manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. GHM Greisinger
  6. •
  7. Transducer
  8. •
  9. GHM Greisinger GRMU2000 MP User manual

GHM Greisinger GRMU2000 MP User manual

T02.0.1X.6C-01 page 1of 3
Operating Manual for Redox-Measuring transducer
GRMU2000 MP
Specification:
Measuring range: -2000 to 2000mV or refer to type plate
Accuracy: ±0,2% (at nominal temperature)
Output signal: refer to type plate
Connection: 4 - 20 mA (2-wire)
Voltage (3- resp. 4-wire)
Electric isolation: input electrically isolated
Auxiliary energy: (supply voltage) Uv = 12 - 30 V DC (4-20mA)
Uv = 18 - 30 V DC (0-10V)
or refer to type plate
Reverse voltage protection: 50V permanent
Perm. impedance (at 4-20mA):RA(Ohm) < ( (Uv - 12V) / 0.02A )
Example: for Uv = 18V: RA< (18V - 12V) / 0.02A => RA< 300 Ohm
Permissible load(at 0-...V):RL(Ohm) > 3000 Ohm
Electrode: any Redox-Electrode of our program is suitable.
(electrode not included in scope of supply!)
Input resistance: 1012 Ohm
Electrode socket: Cinch-socket (standard), optionally available with BNC- and DIN-socket
Display: none
Optional display: approx. 10 mm high, 3½-digit LCD-display
Nominal temperature: 25°C
Operating temperature: 0 to 50°C
Relative humidity: 0 to 95 % r.F. (non-condensing)
Storage temperature: -20 to 85°C
Housing: ABS (IP65 - with the exception of electrode)
Dimensions: 82 x 80 x 55 mm (without elbow-type plug and sensor sockets)
Mounting: With fixing holes for wall mounting (in housing - accessible after cover has been
removed).
Mounting distance: 50 x 70mm, max. shaft diameter of mounting screws is 4 mm.
Electric connection: elbow-type plug conforming to DIN 43650 (IP65),
max. wire cross section: 1.5 mm², wire/cable diamter from 4.5 to 7 mm
EMC: The
GRMU2000MP corresponds to the essential protection ratings established in the Regulations
of the Council for the Approximation of Legislation for the member countries regarding
electromagnetic compatibility (89/336/EWG). In accordance with EN50081-1 and EN50082-1
Additional error: <1%
GREISINGER electronic GmbH
T02.0.1X.6C-01 page 2of 3
Assignment of elbow-type plug:
2-wire connection (4-20mA) 3-wire connection (voltage) 4- wire connection (voltage)
1= supply voltage +Uv 1= signal + 1= signal +
2= GND / signal 3= supply voltage +Uv 2= signal -
=supply voltage -Uv 3= supply voltage +Uv
signal - = supply voltage -Uv
General installation instructions:
To mount the connection cable (2-, 3-, or 4-wire depending on type of device) the angle plug screw has to be loosened
and the coupling insert has to be removed by means of a screw driver at the position indicated (arrow).
Pull out connection cable through PG glanding and connect to the loose coupling insert as described in the wiring
diagram. Replace loose coupling insert onto the pins at the transmitter housing and turn cover cap with PG glanding in
the direction desired till it snaps on (4 different starting positions at 90° intervals). Re-tighten the screw at the angle plug.
Before connecting to supply voltage, ensure that a working electrode is connected.
Safety instructions:
This device has been designed and tested in accordance with the safety regulations for electronic devices.
However, its trouble-free operation and reliability cannot be guaranteed unless the standard safety measures and special
safety advises given in this manual will be adhered to when using the device.
1. Trouble-free operation and reliability of the device can only be guaranteed if the device is not subjected to any other
climatic conditions than those stated under "Specification". If the device is transported from a cold to a warm
environment condensation may cause in a failure of the function. In such a case make sure the device temperature
has adjusted to the ambient temperature before trying a new start-up.
2. General instructions and safety regulations for electric, light and heavy current plants, including domestic safety
regulations (e.g. VDE), have to be observed.
3. If device is to be connected to other devices (e.g. via PC) the circuitry has to be designed most carefully. Internal
connection in third party devices (e.g. connection GND and earth) may result in not-permissible voltages impairing or
destroying the device or another device connected.
4. If there is a risk whatsoever involved in running it, the device has to be switched off immediately and to be marked
accordingly to avoid re-starting.
Operator safety may be a risk if:
- there is visible damage to the device
- the device is not working as specified
- the device has been stored under unsuitable conditions for a longer time.
In case of doubt, please return device to manufacturer for repair or maintenance.
1
2
A
Uv V
3
Uv1VUv
3
1
2
T02.0.1X.6C-01 page 3of 3
Important!! redox - electrodes are very sensitive. Please read manual of the electrode carefully before usage.
Error and System Messages [only with option display ]
Display Description Posible fault cause Remedy
FE 1 Measuring values
exceeding measuring
range
redox value is out of the
transducers measuring range Replace electrode.
Redox electrode defective Replace electrode.
FE 2 Measuring values below
measuring range transducer defective Return to manufacturer for repair
FE 7 System fault Error in transducer Disconnect transducer from supply and
reconnect. If error remains: Return to
manufacturer for repair .
Segment test The transducer performs a display test for 2 seconds after switch on. After
that it will change the the display of the measuring.
redox electrode not connected Check the connection and cable.
8.8.8.8 Input signal is not valid Permissible input range is
exceeded
Check if not a wrong electrode (ph or
others) is connected.
Replace electrode.

Popular Transducer manuals by other brands

American Printing House for the Blind Braille Plus 18 user guide

American Printing House for the Blind

American Printing House for the Blind Braille Plus 18 user guide

Mianyang Weibo Electronic WBP214P75 user manual

Mianyang Weibo Electronic

Mianyang Weibo Electronic WBP214P75 user manual

novotechnik RSM-2800 user manual

novotechnik

novotechnik RSM-2800 user manual

Simrad ES38-18 installation manual

Simrad

Simrad ES38-18 installation manual

MKS 907 Series instruction manual

MKS

MKS 907 Series instruction manual

Siemens SITRANS T3K PA instruction manual

Siemens

Siemens SITRANS T3K PA instruction manual

HBM Z16A operating manual

HBM

HBM Z16A operating manual

Clark Synthesis TST239 specification

Clark Synthesis

Clark Synthesis TST239 specification

Geokon 4450 instruction manual

Geokon

Geokon 4450 instruction manual

Guitammer BK-SK Product guide

Guitammer

Guitammer BK-SK Product guide

Asco Power Manager Xp 5200 Series Operator's manual

Asco

Asco Power Manager Xp 5200 Series Operator's manual

Panametrics T17 installation guide

Panametrics

Panametrics T17 installation guide

DFE TrueTension TI17C instruction manual

DFE

DFE TrueTension TI17C instruction manual

controlair 550 Series Installation, operation and maintenance instructions

controlair

controlair 550 Series Installation, operation and maintenance instructions

Siemens Echomax XPS-15 Quick start manual

Siemens

Siemens Echomax XPS-15 Quick start manual

Iskra MT 511 user manual

Iskra

Iskra MT 511 user manual

S+S Regeltechnik PREMASGARD SHD Operating Instructions, Mounting & Installation

S+S Regeltechnik

S+S Regeltechnik PREMASGARD SHD Operating Instructions, Mounting & Installation

Lumel P18S User Manual & Quick Start

Lumel

Lumel P18S User Manual & Quick Start

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.