Garnet SeeLevel Special 807-ICE 05 User manual

Printed in Canada
www.garnetinstruments.com
MODEL 807-ICE 05 MANUAL
IMPORTANT OPERATOR INFORMATION
DATE INSTALLED:_______________________________________________________________________________
UNIT NUMBER:_________________________________________________________________________________
COMPARTMENT: _______________________________________________________________________________
DISPLAY CALIBRATION UNITS (e.g. inches, gallons): ___________________________________________
MINIMUM TANK READOUT: ___________________________________________________________________
MAXIMUM TANK READOUT: ___________________________________________________________________
FULL SCALE ANALOG CALIBRATION VALUE: ___________________________________________________
NOTES :_________________________________________________________________________________________
_________________________________________________________________________________________________
_________________________________________________________________________________________________
_________________________________________________________________________________________________
_________________________________________________________________________________________________
TM
Remote Display

Page 2 807-ICE 05 Manual
Remote Display
MODEL 807-ICE 05
Table of Contents
CHAPTER 1 - INTRODUCTION....................................................................................3
CHAPTER 2 - FEATURES OF THE 807-ICE 05 .........................................................4
CHAPTER 3 - WIRING DIAGRAMS.............................................................................5
CHAPTER 4 - DISPLAY PROGRAMMING .................................................................6
CHAPTER 4 - TROUBLESHOOTING GUIDE .............................................................8
CHAPTER 10 - SERVICE & WARRANTY INFORMATION....................................9
MAIL IN WARRANTY ................................................................................................... 11
807-ICE 05_v8.2 - 11-Aug-2017
TM

Page 3
807-ICE 05 Manual
CHAPTER 1 - INTRODUCTION
C
ongratulations on purchasing the Garnet Instruments Model
807-ICE 05 SEELEVELSPECIAL
™
Remote Display. The 807-ICE 05
compliments the 808-P2 or 810-PS2 gauges by providing an ad-
ditional volume readout in the cab of the truck.
In addition to providing an additional readout of the tank level,
the 807-ICE 05 provides a 0-5V analog output proportional to the
uid volume displayed. This analog output can be used to com-
municate the tank level to other pieces of equipment.
The full scale value of the analog output can be set using the but-
tons on the back of the display, no additional equipment is re-
quired for calibration.
The 807-ICE 05 display has been designed to withstand the vibra-
tion and shock encountered in mobile applications. While the 808
and 810 series operate on internal batteries, (12 volt truck power
is used to operate the back light and external alarms), the 807
display operates on 12V truck power.

Page 4 807-ICE 05 Manual
CHAPTER 2 - FEATURES OF THE 807-ICE 05
T
he 807-ICE 05 has been uniquely designed for specic applica-
tions and with specic features:
Standard SeeLeveL Remote Display Features
1. The signal between the 808-P2 or 810-PS2 display and the
807 is digitally encoded so the signal line can be connected
using a standard 7 pin trailer plug.
2. The display operates on 12 volt truck power, and draws less
than 250 mA.
3. All-digital design eliminates reading drift or degradation, en-
suring long term accuracy under all operating conditions.
4. Operation from -40 °C to +60 °C (-40 °F to +140 °F) ambient
temperature.
5. Easy installation and servicing with a one year limited war-
ranty.
Additional 807-ICE 05 Remote Display Features
1. An analog 0-5V output, with 0V corresponding to zero dis-
played volume, and 5V corresponding to the full scale dis-
played volume programmed into the remote display.
2. The model
807-ICE
05 provides an easy-to-read LED display
inside a compact, edge-view enclosure, optimized for top-of-
dash or overhead console mounting.
3. The display is housed in an aluminum enclosure 2.7” wide x
1.1” high x 3.4” deep (68 mm wide x 29 mm high x 87 mm.
deep).
4. A dimmer button switch enables the operator to control
brightness.
5. Simple 4 wire electrical installation - 12V power (red), ground
(black), gauge signal (yellow), and analog output (white/blue).

Page 5
807-ICE 05 Manual
CHAPTER 3 - WIRING DIAGRAMS
T
HE 807-ICE 05 has been designed for easy installation with
your 808 or 810 series SEELEVEL
™
gauge. Installation instruc-
tions for the gauge were supplied with the equipment, and are
available online at
www.garnetinstruments.com
.
The 807-ICE 05 Remote Display is easy to install:
808-P2 Wiring Diagram
810-PS2 Wiring Diagram

Page 6 807-ICE 05 Manual
CHAPTER 4 - DISPLAY PROGRAMMING
The 807-ICE 05 display shows the tank level by repeating the
information shown on the 808-P2 or 810-PS2 gauge. The 0-5V
analog output is calculated from the display level with a 0V output
corresponding to a display level of zero, and a 5V output corre-
sponding to the full scale level programmed into the 807 display.
For example, if the full scale is programmed to be 500.0, then a
display value of 400.0 will result in an analog output of 4.00 volts.
The display will recognize the decimal location and adjust the out-
put accordingly, so in this example a display value of 400 will also
result in an analog output of 4.00 volts.
To set the full scale level:
1. Determine the maximum volume that can be displayed and
pick a full scale amount that is equal to or greater than this
volume.
2. Press both the SEL and UP buttons on the back panel, the
display will show ACAL. Release both buttons.
3. The display will show the existing calibration with the left digit
bright. Press the UP button to change the bright digit. Press
the SEL button to go to the next digit.
4. Set all 4 digits, then press SEL again to set the decimal point, it
will be bright to indicate that it is selected. Press the UP but-
ton to select either x.xxx, xx.xx, xxx.x or no decimal. For best
accuracy of the analog output, try to use all 4 digits such as
500.0 instead of just 500.
5. After the decimal as been set, press SEL again, the display will
show Stor. Press UP to store the calibration and exit the
setting menu. The display will continue to show Stor for a
moment and then will show donE for a second. Then normal
operation resumes.
6. If you do not want to store the calibration, press SEL again
and the display will show Abrt. Press UP to abort which exits
the calibration menu without saving.
7. If you press SEL again from the Abrt display, the menu will
return to the beginning with the left digit selected by being
bright.

Page 7
807-ICE 05 Manual
8. If the full scale calibration is below 128, the display will be un-
able to calculate a valid calibration, and will show cErr (cali-
bration error) after a few seconds. The existing calibration will
be retained, and the display will return to normal operation.
To view the existing calibration:
1. Press either the SEL or UP button (but not both) on the back
panel, the display will show the existing full scale analog cali-
bration while the button is held down. Release the button to
return to normal operation.
To test the analog output:
1. While either the SEL or UP button on the back panel is pressed,
the display will show the full scale calibration and the analog
output will go to full scale (5V). This can be used to test or
calibrate the equipment connected to the analog output.
2. While the display is in the calibration mode (entered by press-
ing both the SEL and UP buttons) the analog output will be
at zero.

Page 8 807-ICE 05 Manual
CHAPTER 4 - TROUBLESHOOTING GUIDE
Error conditions:
1. If the display is not receiving any signal from the 808-P2 or
810-PS2 gauge, it will show no S and the analog output will
go to zero.
2. If the display receives corrupted data, it will show Err and the
analog output will go to zero.
3. If the display cannot communicate with its own memory, the
display will show EErr.
4. If the display cannot communicate with its own digital to ana-
log convertor, it will show 5Err.
5. For either condition 1 or 2, check the wiring and grounding for
errors or bad connections. Also ensure that the 808-P2 or the
810-PS2 is working properly.
6. For either condition 3 or 4, the display will need to be serviced
or replaced.
Accuracy:
The analog output has an accuracy of ± 0.5% of the full scale val-
ue, so any output value should be within 25 mV of the “ideal”
value. There are no user adjustments that can be made to alter
the accuracy.
As with any digital system, there are round off and truncation er-
rors inherent in the mathematical process. However, since the
807-ICE 05 utilizes a 10 bit digital to analog convertor, it has suf-
cient accuracy to allow the full resolution of the truck gauge to
be realized. Note that the truck gauge sending the data has a
resolution of only 8 bits (1/3” systems).

Page 9
807-ICE 05 Manual
T
he warranty will only apply only if the warranty card that is shipped with the equipment
has been returned to Garnet Instruments Ltd.
DISCLAIMER OF WARRANTY ON HARDWARE
Garnet Instruments Ltd. warrants equipment manufactured by Garnet to be free from defects in
material and workmanship under normal use and service for a period of one year from the date
of sale from Garnet or an Authorized Dealer. The warranty period will start from the date of
purchase or installation as indicated on the warranty card. Under these warranties, Garnet shall
be responsible only for actual loss or damage suffered and then only to the extent of Garnet’s
invoiced price of the product. Garnet shall not be liable in any case for labor charges for indirect,
special, or consequential damages. Garnet shall not be liable in any case for the removal and/or
reinstallation of defective Garnet equipment. These warranties shall not apply to any defects or
other damages to any Garnet equipment that has been altered or tampered with by anyone other
than Garnet factory representatives. In all cases, Garnet will warrant only Garnet products which
are being used for applications acceptable to Garnet and within the technical speci cations of the
particular product. In addition, Garnet will warrant only those products which have been installed
and maintained according to Garnet factory speci cations.
LIMITATION ON WARRANTIES
These warranties are the only warranties, expressed or implied, upon which products are sold by
Garnet and Garnet makes no warranty of merchantability or tness for any particular purpose in
respect to the products sold. Garnet products or parts thereof assumed to be defective by the
purchaser within the stipulated warranty period should be returned to the seller, local distributor,
or directly to Garnet for evaluation and service. Whenever direct factory evaluation, service or
replacement is necessary, the customer must rst, by either letter or phone, obtain a Returned
Material Authorization (RMA) from Garnet Instruments directly. No material may be returned to
Garnet without an RMA number assigned to it or without proper factory authorization. Any returns
must be returned freight prepaid to: Garnet Instruments Ltd, 286 Kaska Road, Sherwood Park,
Alberta, T8A 4G7. Returned warranted items will be repaired or replaced at the discretion of Garnet
Instruments. Any Garnet items under the Garnet Warranty Policy that are deemed irreparable by
Garnet Instruments will be replaced at no charge or a credit will be issued for that item subject to
the customer’s request.
If you do have a warranty claim or if the equipment needs to be serviced, contact the installation
dealer. If you do need to contact Garnet, we can be reached as follows:
CANADA UNITED STATES
Garnet Instruments Ltd. Garnet US Inc.
286 Kaska Road 5360 Granbury Road
Sherwood Park, AB T8A 4G7 Granbury, TX 76049
CANADA USA
CHAPTER 10 - SERVICE & WARRANTY INFORMATION

Page 10 807-ICE 05 Manual
NOTES:

MAIL IN WARRANTY
MODEL NO. SERIAL NO.
DATE PURCHASED DATE INSTALLED
YR/MO/DAY YR/MO/DAY
COMPANY NAME
PRINCIPAL CONTACT
ADDRESS
TELEPHONE FAX
IN CANADA RETURN TO:
Garnet Instruments Ltd.
286 Kaska Road
Sherwood Park, AB T8A 4G7
CANADA
SENDER BAR SERIAL NO. (if applicable)
IMPORTANT: WITHOUT THE SERIAL NUMBER OF EACH UNIT IT IS
DIFFICULT TO DETERMINE WARRANTY VALIDITY
DEALERS NAME
WARRANTY CONTACT
ADDRESS
TELEPHONE FAX
IN UNITED STATES RETURN TO:
Garnet US Inc.
5360 Old Granbury Road
Granbury, TX 76049
USA
IMPORTANT: RETURNING THIS CARD WILL ENABLE US TO NOTIFY YOU IN THE EVENT OF A PRODUCT RECALL OR TO SUPPLY YOU WITH REQUIRED PRODUCT SAFETY INFORMATION.
TO MAXIMIZE YOUR WARRANTY PLEASE REGISTER ONLINE AT www.garne nstruments.com OR MAIL THIS FORM IN TO GARNET.
LIMITED WARRANTY REGISTRATION

Printed in Canada
www.garnetinstruments.com
CANADA
Garnet Instruments Ltd.
286 Kaska Road
Sherwood Park, AB T8A 4G7
USA
Garnet US Inc.
5360 Old Granbury Road
Granbury, TX 76049
P: 780-467-1010
F: 780-467-1567
TF: 1-800-617-7384
P: 817-578-8601
F: 817-573-0005
TF: 1-877-668-7813
Table of contents
Other Garnet Monitor manuals

Garnet
Garnet SEELEVEL II 709-LL User manual

Garnet
Garnet SeeLevel Access T-DP0301-B User manual

Garnet
Garnet SEELEVEL Access T-DP0301-A User manual

Garnet
Garnet SEELEVEL II 709-4LP User manual

Garnet
Garnet SeeLevel II 709-PG User manual

Garnet
Garnet SeeLevel II User manual

Garnet
Garnet SeeLevel Access T-DP0301-C User manual

Garnet
Garnet SeeLeveL II 709-RVC NLP User manual

Garnet
Garnet SeeLevel II 900-D4D DUAL User manual