2 of 2
GeneracPowerSystems,Inc.•S45W29290HWY.59,Waukesha,WI53189•generac.com
©2010GeneracPowerSystems,Inc.Allrightsreserved.Allspecificationsaresubjecttochangewithoutnotice.Bulletin0164210SBY-A/PrintedinU.S.A.01/06/11
100 - 400 Amps, 600 VAC
TerminalLugWireRanges
WithstandCurrent-600VoltCTTSSeries
MechanicalDimensions(NEMA1,Standard)
CTTSControlSystems
LOGIC CONTROL w / Inphase Monitor
UtilityVoltage
Dropout(%ofpickup)............................................................................................75-95%(Adj.)
Pickup....................................................................................................................85-95%(Adj.)
LineInterrupt......................................................................................................0.1-10Sec.(Adj.)
EngineMinimumRun......................................................................................................... 5-30Min.(Adj.)
EngineWarmup............................................................................................................... 5Sec.-3Min.(Adj.)
ReturntoUtility.................................................................................................................. 1-30Min.(Adj.)
EngineCooldown............................................................................................................... 1-30Min.(Adj.)
StandbyVoltage...................................................................................................................85-95%(Adj.)
StandbyFrequency..............................................................................................................80-90%(Adj.)
TimeDelayNeutral...........................................................................................................0.1-10Sec.(Adj.)
TransferonExercise............................................................................................................On/OffSwitch
WarmupTimerBypass.........................................................................................................On/OffSwitch
TimeDelayNeutralWhenFailtoSyng.................................................................................On/OffSwitch
GTSRatedAmps 100 150 200 300 400
FuseProtected
MaximumRMSSymmetrical
WithstandCurrent 200,000 200,000 200,000 200,000 200,000
ProtectiveDeviceContinuous
Rating(Max)Amp 200 400 400 600 600
Fuse Class J,T J,T J,T J,T J,T
CircuitBreakerProtected
MaximumRMSSymmetrical
WithstandCurrent 14,000 25,000 25,000 35,000 35,000
ProtectiveDeviceContinuous
Rating(Max)Amp 150 300 300 600 600
*TestedperUL1008andCSAStandards
*Currentratingsarelisted@480VAC
Current Height Width Depth Weight
Rating H1 H2 W1 W2 (lbs.)
100 36.8 37.5 18 24.8 10 180
150 48.8 49.5 24 30.75 12 265
200 48.8 49.5 24 30.75 12 265
300 48.8 49.5 24 30.75 12 325
400 48.8 49.5 24 30.75 12 325
GTSRatedAmps SwitchTerminal NeutralBar GroundLug
100 1X-2/0-14 4X-2/0-14 1X-2/0-14
150 1X-400MCM-4 4X-350MCM-6 1X-350MCM-6
200 1X-400MCM-4 4X-350MCM-6 1X-350MCM-6
300 2X-250MCM-1/0or1X-600MCM-4 8X-250MCM-1/0or4X-600MCM-4 1X-350MCM-6
400 2X-250MCM-1/0or1X-600MCM-4 8X-250MCM-1/0or4X-600MCM-4 1X-350MCM-6