Friedrich VRPXEMWRT2 User manual

VRPXEMWRT2
Wireless VRP®Energy Management Wall
Controller with an Occupancy Sensor
INSTRUCTION MANUAL
PART NO. 95200303 Rev 00
VPXEMWRT2-Thermostat Manual_pkg.indd 1 2017-12-15 3:37 PM

VPXEMWRT2-Thermostat Manual_pkg.indd 2 2017-12-15 3:37 PM

3
Table of Contents
Introduction............................................................................................................ 5
Before you begin ................................................................................................... 7
Wall Controller Installation..................................................................................... 9
Pairing the Wall Controller and the Receiver......................................................... 9
Mounting the Wall Controller to the wall ................................................................ 9
Installing the Wireless Receiver ..................................................................... 10-11
Wall Controller Wiring Installation.............................................................................12-14
Wall Controller Conguration............................................................................... 15
Setting the Wall Controller Clock................................................................................... 16
Entering the Room Number........................................................................................... 17
Conguring the Energy Saving Settings ....................................................................... 18
Testing the Wall Controller............................................................................................. 19
Custom Energy Savings Settings.................................................................................. 20
Using the Wall Controller Settings Screens......................................................... 21
01 – FAN CONTROL MODE ............................................................................... 22
02 – 1ST STAGE DIFFERENTIAL - HEAT ............................................................ 23
03 – 2ND STAGE DIFFERENTIAL - HEAT............................................................ 24
04 – 1ST STAGE DIFFERENTIAL - COOL ......................................................... 25
05 – INCIDENTAL OCCUPANCY THRESHOLD................................................. 26
06 – NIGHT OCCUPANCY THRESHOLD........................................................... 27
07 – NA................................................................................................................ 28
08 – NIGHT OCCUPANCY START ..................................................................... 29
09 – NIGHT OCCUPANCY END ......................................................................... 30
10 – NA................................................................................................................ 31
11 – NA................................................................................................................ 32
12 – TEMPERATURE SETBACK DELAY - HEAT............................................... 33
13 – MINIMUM SETBACK TEMPERATURE ...................................................... 34
14 – TEMPERATURE SETBACK DELAY - COOL .............................................. 35
15 – MAXIMUM SETBACK TEMPERATURE...................................................... 36
16 – NA................................................................................................................ 37
17 – MINIMUM SET POINT................................................................................. 38
18 – MAXIMUM SET POINT ............................................................................... 39
VPXEMWRT2-Thermostat Manual_pkg.indd 3 2017-12-15 3:37 PM

4
Table of Contents
19 – TEMPERATURE CONTROL MODE ........................................................... 40
20 – AUTO CHANGEOVER SET POINT OFFSET (DEAD BAND)..................... 41
21 – SETBACK SET POINTS / AUTO-RESTORE .............................................. 42
22 – AUTOMATIC HUMIDITY CONTROL†.......................................................... 43
23 – TEMPERATURE CALIBRATION ................................................................. 44
Wall Controller Maintenance ............................................................................... 45
Replacing Wall Controller Batteries..................................................................... 46
Troubleshooting................................................................................................... 47
Error Codes ......................................................................................................... 47
Wall Controller is not controlling the VRP unit..................................................... 48
APPENDIX 1 - Energy Saving Presets................................................................ 49
APPENDIX 2 - Glossary...................................................................................... 50
Technical Specications ...................................................................................... 51
VPXEMWRT2-Thermostat Manual_pkg.indd 4 2017-12-15 3:37 PM

5
Introduction
Friedrich VRPXEMWRT2 Energy Management Wall Controllers for the hospitality
industry deliver unprecedented energy savings without compromising guest
comfort. Integrated occupancy sensor uses a combination of motion and thermal
sensing technologies for accurate occupancy detection. Reliable occupancy
detection allows saving energy when rooms are unoccupied.
Energy saving presets eliminate the guesswork and make it easy to adjust the
energy saving settings. (Patent Pending) Fully congurable energy saving
settings allow customizing the Wall Controller energy saving settings to t any
situation.
Large buttons with international symbols make it easy to adjust the temperature
in ±1° °F or °C and control the fan speed.
Built-in wireless mesh-networking enables optional remote management. For
installation of a networking Wall Controller with remote management, refer to the
“Network Installation” manual.
FOR INSTALLATION OF NETWORKING WALL CONTROLLERS WITH REMOTE
MANAGEMENT, REFER TO THE NETWORK INSTALLATION” MANUAL.
LOGIN TO THE REMOTE MANAGEMENT WEBSITE TO CONFIRM THE SERVER IS
CONNECTED TO THE INTERNET BEFORE INSTALLING WALL CONTROLLERS.
DO NOT INSTALL WALL CONTROLLERS IF THE SERVER IS NOT CONNECTED TO
THE INTERNET. STOP THE INSTALLATION AND CONTACT TECHNICAL SUPPORT.
START BY FIRST INSTALLING A WALL CONTROLLER IN THE ROOM CLOSEST TO
THE SERVER.
LOG IN TO REMOTE MANAGEMENT WEBSITE TO CONFIRM THAT THE WALL
CONTROLLER IS ON THE REMOTE MANAGEMENT WEBSITE WITH THE
CORRECT ROOM NUMBER. CONTINUE BY INSTALLING ADDITIONAL WALL
CONTROLLERS IN ADJACENT ROOMS ONLY AFTER CONFIRMING THAT
INSTALLED WALL CONTROLLER(S) HAVE CONNECTED TO THE WIRELESS
NETWORK AND THE REMOTE MANAGEMENT WEBSITE .
IF INSTALLED WALL CONTROLLER(S) ARE NOT CONNECTING TO THE
NETWORK AND DO NOT APPEAR ON THE REMOTE MANAGEMENT WEBSITE
WITH THE CORRECT ROOM NUMBER, STOP THE INSTALLATION AND CONTACT
TECHNICAL SUPPORT THE ROOMS FURTHEST AWAY FROM THE SERVER
SHOULD BE INSTALLED LAST.
VPXEMWRT2-Thermostat Manual_pkg.indd 5 2017-12-15 3:37 PM

6
VPXEMWRT2-Thermostat Manual_pkg.indd 6 2017-12-15 3:37 PM

7
Before You Begin
• Determine the appropriate installation location for the Wall Controller.
The Wall Controller should face the bed area of the room.
• Wall Controller MUST NOT BE INSTALLED NEAR OR ON METAL
STRUCTURES OR SURFACES INCLUDING METAL AIR DUCTING
THAT MAY BE IN THE WALL. METAL STRUCTURES AND SURFACES
SIGNIFICANTLY REDUCE THE RANGE OF THE WIRELESS SIGNAL
VPXEMWRT2-Thermostat Manual_pkg.indd 7 2017-12-15 3:37 PM

8
Wall Controller Installation
Pairing the Wall Controller and the Receiver
Wall Controller and Receiver must be paired in order to operate together. Once
paired, the Wall Controller cannot be used with another wireless Receiver without
repeating the pairing procedure. Friedrich Wall Controllers are pre-linked with the
card in the box.
In case of Network Installation with Remote Management, the Wall Controller and
the Receiver must be paired with a Network Programmer specic to the property
before the installation.
Wall Controller and Receiver must not be powered during the pairing procedure -
remove batteries from the Wall Controller and unplug the Receiver from the
VRP unit during the pairing procedure.
• Plug one programmer connector into the Wall Controller;
• Plug the other programmer connector into the Receiver;
• Push the black button on the programmer. The red light on the programmer
should turn on and remain steadily lit;
If the red light on the programmer is blinking or is not steadily lit, unplug the
programmer from the Wall Controller and the Receiver and repeat the steps
above.
• Unplug the programmer from the Wall Controller and the Receiver;
VPXEMWRT2-Thermostat Manual_pkg.indd 8 2017-12-15 3:37 PM

9
Mounting the Wall Controller to the wall
• Remove the Wall Controller cover;
• Use the supplied wall anchors and mounting screws to secure the Wall
Controller to the wall;
• Insert two (2) AA-cell batteries (not-supplied) into the Wall Controller battery
compartment;
• Follow the “Wall Controller Conguration” instructions;
• Replace the Wall Controller cover and screw in the locking screw;
Wall Controller Installation
VPXEMWRT2-Thermostat Manual_pkg.indd 9 2017-12-15 3:37 PM

10
Installing the Wireless Receiver
• Unplug the VRP®unit from power supply.
• Connect the low voltage wires to screw terminals on the VRP®unit low
voltage terminal block - refer to the Wiring Table to determine proper
connections.
• Ensure that the Wireless Receiver antenna is not touching any metal
components of the VRP®unit.
• Ensure that the Wireless Receiver antenna is facing the Wall Controller
on the wall and is oriented so that any metal parts of the VRP®unit do not
obstruct the wireless communication to the Wall Controller and, in case of a
network installation, to other wireless Receivers and the server.
• Plug the VRP®unit to power supply.
Wall Controller Installation
Receiver
VPXEMWRT2-Thermostat Manual_pkg.indd 10 2017-12-15 3:37 PM

11
Wall Controller Installation
Installing the Wireless Receiver
Mount the Receiver as high as
possible. It MUST be higher than
the VRP unit (top)
To maximize the wireless signal
strength from the Receiver to the
VRPXEMWRT2 Wall Controller,
the Receiver MUST NOT be
installed on the VRP unit.
Note: Depending upon the closet size, an appropriate length of Field Supplied
CAT 6 cable will be required.
VPXEMWRT2-Thermostat Manual_pkg.indd 11 2017-12-15 3:37 PM

12
Wall Controller Wiring Installation
There are four sets of connections for the VRPXEMWRT2 Wall Controller. The
supplied cable from the VRPXEMWRT2 Receiver as shown in Figure 1, has four
color coded wires. Each of these wires must be connected to two Cat6 wires as
shown in Figure 2. Each connection is made with a lever type connector. Four
connectors will be needed to complete unit wiring. Each connector is capable of
connecting three wires.
Figure 1
Figure 2
WIRE COLOR LABEL
Orange Connection 1
V+
Orange
Green/White
Brown Connection 2
D+
Brown
Blue/White
Blue Connection 3
D-
Blue
Brown/White
Green Connection 4
V-
Green
Orange/White
Ground Shield
Wire GND
VPXEMWRT2-Thermostat Manual_pkg.indd 12 2017-12-15 3:37 PM

13
Wall Controller Wiring Installation
General Connection Procedure:
1. Remove 2” of the outer sheath of the
CAT6 cable including the shield and
strip the wires.
2. Insert the specied wire from the
Receiver into a slot of the
lever connector as shown in Figure 3
and close lever as shown in Figure 4.
3. Insert two specied twisted, paired
wires from the CAT6 cable into the
remaining lever connector slot as
shown in Figure 4. Each twisted,
paired wire should be inserted into
its own separate slot in the lever
connector.
4. Close the orange lever on the lever
connector as shown in Figure 5.
Make sure the levers seat properly.
Figure 3.
Figure 4.
Figure 5.
VPXEMWRT2-Thermostat Manual_pkg.indd 13 2017-12-15 3:37 PM

14
Connection 1
Insert the Orange (V+) wire from the Receiver into a lever connector slot and
close the orange lever on the connector.
Insert the twisted Orange and Green/White Cat 6 wires into the remaining lever
connector slot and close the orange lever on the connector.
Connection 2
Insert the Brown (D+) wire from the Receiver into a lever connector slot and
close the orange lever on the connector.
Insert the twisted Brown and Blue/White Cat 6 wires into the remaining lever
connector slot and close the orange lever on the connector.
Connection 3
Insert the Blue (D-) wire from the Receiver into a lever connector slot and close
the orange lever on the connector.
Insert the twisted Blue and Brown/White Cat 6 wire into the remaining lever
connector slot and close the orange lever on the connector.
Connection 4
Insert the Green (V-) wire from the Receiver into a lever connector slot and close
the orange lever on the connector.
Insert the twisted Green and Orange/White Cat 6 wire into the remaining lever
connector slot and close the orange lever on the connector.
WIRE COLOR LABEL
Orange Connection 1
V+
Orange
Green/White
Brown Connection 2
D+
Brown
Blue/White
Blue Connection 3
D-
Blue
Brown/White
Green Connection 4
V-
Green
Orange/White
Ground Shield
Wire GND
Wall Controller Wiring Installation
VPXEMWRT2-Thermostat Manual_pkg.indd 14 2017-12-15 3:37 PM

NOTE: You can access Wall
Controller Conguration settings
at any time by pressing the
“Conguration” button.
NOTE: If the Wall Controller is connected to a network, the equipment and the
energy saving settings congured on the Wall Controller will be ignored and the
settings congured on the Remote Management
Website will be applied.
CONFIGURATION
BUTTON
15
Wall Controller Conguration
Once the Wall Controller is powered, Wall Controller conguration settings will
appear on the Wall Controller screen.
In order to properly operate the VRP unit:
• Set the Wall Controller clock;
• Enter the room number;
• Select Energy Savings Preset;
The Wall Controller conguration screens have a 3-minute time-out. If no action
is taken within three (3) minutes, the Wall Controller will exit conguration
settings.
NOTE: If the Wall Controller is connected to a network, the equipment settings
congured on the Wall Controller will be ignored and the Wall Controller settings
congured through the network will be applied.
VPXEMWRT2-Thermostat Manual_pkg.indd 15 2017-12-15 3:37 PM

16
Wall Controller Conguration
Setting the Wall Controller Clock
Set the Wall Controller clock to current time in 24h (Military Time) format.
• Use the “Up” and “Down” buttons to set the hours;
• Press the “Fan” button to advance to the minutes setting;
• Use the “Up” an “Down” buttons to set the minutes;
• Press the “F/C” button to advance to the next menu;
Setting the clock correctly is crucial for proper operation of the Wall Controller.
HOURS MINUTES
VPXEMWRT2-Thermostat Manual_pkg.indd 16 2017-12-15 3:37 PM

17
Wall Controller Conguration
Entering the Room Number
Enter the room number by changing the digits on the screen. Leading zeros “0”
preceding other digits will be ignored, i.e. Room number “123” should be entered
as “00123”.
• Use the “Up” and “Down” buttons to change the digit;
• Press the “Fan” button advance to the next digit;
• Press the “F/C” button to advance to the next menu;
Entering the room number correctly is crucial for proper operation of remotely
managed Wall Controllers.
VPXEMWRT2-Thermostat Manual_pkg.indd 17 2017-12-15 3:37 PM

18
Wall Controller Conguration
Conguring the Energy Savings Settings
Use the “Up” and “Down” buttons to select the Energy Saving preset:
E-0* Energy Savings Off - No Temperature Setback;
E-1 Lowest Energy Savings;
E-2 Lower Energy Savings;
E-3 Standard Energy Savings;
E-4 Higher Energy Savings;
E-5 Highest Energy Savings;
Refer to the APPENDIX 1 for Energy Saving Preset details.
E-C Indicates “Custom Energy Savings Settings” in case the active
Wall Controller savings settings differ from any Energy Saving preset;
For details, refer to the “Custom Energy Savings Settings” section;
Press the “Power” button to save the Wall Controller Conguration and start
using the Wall Controller;
* Indicates default setting;
VPXEMWRT2-Thermostat Manual_pkg.indd 18 2017-12-15 3:37 PM

19
Testing the Wall Controller
Following the Wall Controller conguration, test if the Wall Controller is controlling
the VRP unit.
• Press the “Power” button to turn the Wall Controller ON;
• Press the “Up” and “Down” buttons to change the temperature set point
above and below the current room temperature to test if the Wall Controller
initiates heating and cooling - the VRP unit should turn heating and air
conditioning on and off.
• Change the fan speed by touching “Fan” button to test if the Wall Controller
is controlling the fan speed.
Wall Controller Conguration
VPXEMWRT2-Thermostat Manual_pkg.indd 19 2017-12-15 3:37 PM

20
Custom Energy Savings Settings
If you don’t want to use the one of the energy saving presets detailed in the
Appendix 1, you can enter the custom energy savings settings.
Accessing the Wall Controller Settings
• Press and hold the “Conguration” button until the rst Wall Controller
settings screen appears.
The Wall Controller must be turned on to access the Wall Controller settings.
NOTE: If the Wall Controller is connected to a network, the equipment and the
energy saving settings congured on the Wall Controller will be ignored and the
settings congured on the Remote Management Website will be applied
NOTE: You can access Wall Controller Settings by pressing and holding the
“Conguration” button.
CONFIGURATION
BUTTON
VPXEMWRT2-Thermostat Manual_pkg.indd 20 2017-12-15 3:37 PM
Table of contents
Other Friedrich Controllers manuals
Popular Controllers manuals by other brands

Resol
Resol VA300 Mounting instructions

Dwyer Instruments
Dwyer Instruments DH-010 Installation and operating instructions

AMX
AMX NetLinx Integrated Controller NI-2100 quick start guide

GAI-Tronics
GAI-Tronics HUBBCOM GSC1000 Quick installation guide

Cytron
Cytron SD02C user manual

Mitsubishi
Mitsubishi CR750 Series instruction manual