
3
Default limits (0.1C and 0.3C) are determined for VRLA batteries.
Refer to battery datasheet to verify maximum charge current limits.
2.3. Metering
The device control unit measures following parameters
• AC input voltage, • DC output voltage, • In-cabinet temperature.
• AC input frequency, • Total system output current,
• AC input current, • Battery charge current,
2.4. Alarm and Annunciation
14 different alarms are available. All alarms are shown on control unit screen and some are available
as LEDs on control unit. An internal buzzer is available for local alarm annunciator.
Optional alarm module has NO contacts and LEDs for each alarm. Descriptions are given at the
below:
• For DC leakage, see section ‘2.5.5. DC Leakage’.
• AC Loss will trigger if AC supply not applied or detected.
• AC High/Low will trigger if AC input voltage is out of preset limits.
• DC High/Low will trigger if DC output voltage is out of preset limits.
• For battery lead supervision or battery continuity, see section ‘2.5.3. Battery Lead Supervision’.
• Replace battery will trigger if battery capacity is under 50%. While AC is not present and load is
supplied from battery group, control unit calculates battery group capacity according to Peukert’s law.
This device is intended to use with AGM or gel VRLA batteries, so coefficient is 1.1.
• Overload will trigger if total current output is limited at maximum current for 1 hour.
• Over-temperature will trigger if in-cabinet temperature is over preset limit.
• For fan fault, see section ‘2.5.2. Fan Fault Supervision’.
• Common alarm will trigger if any alarm condition described above occurs, except AC loss.
2.5. Supervising
Each supervising function triggers an alarm which will be shown on control unit screen or available on
remote monitoring modules.
2.5.1. Temperature Supervision
If in-cabinet temperature (heating components in particular) reaches over preset value, over-
temperature alarm will be triggered.
2.5.2. Fan Fault Supervision
Fan fault alarm will trigger if fan fails to operate.
2.5.3. Battery Lead Supervision
Battery charger continuously supervises its connection to battery group. In case of disconnection,
device announces audible and visible alarm from control unit LED, LCD and related alarm contact
output. Battery lead supervision is able to detect following faults:
• Corrosion or shedding occurs at battery plates during usage and it’s unavoidable. Because of
corrosion, plate may lose it conductance to battery lead. In series connected battery group even one
plate loses connection, battery charger and battery group disconnects from system. In this case,