( Fig.1 : Outdoor temperature zone )
1. COOLING OPERATION
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
Minimum
frequency Maximum
frequency Maximum
frequency
22rps 76rps
76rps
18rps 88rps
80rps
36°C
A zone
34°C 32°C
B zone
30°C 21°C
C zone
19°C
D zone
Indoor fan mode
Me Lo Quiet
A zone 79rps 61rps 52rps 37rps
B zone 79rps 61rps 52rps 37rps
C zone 79rps 61rps 52rps 37rps
D zone 52rps 43rps 37rps 28rps
E zone 64rps 55rps 49rps 36rps
F zone 64rps 55rps 49rps 36rps
( Table 1 : Compressor frequency range )
01-01
E zone
F zone
10°C
0°C
12°C
2°C
* When the room temperature is between +2°C to -2.5°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table1.
However, the maximum frequency is limited in the range shown in Fig.1 based on the indoor
fan mode and the outdoor temperature.
* If the room temperature is some degrees lower than a set temperature,
the compressor will be stopped.
AO*G12LUC
AO*G14LUC
A zone 96rps 61rps 51rps 33rps
B zone 96rps 61rps 51rps 33rps
C zone 96rps 61rps 51rps 33rps
D zone 57rps 42rps 36rps 27rps
E zone 73rps 54rps 45rps 30rps
F zone 73rps 54rps 45rps 30rps
A zone 105rps 64rps 54rps 42rps
B zone 105rps 64rps 54rps 42rps
C zone 105rps 54rps 42rps
D zone 61rps 51rps 45rps 30rps
E zone 84rps 54rps 45rps 30rps
F zone 84rps 54rps 45rps 30rps
AO*G09LTC
AO*G12LTC
A zone 96rps 61rps 51rps 33rps
B zone 96rps 61rps 51rps 33rps
C zone 96rps 61rps 51rps 33rps
D zone 57rps 42rps 36rps 27rps
E zone 57rps 42rps 36rps 27rps
F zone 57rps 42rps 36rps 27rps
A zone 76rps 45rps 37rps 29rps
B zone 76rps 45rps 37rps 29rps
C zone 76rps 45rps 37rps 26rps
D zone 43rps 35rps 26rps 20rps
E zone 51rps 37rps 31rps 22rps
F zone 51rps 37rps 31rps 22rps
64rps
Outdoor
temperature
Outdoor
temperature
( Table 2 : Limit of maximum speed based on outdoor temperature )
10rps
AO*G07LUC/LUCA
AO*G09LUC/LUCB
AO*G07LUC/LUCA
AO*G09LUC/LUCB
AO*G12LUC
AO*G14LUC
AO*G09LTC
AO*G12LTC 57rps
79rps
96rps
105rps
96rps
76rps
Outdoor
temp. zone Hi
* If the room temperature is 2°C higher than a set temperature, the compressor operation
frequency will attain to maximum performance.
When the compressor operates for 30 minutes continuously at over the maximum frequency ,
the maximum frequency is changed from Maximum Frequency to Maximum Frequency .