
13–10–612 Page 9
unit near level. Temporary installation may be made at
a maximum of 10_angle lengthwise or 30_sidewise.
Mounting bolts are not normally required. However,
installation conditions such as piping rigidity, angle of
tilt,ordanger ofshiftingfromoutsidevibrations ormov-
ing vehicles may require the use of mounting bolts to
the foundation.
OIL RESERVOIR DRAIN (FIGURE 1–3, page 2) –
The oil reservoir drain valve is located near the center
of the oil reservoir just below the separator tower. The
drain valve is approximately five (5) inches from the
floor level. If this height is not sufficient toconveniently
drain the oil, some other methods of providing oil drain
are:
1. Elevate the compressor unit on the foundation to
obtain the desired drain height.
2. Construct an oil sump or trough below the floor
level and pump or bail the drained oil.
3. Pump oil from the reservoir filler opening or reser-
voir drain to a container.
ACOUSTICENCLOSURE – The Electra–Saver unit is
furnishedwithanacousticenclosureoverthecompres-
sor only, as standard equipment. The enclosure re-
ducesthenormaloperatingsoundoftheunitto90DBA
or below in free field conditions.
AIR–COOLED OIL COOLER MODULE – The air–
cooled oil cooler is a separate module and may be
mounted remote to the compressor unit.
Ventilation – The oil cooler requires adequate cooling
air flow. Proper ventilation MUST be provided, with hot
air exhausted away from the cooler; take care that hot
air is not recirculated from the exhaust to the inlet side
ofthecooler.Coolingairflowdirectionisfromthemotor
side through the grille side of the oil cooler. Do not ob-
struct the air flow to or from the cooler. Allow two (2)
feet clearance on all sides of the cooler module. See
FIGURE 2–2, page 8, for cooling air flow require-
ments.
LowOil Pressure Protection–The standardfactory–
installed low oil pressure shutdown is incorporated in
the functions of the Auto Sentry ”ES” Controller, and
willpreventstart–uporshuttheunitdownifoilpressure
is not established or maintained due to malfunction in
the oil cooler system.
Oil Cooler – Location and General Piping – The oil
coolermodulecanbemountedinanyofseveralremote
locations: close coupled but not joined to the compres-
sor unit; horizontal remote, located on the same level
as the compressor unit, but some distance away; or
overhead remote, located above level of the compres-
sor unit, as on a roof.
The low demand mode switch cannot
be used with remote overhead oil
coolers. These units require special
wiring diagram – check with the facto-
ry. Use of low demand switch with an
overhead cooler could result in dam-
age to the compressor.
All piping and wiring between the compressor unit and
the remote oil cooler is to be supplied by the user. The
design of the remote oil cooler module system
must be approved by the Factory before installa-
tion. The design information to be submitted for ap-
proval includes:
1. Locationof oil cooler module–inside or outdoors.
2. Range of operating ambient temperatures at the
oil cooler location.
3. Elevation of the oil cooler above the compressor
unit.
4. Pipe type and size(s) to be used to connect the oil
cooler and the compressor unit. Minimum pipe
size is 2” NPT.
5. Horizontal and vertical lengths of the pipe run. If
morethanonepipesizeisused,listlengthofeach
size and total length.
6. Number and size of elbows, tees, unions, reduc-
ers, and valves to be used in the pipe run.
7. A dimensional sketch of the proposed piping sys-
tem showing location of the compressor unit, oil
cooler, and pipe and fittings of 3 through 6 above.
All remote piping should be of adequate size to insure
the minimum pressure loss. Number 4 above lists the
pipesize at thecompressor unitoilinlet andoutlet con-
nectionsandistheminimumpipesizetobeused.Long
runs of pipe and the use of valves and fittings require
larger than the minimum pipe sizes in the system to
keep the pressure loss low. All pipe and fittings used in
a remote oil cooler system should be galvanized or
treated internally to prevent rust, and all valves are to
be of a nonferrous construction to prevent corrosion
and fouling.
The remote cooler should be placed so that the fan air
flow through the cooler (air flow is from motor side
throughcore ) andthe prevailingwindsare inthe same
direction. A baffle should be provided on the exhaust
sideofthecoolerforprotectionagainstoccasionalwind
shifts.