Frico AGS5500 User manual

AGS5500 / AGR5500
Original instructions
.... 17
SE .... 21
GB .... 24
NO .... 28
FR .... 32
DE
.... 36
ES .... 40
NL .... 44
IT .... 48
PL .... 52
RU
AGS5500
AGR5500

AGS5500/AGR5500
2
RU Страницы в начале Инструкции состоят в основном из рисунков, схем и
таблиц. Перевод встречающегося там текста приведен в разделе RU.
Introduktionssidorna består huvudsakligen av bilder. För översättning av de
engelska texter som används, se respektive språksidor.
SE
The introduction pages consist mainly of pictures. For translation of the
English texts used, see the respective language pages.
GB
Introduksjonssidene består hovedsakelig av bilder. For oversettelse av de
engelske tekstene, se de respektive språksidene
NO
Les pages de présentation contiennent principalement des images. Pour la
traduction des textes, consulter la page correspondant à la langue souhaitée.
FR
Die Einleitungsseiten bestehen hauptsächlich aus Bildern. Für die Übersetzung
der verwendetenTexte in englischer Sprache, siehe die entsprechenden
Sprachseiten.
DE
Las páginas introductorias contienen básicamente imágenes. Consulte la
traducción de los textos en inglés que las acompañan en las páginas del
idioma correspondiente.
ES
De inleidende pagina's bevatten hoofdzakelijk afbeeldingen.Voor een vertaling
van de gebruikte Engelse teksten, zie de pagina's van de resp. taal.
NL
Le pagine introduttive contengono prevalentemente immagini. Per le
traduzioni dei testi scritti in inglese, vedere le pagine nelle diverse lingue.
IT
Początkowe strony zawierają głównie rysunki. Tłumaczenie wykorzystanych
tekstów angielskich znajduje się na odpowiednich stronach językowych.
PL

AGS5500/AGR5500
3
Fig.1A. Dimensions AGS5500
L766
4087
147
500
450
30
1,5 m: 4 x M10
2, 2,5 m: 6 x M10
3 m: 8 x M10
605
555
L
[mm]
AGS5515 1515
AGS5520 2010
AGS5525 2520
AGS5530 3030
PC board (2 x for AGS5525/5530)
WL WH
AGS5515 DN25 (1") DN20 (3/4")
AGS5520 DN32 (1 1/4") DN25 (1")
AGS5525 DN32 (1 1/4") DN32 (1 1/4")
AGS5530 DN40 (1 1/2") DN32 (1 1/4")
Inside thread
SIRe
AGS5500

AGS5500/AGR5500
4
30
500
40
555
605
87
147
1200
470
L
450
1,5 m: 4 x M10
2, 2,5 m: 6 x M10
3 m: 8 x M10
L
[mm]
AGR5515 1515
AGR5520 2010
AGR5525 2520
AGR5530 3030
WL WH
AGR5515 DN25 (1") DN20 (3/4")
AGR5520 DN32 (1 1/4") DN25 (1")
AGR5525 DN32 (1 1/4") DN32 (1 1/4")
AGR5530 DN40 (1 1/2") DN32 (1 1/4")
Inside thread
AGR5500
Fig.1B. Dimensions AGR5500

AGS5500/AGR5500
5
30
500
40
555
605
87
147
1200
470
L
450
1,5 m: 4 x M10
2, 2,5 m: 6 x M10
3 m: 8 x M10
93040
470 30
30
30
470
470
40
40
965 965
990 990
970
AGR5500
Fig.1C.

AGS5500/AGR5500
6
1 2 3
Fig. 3. Installation alternatives
Fig. 4A. AGS5500: Open the unit
min 200
min 80
Fig. 2. Minimum distance
Fig. 4B. AGR5500: Open the unit
1 2 3

AGS5500/AGR5500
7
20 mm
20 mm
20 mm
AGS/AGR5500 + GWB640
AB
CD
EF
GWB640
40
640
120
Type Wall bracket
GWB640
AGS5515/AGR5515 2 pcs
AGS5520/AGR5520 3 pcs
AGS5525/AGR5525 3 pcs
AGS5530/AGR5530 4 pcs
Fig. 5.Wall bracket GWB640

AGS5500/AGR5500
8
SIReBN
SIReAC
SIReAA
SIReRTX 70x33x23 mm
SIReUR 114x70x50 mm
SIReWTA
SIReCJ4
SIReCJ6
SIReCC603 3 m
SIReCC605 5 m
SIReCC610 10 m
SIReCC615 15 m
SIReCC640 40 m
SIReCC403 3 m
SIReCC405 5 m
SIReCC410 10 m
SIReCC415 15
SIRe
C
SIReBN
SIReAC/SIReAA
SIReRTX
SIReUR
SIReWTA
SIReCC
SIReCJ4/SIReCJ6
VKF15LF
DN15
VKF15NF
DN15
VKF20
DN20
VKF25
DN25
VKF32
DN32
SD230
BPV10
SDM24
ST23024
VOT15 DN15
VOT20 DN20
VOT25 DN25
VKF
SDM24 ST23024
SD230 BPV10
VKF
VLSP VLP
VOT
GWB640 AGS/AGR5500
L: 640 mm
GP1010 AGS/AGR5500
L: 1 m
AGR55XTT15 AGR5515
H: 133-200 mm
AGR55XTT20 AGR5520
H: 133-200 mm
AGR55XTT25 AGR5525
H: 133-200 mm
AGR55XTT30 AGR5530
H: 133-200 mm
GWB640
GP1010 AGR55XTT
See separate manual
Accessories

AGS5500/AGR5500
9
AGS5515/AGR5515, AGS5520/AGR5520
C°
C°
H1 H2N
Id RoomC2 C1 Actuator 230V Supply 230V
PE L
N
Heating
L
N
~
L
N F2 F3F1 F4 F5
Trafo
N
L
Motor
SIRe B1N
Trafo
Motor
protection
Internal
sensor
AGS/AGR5520
AGS/AGR5515
C°
Black
Blue
230V
200V
175V
145V
120V
100V
N
Transformer
230V
200V
175V
145V
120V
100V
Transformer
Yellow
Red
Brown
Black
Green
N
Orange
Blue
230V~

AGS5500/AGR5500
10
AGS5525/AGR5525, AGS5530/AGR5530
C°
C°
H1 H2N
Id RoomC2 C1 Actuator 230VSupply 230V
PE L
N
Heating
L
N
~
L
N F2 F3F1 F4 F5
Trafo
N
L
Motor
SIRe B1N
Trafo
Motor
protection
Internal
sensor
C°
C°
H1 H2N
Id RoomC2 C1 Actuator 230VSupply 230V
PE L
N
Heating
L
N
~
L
N F2 F3F1 F4 F5
Trafo
N
L
Motor
SIRe B1N
Trafo
Motor
protection
Internal
sensor
C°
Black
Blue
230V
200V
175V
145V
120V
100V
N
Transformer
230V
200V
175V
145V
120V
100V
Transformer
Yellow
Red
Brown
Black
Green
N
Orange
Blue
Black
Blue
230V
200V
175V
145V
120V
100V
N
Transformer
AGS/AGR5530
AGS/AGR5525
230V~

AGS5500/AGR5500
11
SIReB Basic
AGS5500A, AGR5500A
Wiring diagrams for SIReAC Competent, see manual for SIRe.
C2
X5
C1
X4
ROOM
X3
Pot.
Unit ID ACTUATORSUPPLY
N L NL
PE
L
~
230V~
C2
X5
C1
X4
ROOM
X3
Pot.
Unit ID ACTUATORSUPPLY
N L NL
PE
L
~
230V~
C2
X5
C1
X4
ROOM
X3
Pot.
Unit ID ACTUATORSUPPLY
N L NL
PE
L
~
230V~
SIReCC6XX (max 50 m)
SIReCC6XX
(max 50 m)
SIReCC6XX
(max 50 m)
SIReUB1
SIReRTX
(optional)
L=2m
SIReB1/B2/B1EC
SIReB1/B2/B1EC
SIReB1/B2/B1EC

AGS5500/AGR5500
12
SIReB Basic
AGS5500W, AGR5500W
Wiring diagrams for SIReAC Competent and SIReAA Advanced, see manuals for SIRe.
C2
X5
C1
X4
ROOM
X3
Pot.
Unit ID ACTUATORSUPPLY
N L NL
PE
L
~
230V~
C2
X5
C1
X4
ROOM
X3
Pot.
Unit ID ACTUATORSUPPLY
N L NL
PE
L
~
230V~
C2
X5
C1
X4
ROOM
X3
Pot.
Unit ID ACTUATORSUPPLY
N L NL
PE
L
~
230V~
SIReCC6XX (max 50 m)
SIReB1/B2/B1EC
SIReB1/B2/B1EC
SIReB1/B2/B1EC
SIReCC6XX
(max 50 m)
SIReCC6XX
(max 50 m)
SIReUB1
SIReRTX
(optional)
SD230
SD230
SD230
L=1,5m
L=2m

AGS5500/AGR5500
13
Output charts water AGS5500/AGR5500 WL
Supply water temperature: 80 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*1
Water temperature: 80/60 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Return
water temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
Output*2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
AGx5515WL max 5500 31 40 0,19 1,3 47 43 0,58 9,8
min 2500 14 33 0,07 0,2 28 51 0,35 3,7
AGx5520WL max 8250 49 34 0,26 2,4 78 46 0,95 27,3
min 3750 21 26 0,09 0,4 47 55 0,57 10,4
AGx5525WL max 11000 64 34 0,34 4,4 100 45 1,22 49,1
min 5000 29 26 0,13 0,8 61 54 0,74 18,7
AGx5530WL max 13750 78 36 0,44 4,9 124 45 1,51 43,2
min 6250 35 29 0,17 0,9 73 52 0,89 16,6
Supply water temperature: 70 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*1
Water temperature: 70/50 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Return
water temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
Output*2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
AGx5515WL max 5500 32 44 0,30 2,9 37 38 0,45 6,2
min 2500 14 35 0,10 0,4 22 44 0,27 2,4
AGx5520WL max 8250 48 38 0,36 4,5 62 40 0,75 1 7, 7
min 3750 22 28 0,13 0,7 37 47 0,46 6,8
AGx5525WL max 11000 63 38 0,47 8,2 80 39 0,97 31,8
min 5000 29 28 0,17 1,3 49 47 0,59 12,3
AGx5530WL max 13750 81 41 0,67 10,6 98 39 1,19 28,9
min 6250 36 32 0,23 1,6 58 45 0,70 11,2
*1) Recommended outlet air temperature for good comfort and optimized output.
*2) Nominal output at given supply and return water temperature.
Supply water temperature: 60 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*1
Water temperature: 60/40 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Return
water temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
Output*2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
AGx5515WL max 5500 33 48 0,63 11,9 27 32 0,32 3,4
min 2500 15 37 0,16 0,9 16 37 0,19 1,3
AGx5520WL max 8250 48 42 0,67 14,4 46 34 0,55 10,1
min 3750 21 31 0,18 1,2 28 40 0,34 4,0
AGx5525WL max 11000 65 45 1,06 38,2 59 34 0,72 18,1
min 5000 30 32 0,26 2,7 36 39 0,44 7, 2
AGx5530WL max 13750 81 45 1,30 35,0 71 33 0,87 1 7, 0
min 6250 36 35 0,35 3,4 42 38 0,51 6,7
Supply water temperature: 55 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*1
Water temperature: 55/35 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Return
water temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
Output*2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
AGx5515WL max 5500 32 48 1,14 37,4 21 29 0,26 2,2
min 2500 14 38 0,21 1,5 13 33 0,15 0,9
AGx5520WL max 8250 49 46 1,31 52,4 37 31 0,45 7, 0
min 3750 21 32 0,23 2,0 23 36 0,28 2,8
AGx5525WL max 11000 62 46 1,68 94,3 49 31 0,59 12,6
min 5000 29 34 0,33 4,2 30 36 0,36 5,1
AGx5530WL max 13750 78 46 2,10 83,9 58 30 0,70 12,0
min 6250 37 37 0,49 6,4 34 34 0,42 4,8

AGS5500/AGR5500
14
Output charts water AGS5500/AGR5500WH
Supply water temperature: 110 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*1
Water temperature: 110/80 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Return
water temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
Output*2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
AGx5515WH max 5500 32 47 0,13 1,2 51 45 0,42 10,9
min 2500 14 34 0,05 0,2 31 55 0,26 4,4
AGx5520WH max 8250 48 42 0,17 0,8 85 48 0,70 10,7
min 3750 22 32 0,07 0,1 52 59 0,43 4,2
AGx5525WH max 11000 62 42 0,22 0,7 111 48 0,92 10,0
min 5000 29 33 0,09 0,1 68 58 0,56 3,9
AGx5530WH max 13750 80 47 0,31 1,0 138 48 1,14 10,6
min 6250 36 37 0,12 0,2 87 59 0,72 4,5
Supply water temperature: 90 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*1
Water temperature: 90/70 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Return
water temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
Output*2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
AGx5515WH max 5500 32 52 0,20 2,9 41 40 0,51 16,1
min 2500 15 39 0,07 0,4 26 48 0,31 6,5
AGx5520WH max 8250 48 47 0,28 1,9 69 43 0,85 15,8
min 3750 22 36 0,10 0,3 42 51 0,52 6,1
AGx5525WH max 11000 63 47 0,36 1,7 90 42 1,11 14,7
min 5000 29 36 0,13 0,3 55 51 0,68 5,7
AGx5530WH max 13750 77 50 0,47 2,2 11 3 42 1,38 15,8
min 6250 36 40 0,18 0,4 71 51 0,87 6,7
*1) Recommended outlet air temperature for good comfort and optimized output.
*2) Nominal output at given supply and return water temperature.
Supply water temperature: 80 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*1
Water temperature: 80/60 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Return
water temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
Output*2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
AGx5515WH max 5500 33 58 0,35 8,3 34 36 0,41 11,2
min 2500 14 40 0,09 0,6 21 43 0,26 4,5
AGx5520WH max 8250 48 50 0,39 3,7 57 38 0,70 10,9
min 3750 22 38 0,13 0,5 35 45 0,42 4,3
AGx5525WH max 11000 62 50 0,51 3,3 74 38 0,91 10,1
min 5000 29 38 0,17 0,4 46 45 0,56 4,0
AGx5530WH max 13750 81 54 0,75 5,3 92 38 1,12 11,0
min 6250 35 40 0,22 0,6 58 45 0,70 4,7
Supply water temperature: 82 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*1
Water temperature: 82/71 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m3/h]
Output
[kW]
Return
water temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
Output*2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPA]
AGx5515WH max 5500 31 54 0,27 5,1 40 39 0,89 47,9
min 2500 14 40 0,08 0,6 25 47 0,55 19,0
AGx5520WH max 8250 48 50 0,37 3,3 67 42 1,49 47,6
min 3750 22 37 0,12 0,4 41 50 0,91 18,2
AGx5525WH max 11000 63 50 0,48 3,0 88 42 1,96 44,8
min 5000 29 38 0,16 0,4 54 50 1,19 1 7, 1
AGx5530WH max 13750 79 52 0,64 4,0 111 42 2,47 47,1
min 6250 36 40 0,21 0,5 70 51 1,55 19,6

AGS5500/AGR5500
15
AGS5500 A without heat 1
AGS5500 WL with water heat, coil for low temperature water < 80/60 °C 2
See www.frico.se for additional calculations.
Protection class: IP24.
CE compliant.
*1) Lowest/highest airflow of totally 5 fan steps.
*2) Sound power (LWA) measurements according to ISO 27327-2: 2014, Installation type E.
*3) Sound pressure (LpA). Conditions: Distance to the unit 5 metres. Directional factor: 2. Equivalent
absorption area: 200 m². At lowest/highest airflow.
*4) ∆t = temperature rise of passing air at maximum heat output and lowest/highest airflow.
*5) Applicable at water temperature 60/40 °C, air temperature, in +18 °C.
*6) Applicable at water temperature 80/60 °C, air temperature, in +18 °C.
Type Output
[kW]
Airflow*1
[m3/h]
Sound
power*2
[dB(A)]
Sound
pressure*3
[dB(A)]
Voltage
motor
[V]
Amperage
motor
[A]
Length
[mm]
Weight
[kg]
AGS5515A 0 2500/5800 86 51/70 230V~ 8,1 1515 114
AGS5520A 0 3750/8700 88 52/72 230V~ 12,1 2010 149
AGS5525A 0 5000/11600 89 53/73 230V~ 16,2 2520 189
AGS5530A 0 6250/14500 90 55/74 230V~ 20,3 3030 229
Type Output*5
[kW]
Airflow*1
[m3/h]
∆t*4,5
[°C]
Water
volume
[l]
Sound
power*2
[dB(A)]
Sound
pressure*3
[dB(A)]
Voltage
motor
[V]
Amperage
motor
[A]
Length
[mm]
Weight
[kg]
AGS5515WL 26 2500/5500 19/14 4,0 85 50/69 230V~ 7, 7 1515 131
AGS5520WL 45 3750/8250 22/16 8,1 86 51/70 230V~ 11,6 2010 177
AGS5525WL 59 5000/11000 21/16 9,2 88 52/72 230V~ 15,4 2520 222
AGS5530WL 71 6250/13750 20/15 11,0 89 54/73 230V~ 19,3 3030 268
AGS5500 WH with water heat, coil for high temperature water 580/60 °C 2
Technical specifications AGS5500
Type Output*6
[kW]
Airflow*1
[m3/h]
∆t*4,6
[°C]
Water
volume
[l]
Sound
power*2
[dB(A)]
Sound
pressure*3
[dB(A)]
Voltage
motor
[V]
Amperage
motor
[A]
Length
[mm]
Weight
[kg]
AGS5515WH 34 2500/5500 25/18 3,8 85 50/69 230V~ 7, 7 1515 129
AGS5520WH 57 3750/8250 27/20 4,9 86 51/70 230V~ 11,6 2010 169
AGS5525WH 74 5000/11000 27/20 6,4 88 52/72 230V~ 15,4 2520 213
AGS5530WH 92 6250/13750 27/20 7, 6 89 54/73 230V~ 19,3 3030 258

AGS5500/AGR5500
16
AGR5500 A without heat 1
AGR5500 WL with water heat, coil for low temperature water < 80/60 °C 2
See www.frico.se for additional calculations.
Protection class: IP24.
CE compliant.
*1) Lowest/highest airflow of totally 5 fan steps.
*2) Sound power (LWA) measurements according to ISO 27327-2: 2014, Installation type E.
*3) Sound pressure (LpA). Conditions: Distance to the unit 5 metres. Directional factor: 2. Equivalent
absorption area: 200 m². At lowest/highest airflow.
*4) ∆t = temperature rise of passing air at maximum heat output and lowest/highest airflow.
*5) Applicable at water temperature 60/40 °C, air temperature, in +18 °C.
*6) Applicable at water temperature 80/60 °C, air temperature, in +18 °C.
AGR5500 WH with water heat, coil for high temperature water 580/60 °C 2
Technical specifications AGR5500
Type Output
[kW]
Airflow*1
[m3/h]
Sound
power*2
[dB(A)]
Sound
pressure*3
[dB(A)]
Voltage
motor
[V]
Amperage
motor
[A]
Length
[mm]
Weight
[kg]
AGR5515A 0 2500/5800 86 51/70 230V~ 8,1 1515 134
AGR5520A 0 3750/8700 88 52/72 230V~ 12,1 2010 174
AGR5525A 0 5000/11600 89 53/73 230V~ 16,2 2520 219
AGR5530A 0 6250/14500 90 55/74 230V~ 20,3 3030 269
Type Output*5
[kW]
Airflow*1
[m3/h]
∆t*4,5
[°C]
Water
volume
[l]
Sound
power*2
[dB(A)]
Sound
pressure*3
[dB(A)]
Voltage
motor
[V]
Amperage
motor
[A]
Length
[mm]
Weight
[kg]
AGR5515WL 26 2500/5500 19/14 4,0 85 50/69 230V~ 7, 7 1515 151
AGR5520WL 45 3750/8250 22/16 8,1 86 51/70 230V~ 11,6 2010 208
AGR5525WL 59 5000/11000 21/16 9,2 88 52/72 230V~ 15,4 2520 252
AGR5530WL 71 6250/13750 20/15 11,0 89 54/73 230V~ 19,3 3030 308
Type Output*6
[kW]
Airflow*1
[m3/h]
∆t*4,6
[°C]
Water
volume
[l]
Sound
power*2
[dB(A)]
Sound
pressure*3
[dB(A)]
Voltage
motor
[V]
Amperage
motor
[A]
Length
[mm]
Weight
[kg]
AGR5515WH 34 2500/5500 25/18 3,8 85 50/69 230V~ 7, 7 1515 149
AGR5520WH 57 3750/8250 27/20 4,9 86 51/70 230V~ 11,6 2010 194
AGR5525WH 74 5000/11000 27/20 6,4 88 52/72 230V~ 15,4 2520 243
AGR5530WH 92 6250/13750 27/20 7, 6 89 54/73 230V~ 19,3 3030 298

AGS5500/AGR5500
28
FR
Généralités
Lisez attentivement les présentes consignes
avant d'installer et d'utiliser l'appareil.
Conservez ce manuel afin de pouvoir le
consulter ultérieurement.
Le produit doit être utilisé uniquement en
conformité avec les consignes de montage et
le mode d’emploi. La garantie n’est valable
que si l’utilisation du produit est conforme
aux indications et consignes.
Fonctionnement
L'air est aspiré par la grille frontale de
l'appareil et rejeté vers le bas de manière à
minimiser la déperdition de chaleur.
Pour un rendu maximal, la longueur de
l'appareil doit être égale à la largeur de
l'ouverture de la porte.
La grille la plus près de la porte est
orientable ; elle est en principe dirigée vers
l'extérieur de manière à optimiser la barrière
créée contre l'air froid de l'extérieur.
L'efficacité du rideau d'air dépend de
la température de l'air, des variations de
pression dans l'ouverture de porte et, le cas
échéant, de la pression du vent.
REMARQUE : une pression négative à
l'intérieur du local réduit considérablement
l'efficacité du rideau d'air. La ventilation doit
donc être équilibrée.
Application
Le rideau d'air AGS5500/AGR5500 est fourni
sans chauffage ou avec chauffage à eau
chaude. Le AGS5500/AGR5500 est conçu
pour les entrées et portes avec une hauteur
d'installation jusqu'à 5,5 m. L'AGS5500 est
monté en surface tandis que l'AGR5500 est
prévu pour un montage encastré. Indice de
protection : IP24.
Installation électrique
L’installation, qui doit être précédée
d’un interrupteur omnipolaire avec une
séparation de contact de 3 mm au moins,
doit être réalisée par un installateur qualifié,
conformément à la règlementation IEE sur
les branchements électriques en vigueur dans
son édition la plus récente.
Le système de régulation est préinstallé
dans le rideau d'air à l'aide d'une carte de
régulation intégrée. SIRe est préprogrammé
avec des raccords rapides. Les câbles
modulaires sont raccordés au circuit imprimé.
Les modèles AGS5525/5530 et AGR5525/5530
disposent de deux cartes SIRe, l'une étant un
module esclave. Voir la notice du SIRe.
Le fonctionnement (230 V~) est raccordé
au bornier du bloc de fonction sur le haut de
l'appareil. Voir les schémas de raccordement.
Raccordement de la batterie à eau
chaude (W).
L'installation doit être effectuée par un
installateur agréé.
La batterie à eau chaude est constituée
de tubes de cuivre dotés d'ailettes en
aluminium ; elle est conçue pour être
raccordée à un circuit fermé d'eau chaude.
La batterie à eau chaude ne doit pas être
branchée sur un circuit hydraulique à
pression standard, ni sur un circuit ouvert.
Noter que l'appareil doit être précédé d'une
vanne de régulation ; voir le kit de vannes
Frico.
La batterie à eau est connectée au côté
supérieur de l'unité via des connections, voir
fig. 1A-B.
Les raccordements à la batterie à eau
chaude doivent être dotés de vannes d'arrêt
permettant une dépose aisée. La batterie est
munie d’une vanne de vidange. Un purgeur
d'air doit être raccordé à un point haut du
circuit hydraulique.
Les purgeurs d'air ne sont pas inclus.
Montage
Le rideau d'air est monté horizontalement,
la grille de soufflage orientée vers le bas et
le plus près possible de la porte. Plusieurs
appareils peuvent être montés côte à côte
pour les entrées très larges. La trappe
d’entretien doit être accessible, rien ne doit
empêcher son ouverture complète.
L'appareil est doté de 4 écrous fixes de type
M10 (6 sur les modèles de 2 et 2,5 mètres et
Consignes de montage et mode d'emploi
8 sur ceux de 3 mètres) sur sa face supérieure
pour un montage plafond à l'aide de tiges
filetées, ou pour un montage mural à l'aide
des accessoires prévus à cet effet (consoles).
Voir fig. 5.

AGS5500/AGR5500
29
FR
Réglage de l'appareil et du débit d'air
La direction et la vitesse du jet d'air doivent
être réglés en tenant compte de la charge sur
l’ouverture. Les pressions d'air présentes au
niveau de l'entrée influent sur le débit d'air, le
repoussant vers l'intérieur (lorsque le local est
chauffé et que l'air extérieur est froid).
Le débit d'air doit par conséquent être
orienté vers l'extérieur de manière à
contrebalancer la charge. D'une manière
générale, plus la charge est élevée, plus l'angle
doit être important.
Entretien, réparations et maintenance
Opérations initiales pour toute intervention
d'entretien, de réparation et de maintenance :
1. Déconnecter l'alimentation électrique.
2. Pour ouvrir la trappe de visite, ouvrir la
grille de prise d'air, puis desserrer les vis
situées sur la face inférieure de l'appareil,
comme illustré sur la figure 4A-B.
Filtre (W)
La distance entre les plaques de batterie ainsi
que le diamètre des ouvertures de la grille
de prise d'air protègent l'appareil contre les
corps étrangers et un éventuel colmatage,
rendant inutile la présence d'un filtre spécial.
Réglage initial de la vitesse de ventilation
La vitesse de ventilation lorsque la porte
s'ouvre est réglée à l'aide de la commande.
Garder à l'esprit le fait qu'un réglage fin de
l'orientation et de la vitesse du débit d'air
peut s'imposer en fonction de la charge.
Entretien
Les moteurs du ventilateur et les autres
organes de l'appareil ne nécessitant aucune
maintenance, seul un nettoyage régulier est
nécessaire. La fréquence de nettoyage dépend
des conditions locales. Un nettoyage s'impose
cependant au moins deux fois par an. Les
grilles d'admission et de diffusion, la turbine
et les autres éléments peuvent être nettoyés
à l'aspirateur, ou essuyés à l'aide d'un chiffon
humide. Lors du passage de l’aspirateur,
utiliser une brosse afin de ne pas endommager
les pièces fragiles. Ne pas utiliser de produits
de nettoyage très alcalins ou acides.
Surchauffe
Tous les moteurs sont équipés d'une sécurité
thermique intégrale. Elle fonctionne en
arrêtant le fonctionnement du rideau d'air
si la température du moteur est trop élevée.
Le disjoncteur différentiel se réinitialise
automatiquement lorsque la température
revient dans la plage admissible.
Commande de la température
La commande de la température du SIRe
maintient la température d'échappement.
Si la température est supérieure, l'alarme
de surchauffe se déclenche. Pour plus
d'information, voir le manuel du SIRe.
Remplacement d'un ventilateur
1.Déterminer quel ventilateur ne fonctionne
pas.
2.Débrancher ses câbles d'alimentation.
3.Retirer ses vis de fixation et ôter le
ventilateur.
4.Mettre en place le nouveau ventilateur en
suivant les étapes ci-dessus dans l’ordre
inverse.
Remplacement de la batterie à eau chaude.
1.Couper l'alimentation d'eau de l'appareil.
2.Déconnecter les canalisations de la batterie
à eau chaude.
3.Retirer les vis de fixation de la batterie et la
déposer.
4.Mettre en place la nouvelle batterie en
inversant les étapes ci-dessus.
Purge de la batterie à eau chaude (W)
La purge est située sous la batterie, du côté
du raccord. On peut y accéder par la trappe
d'entretien.

AGS5500/AGR5500
30
FR
Sécurité
• Veiller à ce que les zones à proximité
des grilles de prise et de sortie d'air
soient libres de tout objet susceptible de
provoquer des obstructions.
• Les surfaces de l'appareil peuvent être
brûlantes lors de son fonctionnement et de
son refroidissement !
• L'appareil doit être soulevé à l'aide
d'équipement de levage.
• Les enfants de plus de 8 ans peuvent
utiliser cet appareil, tout comme les
personnes aux capacités physiques,
mentales ou sensorielles réduites,
ou manquant d’expérience ou de
connaissances, si une personne les a
conseillés ou formés à son utilisation et
aux dangers possibles. Les enfants ne
doivent pas jouer avec cet appareil. Le
nettoyage et l'entretien de l'appareil ne
doivent pas être confiés aux enfants sans
surveillance.
Dépannage
Si les ventilateurs ne fonctionnent pas ou ne souff-
lent pas suffisamment, contrôler les points sui-
vants :
• Propreté de la grille/du filtre de prise d'air.
• Vérifier les fonctions et réglages du système
de commande SIRe, voir le manuel SIRe.
Si le chauffage ne fonctionne pas, contrôler les
points suivants :
• Vérifier les fonctions et réglages du système
de commande SIRe, voir le manuel SIRe.
Pour les appareils à batterie à eau chaude, contrôler
également les points suivants :
• Purge de la batterie à eau chaude.
• Débit d’eau suffisant.
• Eau entrante suffisamment chaude.
Si le problème persiste, faire appel à un
technicien d'entretien qualifié.

AGS5500/AGR5500
31
FR
*1)Température d'air de sortie recommandée pour un confort et un rendement optimaux.
*2) Puissance nominale à une température d'eau spécifique d'alimentation et de retour.
Output*4,5 [kW]
Airflow*1[m3/h]
Sound power*2 [dB(A)]
Sound pressure*3 [dB(A)]
Voltage motor [V]
Amperage motor [A]
Length [mm]
Weight [kg]
Water volume [l]
• Dimensions
• Inside thread
• Minimum distance
• Installation alternatives
• Open the unit
• Wall bracket
• pcs
• Accessories
• See separate manual
• Wiring diagrams for xxx, see manual for
SIRe
= Puissance
= Débit d'air
= Puissance acoustique
= Pression acoustique
= Tension moteur
= Intensité moteur
= Longueur
= Poids
= Volume d'eau
*1) Débit d’air mini/maxi de 5 étages de ventilation au total.
*2) Mesures de la puissance acoustique (LWA) selon la norme ISO 27327-2 : 2014, Installation de type E.
*3) Pression acoustique (LpA). Conditions : Distance de l’appareil : 5 mètres. Facteur directionnel : 2. Surface
d’absorption : 200 m². Au débit d’air minimal/maximal.
*4) ∆t = augmentation de température sous un débit d’air mini / maxi et une puissance maximale.
*5) Valable pour une temp. d’eau de 60/40 °C, temp. d’air d’entrée +18 °C.
*6) Valable pour une temp. d’eau de 80/60 °C, temp. d’air d’entrée 18 °C.
Tableaux de dimensionnement eau chaude
Traduction des pages de présentation
= Dimensions
= Taraudage intérieur
= Distances minimales
= Autres installations possibles
= Ouvrir l'appareil
= Console de montage
= Pièces
= Accessoires
= Consultez le manuel associé.
= Schémas de raccordement pour xxx et xxx,
voir le manuel de la référence SIRe.
Caractéristiques techniques
Consultez www.frico.fr pour des calculs supplémentaires.
Supply water temperature [°C]
Room temperature [°C]
Outlet air temperature*1[°C]
Water temperature [°C]
Fan position
Airflow [m3/h]
Output*2[kW]
Return water temperature [°C]
Water flow [l/s]
Pressure drop [kPa]
Température de l'eau d'alimentation
Température ambiante
Température de l'air de sortie
Température de l'eau
Position ventilateur
Débit d'air
Puissance
Température retour d'eau
Débit hydraulique
Perte de charge
=
=
=
=
=
=
=
=
=
=
Indice de protection : IP24.
Marquage CE.
Other manuals for AGS5500
7
This manual suits for next models
31
Table of contents
Languages:
Other Frico Ventilation Hood manuals