GENMAC Powersmart G2200 User manual

G2200 G4000 G5500 G6000E
MANUALE GENERATORI - GENERATOR MANUAL
GENERATOR MANUAL - GENERATOR MANUAL
GENERATOR MANUAL - GENERATOR MANUAL


3
PREFACE
Thank you for choosing a generator set of our
company.
This manual contains the information on how to
do that. Please read it carefully before operating.
Operating safely and correctly can help you get the
best results.
All information in this publication is based on the
latest product information available at the time of
printing. The contents in this manual may be different
from the actual parts due to revision and other
changes.
Our company reserves the right to make changes
at any time without notice and without incurring
any obligation. No part of this publication may
be reproduced without our company’s written
permission.
This manual should be considered a permanent part
of the generator and should accompany the generator
if it is resold.
GENMAC group:
head quarter
42044 GUALTIERI (Reggio Emilia) Italy
via Don Minzoni, 13
Tel. 0039 - 0522.222311
Fax 0039 - 0522.829218 - 0522.222330
www.genmac.it
Genmac USA, Inc.
7060 NW 52nd St.
Miami , FL 33166 - U.S.A.
Ph: 305 599 8099
Fx: 305 599 8098
www.genmac-group.com
INDEX page
1. SAFETY 4
2. COMPONENT IDENTIFICATION 5
3. CONTROL 5
4. GENERATOR OPERATION 6
5. PRE-OPERATION CHECK 8
6. STARTING THE ENGINE 9
7. STOPPING THE ENGINE 9
8. MAINTENANCE 10
9. STORAGE 11
10. TROUBLESHOOTING 12
11. ELECTRIC STARTING 12
12. WHEEL (OPTIONAL) 14
13. SPECIFICATIONS 14
14. WIRING DIAGRAM 15
CHENIT
GENERATORI G2200 G4000 G5500 G6000E
DEESRU

4
SAFETY MESSAGES
Your safety and the safety of others are very important. We
have provided important safety messages in this manual
and on the generator. Please read these messages carefully.
A safety message alerts you to potential hazards that could
hurt you or others.
Each safety message is preceded by a safety alert symbol
and one of three words: DANGER, WARNING, or CAUTION.
meaning as
follows:
You WILL be KILLED or SERIOUSLY HURT if you don’t follow
instructions.
You CAN be KILLED or SERIOUSLY HURT if you don’t follow
instructions.
You CAN be HURT if you don’t follow instructions.
Your generator or other property could be damaged if you
don’t follow instruction.
1.SAFETY
SAFETY STANDARD
Read and understand this owner’s manual before operating
your generator. You can help prevent accidents by being
familiar with your generator’s controls, and by observing
safe operating procedures.
SPECIAl REquIREMENTS
• Electrical equipment, including lines and plug connections
should be free from being bare.
• The circuit breakers should match with the generator
equipment. If the circuit breakers require replacement, they
must be replaced with a circuit breaker of the same ratings
and performance characteristics.
• Don’t operate the generator before grounding.
If using extension lines, the requirement should be met as
following:
for 1.5mm2, the line should not be exceeded 60m; for
2.5mm2, the line not exceeded 100m.
OvERCuRRENT PROTECTOR
Environmental temperature will trigger the action of
overcurrent protector. Please change the overcurrent
protector with one that ts the local environment
temperature if necessary.
WARNING
Don’t operate indoors.
Don’t directly connect to the household
power supply.
Don’t operate in the wet condition.
Don’t smoke when refueling.
Don’t overow the fuel when refueling
Stop the engine before refueling.
Please keep it 1m at least far away from the inammable materials.
GENERATORI G2200 G4000 G5500 G6000E
CHENIT DEESRU

5
ON
OFF
ON
OFF
STARTER GRIP
Per avviare il motore, tirare leggermente la maniglia di
avviamento nché non si avverte resistenza, quindi
tirare energicamente.
Do not allow the starter grip to snap back against
the engine. Return it gently to prevent damage to the
starter.
FuEl vAlvE
The fuel valve controls fuel owing from the fuel tank
to carburetor. Be sure to return the lever to “OFF” after
stopping the engine.
3.CONTROL
GENERATOR SwITCh
2.COMPONENT
IDENTIFICATION
G2200 64000 G5500
WARNING
DC TERMINAL
POSTS
GENERATOR
SWITCH
STARTER
GRIP
FUEL
VALVE
CHOKE
LEVER
AIR CLEANER
RECOIL
STARTER GRIP
DC OVERCURRENT
PROTECTOR OIL CAP
FUEL TANK CAP
FUEL METER
MODEL NO
SER NO
FINISHED
PRODUCT NO
SPARK PLUG
CAP
MUFFLER
GROUND TERMINAL
AC
RECEPTACLES
GENERATOR
SWITCH
VOLTAGE
METER
AC
CIRCUIT
BREAKER
ENGINE TYPE & SERIAl NuMbER
ON
OFF
1kW 2.3kW/2.8kW/5.5kW/6.5kW
FUEL
VALVE
GENERATORI G2200 G4000 G5500 G6000E
CHENIT DEESRU

6
ChOkE lEvER
The choke lever is used to provide an enriched fuel mixture
when starting a cold engine.
Slowly put the choke lever to “OPEN” position after the
engine is started.
AC CIRCuIT bREAkER
The overload current will automatically switch OFF circuit
breaker to avoid short circuiting of the load or overload. If
the circuit breaker is switched OFF automatically, check load
before switching the circuit breaker ON again.
GROuND TERMINAl
This ground terminal is dedicated to reliably grounding the
whole generator.
OIl AlERT SYSTEM
The oil alert system is especially designed to prevent engine
damage caused by an insufcient amount of oil in the
crankcase. When the oil level in the crankcase fall down
below the safe limit, the oil alert system will automatically
shut down the engine(though the generator switch still
remains in the ON position), so that the engine can’t be
damaged due to the insufcient amount of the oil.
ON
OFF
1kW 2.3kW/2.8kW/5.5kW/6.5kW
OPEN
CHOCKE LEVER
OPEN CLOSE
CLOSE
ON
OFF
ON
OFF
AC CIRCUIT
BREAKER
GROUND TERMINAL
4. GENERATOR OPERATION
Ambiente di funzionamento del generatore:
• Temperatura: -15 °C ~ 40 °C.
• Umidità: inferiore al 95%.
• Altezza sul livello del mare: al di sotto di 1.000 m
(Se l’area è superiore a 1.000 m di altitudine, bisogna
considerare che vi sarà una riduzione della potenza erogata
dal generatore).
CONNECTION TO ThE hOuSEhOlD
POwER SuPPlY
When connecting the generator to a household power
supply, connection must be made by a qualied
electrician. After connecting, carefully check electric
connection for their safety and reliability, if not, damage
to the generator, burning and ring may be caused.
WARNING
·
OK NO
OK
GENERATORI G2200 G4000 G5500 G6000E
CHENIT DEESRU

7
starting power, and connect others one by one,
each with a lower starting power than the preceding one,
nally, connect the one with the lowest starting power.
In general, capacitive and inductive loads, especially motor-
driven devices have a big starting current when starting. The
following table is a reference for when connecting to the
electric appliances
GENERATOR GROuNDING
To prevent electrical shock or misuse from faulty appliances,
the generator should be grounded with an insulated lead.
AC CuRRENT
Before starting the generator, make sure that total power of
loads (total of resistive, capacitive and inductive loads) does
not exceed rated power of the generator.
Overload operation will greatly shorten generator
service life.
If the generator set is connected to multiple loads or electric
appliances, please rst connect to one with the highest
starting power, then, the one with the second highest
WARNING
MESSA A TERRA
×1×1100VA
(W)
100VA
(W)
×2×1.5
80VA
(W)
60VA
(W)
×3-5 ×2
450-
750VA
(W)
300VA
(W)
TYPE
INCANDESCENT
LAMP
100 W
INCANDESCENT
LAMP
HEATING DEVICE
FLUORESCENT
LAMP
MOTOR DRIVE
DEVICE
INCANDESCANT LAMP
REFRIGERATOR
REFRIGERATOR
150 W
ELECTRIC FAN
FLUORESCENT LAMP FLUORESCENT LAMP
40 W
TV
DEVICE STARTSTART RATEDRATED
WATTAGE EXAMPLES
TYPICAL
DEVICE
GENERATORI G2200 G4000 G5500 G6000E
CHENIT DEESRU

8
DC CuRRENT
• DC Terminals
The DC terminals are used to provide power supply for
lower-power DC loads and charging other batteries.
The terminals are colored as such: red to identify the
positive (+) terminal and black to identify the negative
(-) terminal. Load connection method: The load must be
connected to DC terminals with the proper polarity (load’s
positive to positive DC terminal and load’s negative to
negative DC terminal).
• DC OVERCURRENT PROTECTOR
The DC overcurrent protector will automatically shut off
when the DC circuit is overloaded or poor connection
occurs. If the indicator inside the DC overcurrent protector
button pops out, it shows that the DC overcurrent protector
has switched off. Wait a few minutes and then push the
button in to return to “ON” position.
Recommended engine oil 4-stroke gasoline engine oil SF
under API service classication or SAE10W-30 (equivalent
to SG class).
Method of checking engine oil level:
Remove the oil ller cap and wipe the dipstick to clean it.
Check the oil level by inserting the dipstick into the ller
neck without screwing it in.
If the level is low, add the recommended engine oil until oil
level can reach the upper mark on the dipstick.
After adding, don’t forget to ret and screw the oil dipstick
tight.
hIGh AlTITuDE OPERATION
At a high altitude, the standard carburetor air-fuel mixture
will be excessively rich. Output power will decrease, and fuel
consumption will increase.
Engine performance can be improved by installing a smaller
diameter main fuel jet in the carburetor and readjusting the
pilot screw. If you always operate the engine at altitudes
1,000 meters above the sea level,
have our company authorized dealer perform this carburetor
modication. If not, you should lower load power in
operating generator.
Even equipped with suitable carburetor, engine horsepower
will decrease approximately 3.5% for each 300 meter
increase in altitude. The effect of altitude on horsepower will
be lowered greater than this if no carburetor
modication is made.
If a carburetor for high altitude operation is installed
onto an engine suitable to a lower altitude, the lean air
fuel mixture will cause lower engine output power, over
heating and serious damage.
5.PRE-OPERATION CHECK
ENGINE OIl
Engine oil is a major factor affecting engine
performance and service life. Non-detergent and
2-stroke engine oils will damage the engine and are
not recommended. Check the oil level before each use
with the generator on a level surface with the engine
stopped.
WARNING
WARNING
PLUS
OIL DIPSTICK
AMBIENT TEMPERATURE
MINUS
OVERCURRENT
PROTECTOR
OIL UPPER
MARK
OIL LOWER MARK
GENERATORI G2200 G4000 G5500 G6000E
CHENIT DEESRU

9
FuEl
1) Check the fuel level gauge.
2) Replenish the tank if the fuel level is low. Do not let oil
level rise above the shoulder of the fuel strainer.
3) Ret and screw the fuel tank cap tight after refueling.
• Refuel in a well-ventilated area with the engine
stopped. Never smoke or allow ames or sparks in the
area where the engine is refueled or where gasoline is
stored.
• Do not overll the fuel tank.
• Avoid repeated or prolonged contact with skin or
breathing in of fuel vapor.
• Keep children from contacting fuel.
• Never use the oil/gasoline mixture or gasoline
containing impurity.
Use gasoline with octane rating ≥90 .
We recommend unleaded gasoline because it produces
fewer engine carbon deposits and spark plug deposits and
extends exhaust system’s life.
Never use stale or contaminated gasoline or oil/gasoline
mixture. Avoid getting dirt or water into the fuel tank.
6. STARTING THE ENGINE
RECOIl STARTER
(1) Remove all the loads from the output side.
(2) Turn the fuel valve to the “ON” position.
(3) Turn the AC circuit breaker to the“OFF” position.
(4) Turn the choke lever to the“CLOSE” position.
Don’t close the choke when starting the engine in a
warm state.
(5) Turn the generator switch to the “ON” position.
(6) Pull the starter grip until a resistance is felt, then pull it
out briskly.
(7) Turn the choke lever to the“OPEN” position after the
engine is warm.
(8) Don’t use electric apparatus before setting circuit
breaker to the “ON” position.
Turn the generator switch to electric starting position
and hold for not longer than 5 seconds, or damage will
be caused to the starting motor. If starting fails, release
the switch and wait for 10 seconds
before operating it again.
If the speed of the starting motor drops fast after
running for a period of time, it means the battery
should be recharged.
7.STOPPING THE ENGINE
(1) Turn the AC circuit breaker to the OFF position.
(2) Turn the generator switch to the OFF position.
(3) Turn the fuel valve to the OFF position.
To stop the engine in an emergency, turn the generator
switch to the OFF position.
WARNING
WARNING
WARNING
WARNING
FUEL MAXIMUM UPPER LEVEL
FUEL TANK CAP FULL
OPEN CLOSE
EMPTY
FUEL LEVEL
GAUGE
GENERATORI G2200 G4000 G5500 G6000E
CHENIT DEESRU

10
8. MAINTENANCE
Good maintenance is essential for safe, economical, and
trouble-free operation. It will also help reduce air pollution.
Exhaust gas contains poisonous carbon monoxide. Shut
off the engine before performing any maintenance. If
the engine must be run, make sure the area is well
ventilated.
Periodic maintenance and adjustment are necessary for
keeping the generator in good operating condition. Perform
the service and inspection at the intervals shown in the
Maintenance schedule below:
(1) Service more frequently when operation is done in dusty
areas.
(2) These items should be serviced by an authorized
generator dealer.
(3) When use is more frequent, only servicing according
to above correct intervals can insure the generator set’s
long-term use.
Improper maintenance, or failure to correct a problem
before operation, can cause a malfunction by which
you can be seriously hurt or killed.
WARNING
WARNING
REGULAR SERVICE PERIOD EACH USE
First
Month
or 20
Hrs.(3)
Every 3
Months
or 50
Hrs.(3)
Every 6
Months
or 100
Hrs.(3)
Every Year or
300 Hrs.
(3)
Engine Oil
Check Level •
Change • •
Air cleaner Check •
Clean • (1)
Drain plug Clean •
Spark plug Clean •change
Valve
clearance Adjust • (2)
Cylinder
cover Clean ogni 300 ore (2)
Fuel tank
and stainer Clean ogni 2 anni (2)
Fuel Line Change ogni 2 anni (2)
Cylinder head
and the head
of piston
Clean
carbon ogni 125 ore (2)
Always follow the inspection and maintenance
recommendations and schedules in this owner’s
manual.
ENGINE OIl ChANGE
Drain the oil while the engine is warm to ensure complete
and rapid draining.
1. Remove the oil dipstick and drain plug to drain the oil.
2.Reinstall the drain plug, then tighten the plug securely.
3. Rell oil and check the oil level.
Oil capacity:
G2200 0,6 L
G4000/G5500/G6000E 1 L
Used engine oil may cause skin cancer if repeatedly
left in contact with the skin for prolonged periods.
Although this is unlikely unless you handle used oil on
a daily basis, it is still advisable to thoroughly
wash your hands with soap and water as soon as
possible after handling used oil.
Please dispose of used engine oil in a manner that is
compatible with the environment. We suggest you take use
a sealed container to take it to your local service station or
recycling center for reclamation. Do not throw it in the trash
or pour it on the ground.
AIR ClEANER SERvICE
A dirty air cleaner will restrict air ow into the carburetor.
To prevent carburetor malfunction, service the air cleaner
regularly. Service more frequently when operating the
generator in extremely dusty areas.
Using gasoline or ammable solvent to clean the lter
element can cause a re or explosion. Use only soapy
water or a non-ammable solvent.
WARNING WARNING
OIL
DIPSTICK UPPER
LEVEL
DRAIN
PLUG
GENERATORI G2200 G4000 G5500 G6000E
CHENIT DEESRU

11
WARNING
WARNING
WARNING
Never run the generator without the air cleaner. If not,
rapid engine wear will result.
(1) Open the air cleaner clip and open the air cover. Check
the air cleaner element to see if it’s complete and clean.
(2) If the air cleaner element is dirt, please clean it:
Wash the air cleaner element in a solution of household
detergent and warm water, then rinse thoroughly or wash in
non-ammable or high ash point solvent: Drop a few points
engine oil in, then, squeeze out.
(3) Reinstall the O-ring, and strainer and screw back the
sediment cup.
(4) Turn the fuel valve ON and check for leaks.
SPARk PluG SERvICE
Recommended spark plugs: F6TC E7RTC(1kW) or other
equivalents.
(1) Remove the spark plug cap.
(2) Use the plug wrench to remove the spark plug.
(3) Visually inspect the spark plug to see if the insulator is
cracked, if so, replace it with a new the spark plug.
(4) Measure the plug gap with a feeler gauge. Correct as
necessary by carefully bending the side electrode. The gap
should be: 0.70-0.80 mm.
(5) Check the spark plug washer to see if it’s good.
(6) Reinstall the spark plug, tighten it with the plug wrench
and impact the washer. Reinstall the spark plug cap
accurately.
In order to avoid burning or re due to contact with
any hot part of the generator, don’t pack and store the
generator before it is cooled.
8. CONSERVAZIONE
In order to avoid burning or re due to contact with
any hot part of the generator, don’t pack and store the
generator before it is cooled.
(3) Reinstall the air cleaner element and the cover.
FuEl SEDIMENT CuP ClEANING
(1) Turn the fuel valve to the OFF position. Remove the
sediment cup, o-ring and strainer according to the
arrow direction.
(2) Clean the sediment cup, and o-ring, and strainer in
nonammable or high ash point solvent.
AIR CLEANER COVER
AIR CLEANER
ELEMENT
CLIP
ELEMENT
PLUG WRENCH
SPARK PLUG
CAP
FUEL
VALVE
SEDIMENT
STRAINER O-RING
GENERATORI G2200 G4000 G5500 G6000E
CHENIT DEESRU

12
If it need be stored for a long time, be sure the storage area
is clean and dry.
(1) Drain the fuel in the fuel tank out, clean strainer, o-ring
and sediment, then ret them well. Drain fuel out of the
carburetor by loosening the drain bolt, then ret it and screw
the carburetor bolt tight.
Gasoline is extremely ammable and is explosive under
certain conditions. Drain fuel in a well ventilated area
with the engine stopped. Never smoke or allow ames
or sparks in the area during this procedure.
(2) Screw the oil dipstick off and screw the drain bolt off the
crankcase to completely drain the oil out. Then screw back
the drain bolt and add fresh oil to upper mark, nally ret
the oil dipstick well.
(3) Remove the spark plug, and pour about a tablespoon of
clean engine oil into the cylinder. Crank the engine several
revolutions to distribute the oil, then reinstall the spark plug.
(4) Slowly pull the starter grip until resistance is felt. Let the
intake and exhaust valves in “close” position.
(5) Place the generator in a clean area.
G2200/G4000/G5500/G6000E
CARBURETOR
BOLT
WARNING
10. TROUBLESHOOTING
ENGINE uNAblE TO START:
11. ELECTRIC STARTING
COMPONENT IDENTIFICATION
G6000E INTERNAl bATTERY
NO POwER SuPPlY
Is there fuel in the
tank?
Is there enough oil in
the engine?
Is there a spark from
the spark plug?
Is the fuel reaching the
carburetor?
If the engine still does not start, take the
generator to an authorized generator dealer
Is the AC circuit
breaker ON?
Check the electrical
appliance or equipment for
any defects.
Check and clean the
fuel sediment cup.
Turn the AC circuit
breaker ON.
Take the generator to an
authorized generator dealer.
Rep lace the electr ical
appliance or equipment.
Replace the
spark plug.
Take the generator
to an authorized
generator dealer.
Add the recommended
oil.
Rell the fuel tank.
YES
NO
NO
NO
NO
NO
NO
STILL
NO
YES
YES
YES
YES
YES
CHOKE
LEVER
AIR
CLEANER
FUEL
VALVE
DC TERMINAL
POSTS
GROUND
TERMINAL
BATTERY
AC
RECEPTACLES
VOLTAGE
METER
GENERATOR
SWITCH
GENERATORI G2200 G4000 G5500 G6000E
CHENIT DEESRU

13
G6000E EXTERNAl bATTERY
AC
RECEPTACLES
FUEL
TANK CAP
FUEL METER
MUFFLER
FUEL
TANK
CHOKE
LEVER
AIR
CLEANER
FUEL VALVE
DC TERMINAL
POSTS
GROUND
TERMINAL
RECOIL STARTER
GRIP
AC
RECEPTACLES
VOLTAGE
METER UPPER MARK
GENERATOR
SWITCH
FUEL TANK CAP
FUEL METER
MUFFLER
BATTERY
WHEEL
HANDLE
bATTERY
Don’t connect the battery positive and negative
poles reversely (pay attention to leads mark). When
connecting, rst connect the positive poles, then
negative poles. When disconnecting, rst disconnect
the negative pole, then positive poles, if not, serious
damage may be caused to the generator set and
battery.
Check the electrolyte of the battery’s each cell if the uid
level is kept between upper mark and lower mark. If the
uid level is under the lower mark, screw off the cap and
add the distilled water up to upper mark. All cells’ electrolyte
uid level should be approximately maintained at the same
level.
• If improper operation is performed, the battery may
be explosive and may potentially hurt persons nearby.
Keep the re and inammable materials far away from
the battery.
• The battery will release the explosive gas, please keep
the re far away from it. Keep a good air ventilation
condition when battery is being charged or used.
• Be careful not to spill or overow when relling
electrolyte.
ElECTRIC STARTING
(1) Remove all the loads form the output side.
(2) Turn the fuel valve to the “ON” position.
(3) Turn the AC circuit breaker to the “OFF” position.
(4) Turn the choke lever to the “CLOSE” position.
Don’t close the choke when starting the engine in
warm state.
WARNING
WARNING
WARNING
LOWER MARK
GENERATORI G2200 G4000 G5500 G6000E
CHENIT DEESRU

14
(5) Turn the GENERATOR switch to electric starting position.
(6) After starting engine, immediately release generator
switch and generator switch can automatically return to
open position.
(7) Turn the choke lever to the “OPEN” position after the
engine is warm.
Turn the GENERATOR switch to electric position and
hold for more than 5 seconds or damage may be
caused to the starting motor.
If starting fails,, release the switch and wait for 10
seconds before starting it again.
If the speed of the starting motor drops fast after
a period of time, it suggests the battery should be
recharged
12. WHEEL (OPTION)
(1) Install the two wheels on the wheel axle with gaskets
and pins.
(2) Install the wheel on the bottom plate of the generator
frame with bolts and nuts.
(3) Fix the handle on the frame.
“•” means available, “-” means unavailable
13. SPECIFICATIONS
(1) Install the two wheels on the wheel axle with gaskets
and pins.
(2) Install the wheel on the bottom plate of the generator
frame with bolts and nuts.
WARNING
Item G2200 G4000 G5500 G6000E
Engine
Engine Style R210 R270 R390 R4200
Engine Type Single cylinder, 4-Stroke, Forced
Air Cooling, OHV
Displacement (cc) 210 270 389 420
Igniting mode Transistorized Magneto
Fuel Volume (L) 15 25 25 25
Fuel consumption
(g / (kW • h)) ≤395 ≤374 ≤374 ≤374
Full load continuum running time 8899
1/2 load continuum running time 12 12 13 13
Oil Capacity (L) 0.6 1.1 1.1 1.1
Generator
Rated Frequency (Hz) 50
Rated Voltage (V) 230
Rated Output Power (kW) 23.2 55.5
Maximum Output Power (kW) 2.2 3.5 5.5 6
General
purpose
Accessory
Large Air Cleaner ••••
Large Mufer ••••
Large Fuel tank ••••
Fuel Gauge ••••
Voltmeter ••••
Automatic Voltage Regulator ••••
Oil Alert system ••••
Overcurrent Protector ••••
Electric starting accessory ----
GENERATORI G2200 G4000 G5500 G6000E
CHENIT DEESRU
WARNING

15
14. WIRING DIAGRAM G2200
G4000-G5500
GENERATORI G2200 G4000 G5500 G6000E
CHENIT DEESRU

16
G6000E
GENERATORI G2200 G4000 G5500 G6000E
CHENIT DEESRU

17
G6000E
GENERATORI G2200 G4000 G5500 G6000E
CHENIT DEESRU
This manual suits for next models
3
Table of contents
Other GENMAC Portable Generator manuals
Popular Portable Generator manuals by other brands

SIGLENT TECHNOLOGIES
SIGLENT TECHNOLOGIES SDG7000A Series quick start

Winco
Winco HPS9000VE Installation and operator's manual

Briggs & Stratton
Briggs & Stratton PRO400 Operator's manual

Atlas Copco
Atlas Copco QAS38 Yd(S) instruction manual

Goodyear
Goodyear GY 2300I owner's manual

R&S
R&S SMA100B user manual