Graco 25B128 User manual

3A6709B
EN
Installation
Pressure
Transducer Kit
For monitoring the inlet pressure on the Electric Fixed Ratio (EFR) System. For
professional use only.
Kit No. 25B128
Important Safety Instructions
Read all warnings and instructions in this
manual and in your system manual before
using the equipment. Save these instructions.
567
F
G
E
AB
AA
D
C
Related Manuals
23A6709B
Related Manuals
Overview
The inlet pressure transducer kit enables the inlet
pressure reading to be displayed on the ADM screen for
easy viewing. This kit also enables the EFR system to
detect when high or low inlet pressure may inhibit
performance.
Installation
1. Ensure the system power is OFF and pressure has
been relieved. Follow the Pressure Relief Procedure
in the Electric Fixed Ratio Proportioner, Setup -
Operation manual.
2. Remove the pump yoke shroud (J) and frame cover
(K) from the EFR system.
Manual Description
3A6165 Electric Fixed Ratio Proportioner, Setup -
Operation
406987 GCA CAN Cables, Reference
Ref. Part Description
Qty
.
A--- MODULE, inlet transducer
monitor
1
AA --- MODULE, FCM 1
AB --- BRACKET, mounting 1
B 127068 CABLE, CAN, 1.0M 1
C 102598 SCREW, cap, socket head 2
D --- WASHER, nylon blk 2
E 15M669 SENSOR, pressure, fluid outlet 2
F 16U440 ADAPTER, fitting, pressure
sensor
2
G 121399 PACKING, o-ring 2
H--- CABLETIE 12
WARNING
ELECTRIC SHOCK HAZARD
To avoid electric shock, make sure the
system power is OFF before connecting or
disconnecting CAN cables.
PRESSURIZED FLUID HAZARD
This equipment stays pressurized until
pressure is manually relieved. To help
prevent serious injury from pressurized
fluid, such as skin injection, splashing fluid
and moving parts, follow the Pressure
Relief Procedure when you stop spraying
and before cleaning, checking or servicing
the equipment.
PERSONAL PROTECTIVE EQUIPMENT
Wear appropriate protective equipment
when in the work area to help prevent
serious injury, including eye injury, hearing
loss, inhalation of toxic fumes, and burns.
FIG. 1
J
K
Related Manuals
3A6709B 3
3. Mount the inlet transducer monitor (A) inside the
system frame with screws (C) and washers (D).
4. Remove the pressure gauges (L) from the inlet
pumps.
5. Install the pressure transducer fittings (E,F,G) into
the ports the pressure gauges were removed from.
6. Route the transducer cables along the pumps and
connect them to the monitor. Secure the cables
along the pump tie bolts and along the lower pair of
EFR tie rods with the provided cable ties (H) as
shown in FIG. 4.
FIG. 2
FIG. 3
567
C
D
A
E,F,G
L
FIG. 4
H
H
H
H
All written and visual data contained in this document reflects the latest product information available at the time of publication.
Graco reserves the right to make changes at any time without notice.
Original instructions. This manual contains English. MM 3A6709
Graco Headquarters: Minneapolis
International Offices: Belgium, China, Japan, Korea
GRACO INC. AND SUBSIDIARIES • P.O. BOX 1441 • MINNEAPOLIS MN 55440-1441 • USA
Copyright 2018, Graco Inc. All Graco manufacturing locations are registered to ISO 9001.
www.graco.com
Revision B, May 2019
7. Connect the red inlet transducer cable to connector
seven on the inlet transducer monitor (A), and
connect the blue inlet transducer cable to connector
six on the inlet transducer monitor (A).
8. Connect the CAN cable (B) from either CAN
connection on the inlet transducer monitor (A) to
CAN connector 1 or 2 found on the motor.
9. Secure the CAN cable (B) to the frame using the
cable ties (H) provided, and route it through the
protected opening as shown in FIG. 5.
10. Re-install the pump yoke shroud (J) and frame
cover (K) onto the EFR system.
11. The transducers will be automatically recognized
upon connection.
Graco Information
Sealant and Adhesive Dispensing Equipment
For the latest information about Graco products, visit www.graco.com.
For patent information, see www.graco.com/patents.
TO PLACE AN ORDER, contact your Graco distributor, go to www.graco.com, or call to identify the nearest
distributor.
If calling from the USA: 1-800-746-1334
If calling from outside the USA: 0-1-330-966-3000
FIG. 5
B
H

Popular Transducer manuals by other brands

HBM SLB700A/06VA1 Mounting instructions

HBM

HBM SLB700A/06VA1 Mounting instructions

TILLQUIST P20 user manual

TILLQUIST

TILLQUIST P20 user manual

Daiichi Electronics PTT2-92A-12 instruction manual

Daiichi Electronics

Daiichi Electronics PTT2-92A-12 instruction manual

MAMAC SYSTEMS PR-243 technical information

MAMAC SYSTEMS

MAMAC SYSTEMS PR-243 technical information

Raymarine HYPERVISION HV-100 installation instructions

Raymarine

Raymarine HYPERVISION HV-100 installation instructions

Wilcoxon PC420VP Series installation guide

Wilcoxon

Wilcoxon PC420VP Series installation guide

WIKA F1811 operating instructions

WIKA

WIKA F1811 operating instructions

GREISINGER GPHU 014 MP operating manual

GREISINGER

GREISINGER GPHU 014 MP operating manual

Thyracont VSP62 operating instructions

Thyracont

Thyracont VSP62 operating instructions

B-K Medical 8824 user guide

B-K Medical

B-K Medical 8824 user guide

HBM T12 manual

HBM

HBM T12 manual

Simrad 18-11 -  REV C datasheet

Simrad

Simrad 18-11 - REV C datasheet

FTS SDI-PT-KEL user manual

FTS

FTS SDI-PT-KEL user manual

Airmar P79 Owner's guide and installation instructions

Airmar

Airmar P79 Owner's guide and installation instructions

GREISINGER electronic GHTUMP Series operating manual

GREISINGER electronic

GREISINGER electronic GHTUMP Series operating manual

KYOWA DTT-A-100 instruction manual

KYOWA

KYOWA DTT-A-100 instruction manual

Thyracont VSR53MV operating instructions

Thyracont

Thyracont VSR53MV operating instructions

Trimec DUALPULSE 490 instruction manual

Trimec

Trimec DUALPULSE 490 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.