,5
65,8
60,5
49,8
49,1
55,3
48,7
43,3
63
Operating point: 1885 m3/h 50 Pa, all components of the HRU clean and dry
63 Hz
125 Hz
250 Hz
500 Hz
1 kHz
2 kHz
4 kHz
8 kHz
Ʃ
dB
dB(A)
Air intake
60,9
57,8
59,2
58,9
56,5
55,3
50,2
37,6
62
Air supply
69,9
70,8
70,2
68,9
69,5
67,3
63,2
57,6
74
Exhaust
60,9
57,8
59,2
58,9
56,5
55,3
50,2
37,6
62
Exhaust vent
69,9
70,8
70,2
68,9
69,5
67,3
63,2
57,6
74
Housing
58,9
56,8
51,2
40,9
40,5
46,3
38,2
30,6
53
3.8 Product data sheets and energy labels.
3.8.1 OnyX Sky 250
Product data sheet (technical data in accordance with Regulation of the European Commission No. 1254/14)
Name or trade mark of the Supplier
-
Frapol Sp. z o.o.
Model identifier
-
OnyX Sky 250
SEC (polar, temperate and tropical climates)
kWh/(m2/year)
-70,7
-34,8
-11,7
SEC class
A+
A
E
Declared type
-
Two-way
Type of drive installed
-
Stepless adjustment system
Type of heat recovery system
-
Other (diaphragm)
Thermal efficiency of heat recovery
%
78,2
Maximum flow rate
m3/h
280
Power consumption by the fan drive system
W
125
Sound power level
dB(A)
44
Reference flow rate
m3/s
0,05
Reference pressure difference
Pa
50
SPI
W/(m3/h)
0,35
Control factor and type of control
-
0.85 –central control
Maximum internal and external air leakage rates
%
Internal –5
External –5
Location and description of the visual warning for filter
replacement
-
Alarms displayed on the control panel
screen
Website address for downloading pre-assembly/dismantling
instructions
-
www.frapol.com.pl
AEC (polar, temperate and tropical climates)
kWh/year
895
358
313
AHS (polar, temperate and tropical climates)
kWh
8432
4310
1949

Operation and Maintenance Manual, OnyX Sky Heat Recovery Units, 2022/01
Frapol Sp. z o.o. reserves the right to introduce changes without any prior notice. Page 20
3.8.2 OnyX Sky 500
Product data sheet (technical data in accordance with Regulation of the European Commission No. 1254/14)
Name or trade mark of the Supplier
-
Frapol Sp. z o.o.
Model identifier
-
OnyX Sky 500
SEC (polar, temperate and tropical climates)
kWh/(m2/year)
-73,7
-35.7
-11.3
SEC class
A+
A
E
Declared type
-
Two-way
Type of drive installed
-
Stepless adjustment system
Type of heat recovery system
-
Other (diaphragm)
Thermal efficiency of heat recovery
%
86,6
Maximum flow rate
m3/h
479
Power consumption by the fan drive system
W
242
Sound power level
dB(A)
49
Reference flow rate
m3/s
0,09
Reference pressure difference
Pa
50
SPI
W/(m3/h)
0,41
Control factor and type of control
-
0.85 –central control
Maximum internal and external air leakage rates
%
Internal –3
External –3
Location and description of the visual warning for filter
replacement
-
Alarms displayed on the control panel
screen
Website address for downloading pre-assembly/dismantling
instructions
-
www.frapol.com.pl
AEC (polar, temperate and tropical climates)
kWh/year
950
413
368
AHS (polar, temperate and tropical climates)
kWh
8877
4538
2052
3.8.3 OnyX Sky 750
Product data sheet (technical data in accordance with Regulation of the European Commission No. 1254/14)
Name or trade mark of the Supplier
-
Frapol Sp. z o.o.
Model identifier
-
OnyX Sky 750
SEC (polar, temperate and tropical climates)
kWh/(m2/year)
-81,7
-37.9
-12.8
SEC class
A+
A
E
Declared type
-
Two-way
Type of drive installed
-
Stepless adjustment system
Type of heat recovery system
-
Other (diaphragm)
Thermal efficiency of heat recovery
%
86,2
Maximum flow rate
m3/h
750,2
Power consumption by the fan drive system
W
337
Sound power level
dB(A)
47
Reference flow rate
m3/s
0,14
Reference pressure difference
Pa
50
SPI
W/(m3/h)
0,349
Control factor and type of control
-
0.85 –central control
Maximum internal and external air leakage rates
%
Internal –3
External –2
Location and description of the visual warning for filter
replacement
-
Alarms displayed on the control panel
screen
Website address for downloading pre-assembly/dismantling
instructions
-
www.frapol.com.pl
AEC (polar, temperate and tropical climates)
kWh/year
898
361
316
AHS (polar, temperate and tropical climates)
kWh
8856
4527
2047
This manual suits for next models
5
Table of contents
Popular Heating System manuals by other brands

UTEK
UTEK FLAT GUIDE FOR INSTALLATION, USE AND MAINTENANCE