ZEOS-AD
Analogue Addressable Fire Detector
ma_zeosad_01_010001_en_180420
TECHNICAL SPECIFICATIONS
ORDER CODE DESCRIPTION
Loop Powered - 17 V to 30 V DC
450 uA max.
4 mA - Alarm LED Iluminated
According to EN54-5 and EN54-7
0.5-2.5 mm²
20 seconds max.
White / ABS / 95% RH Non-Condensing
0°C to 50°C / -10°C to 85°C
100 mm (D) x 50 mm (H) inc. base / 144 g inc. base
SUPPLY VOLTAGE
CURRENT - QUIESCENT / SURGE
CURRENT - DEVICE IN ALARM
SENSITIVITY
CABLE SIZE
RESET/START-UP TIMES
COLOUR / CASE MATERIAL / MAX. HUMIDITY
NORMAL / TRANSIENT OPER. TEMPERATURE
DIMENSIONS / WEIGHT
ZEOS-AD-S
ZEOS-AD-H
ZEOS-AD-SH
ZEOS-AD-SI
ZEOS-AD-HI
ZEOS-AD-SHI
| CERTIFICATE | ANALOGUE ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR
ANALOGUE ADDRESSABLE TEMPERATURE/HEAT DETECTOR
ANALOGUE ADDR. COMBINED SMOKE & HEAT DETECTOR
ANALOGUE ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR WITH ISOLATOR
ANALOGUE ADDRESSABLE TEMPERATURE/HEAT DETECTOR WITH ISOLATOR
ANALOGUE ADDR. COMBINED SMOKE & HEAT DETECTOR WITH ISOLATOR
1328-CPR-0521
1328-CPR-0520
1328-CPR-0519
1328-CPR-0607
1328-CPR-0610
1328-CPR-0492 INSTALLATION
INSTALLINGTHEBASE-Toensureproperfitofthedetectorheadtothebase,allwiresshouldbeproperlydressedatinstallationbypositioningallwiresflatagainstterminalsand
fasteningthewiresawayfromconnectorterminals.Thedetectorbasecanbemounteddirectlyontomoststandardelectricaljunctionboxes.
INSTALLINGTHEHEAD-Aligndetectorcomponentsusingprovidedalignmentmarksonboththeheadandbase.Aligndetectormarkandshortalignmentmarkonbase.Fitthe
detectorheadontothe baseand twistclockwisetosecureit. After all detectorsareinstalled,apply power to thecontrolunitand activate thedetectionloop.Test thedetectors
asdescribedbelow.
TESTING-Allremotesignallingsystems,releasingdevicesandextinguishingsystemsshouldbedisconnectedduringthetestperiodandreconnectedattheconclusionoftesting.
SMOKE:Allowsmokefroma cottonwickortestsmokeaerosoltoenterthedetector’ssmokechamberforatleast10seconds.Whensufficientsmokehasentered,thedetector
willsignal an alarm. This will beindicated by theillumination of the2 Red LEDs provided.Make suretoclearsmoke outof thechamber before resetting in orderto keep the
detectoratitscurrentsensitivitysetting.
HEAT:Thedetectortobetestedshouldbesubjecttoaflowofwarmairatatemperatureofbetween65°Cand80°C.Thisrequirementcanbemetbysomedomestichairdryers.
Switch onthewarmairflow andcheckthat thetemperature iscorrectandstable. Froma distanceofseveralcms,directthe airflowattheguard protectingthethermistor.The
detector should alarm within 60 seconds. Uponalarm immediatelyremovethe heat source and checkthat theRed LEDsof thedetectorare illuminated. If a detectorfails to
activatewithin60seconds,confirmconnections andprogramming.Ifnecessaryreplace unit.Note:Aftertesting,check thatthesystem isreturnedtonormaloperation.Notify
theappropriateauthoritiesthatthetestingprocedurehasbeencompletedandthesystemisactiveagain.
MAINTENANCE - The recommended minimum requirement for detector maintenance consists of annual cleaning of dust from the detector head using a low power
vacuumcleaner. >>DONOTATTEMPTTODISASSEMBLETHEDETECTOR
DETECTOR BASE - LOOP CONNECTIONS
NOTE: Positive terminal of remote indicator should be connected to terminal 4 (+ Loop IN/ OUT)
Connection applicable only to:
ZEOS-AD-S / ZEOS-AD-H / ZEOS-AD-SH
Connection applicable only to:
ZEOS-AD-SI / ZEOS-AD-HI / ZEOS-AD-SHI
-Loop IN/ OUT - REMOTE LED INDICATOR
+Loop IN/ OUT
-Loop IN/ OUT
SCREEN
To next device
in loop or return
to panel
-Loop IN/ OUT
MADE IN PORTUGAL - EU
www.acornfiresecurity.com
www.acornfiresecurity.com