
5
2. PROGRAMMING THE OPTIMA 270
CONTROL UNIT
The control system is preset from the factory, which means
that the unit can be put into operation without changing the
operating settings. The factory setting is a basic setting
that can be adapted to the wishes and requirements
applicable to the home in question to ensure optimal
utilisation and operation of the system.
Depending on the product's configuration, it is possible to
connect Optima displays directly to the connector outside
the product (connector labelled "display") or directly on the
printed circuit board.
The I/O interface includes terminals for connecting both
Modbus Master (e.g. BMS/CTS systems) and Modbus Slave
devices (e.g. district heating, fire box PCB or CO2sensors).
To expose the clamps, carefully remove the dust shield
sticker.
2.1 System without display interface
2.1.1. Connect an Optima Touch display to the Optima 270
and adjust the settings as needed. Remove the Optima
Touch control panel when programming is complete. The
Genvex ventilation system will continue to operate
according to the new set parameters.
2.1.2 Use the Genvex PC tool to adjust the Optima 270
parameters. Connect a laptop to the IO interface via the
Optima Basic or Touch display and use the PC as an
interface for programming the Optima 270, or connect it
directly to the micro-USB connector on the Optima 270
circuit board.
Optima Basic and Touch displays can be retrofitted to this
type of installation if required.
2.2 Installation with Optima Basic display
See details under 1.0.
2.3 Installation with Optima Touch display
2.3.1. Connect an Optima Touch controller to the Optima
270 and adjust the settings as needed.
NOTE: The Optima 270 control unit parameters can be
saved on the Optima Touch for one ventilation system and
transferred to a similar system by using "EA1 Save" and
"EA2 load settings" to save and load the settings,
respectively.
The latest version of the Genvex Genlog software can be
ordered from Genvex by calling +45 73 53 27 00.