
5.2 OPERATION
The EvoLink controls the operation of both the heat pump and the
supplementary heat source (boiler).
Additionally, the EvoLink can be set to operate in either ‘Green’
or ‘Comfort’ mode when meeting either a heating or domestic hot
water demand.
• Comfort Mode
In this mode the priority is to ensure that the required comfort
level is maintained.
If the heat pump is not capable of satisfying the heating load
the boiler will be called in and the EvoLink will mix the boiler
ow with the heat pump ow to maintain the required ow
temperature.
• Green Mode
In this mode the priority is to ensure that the heat pump
supplies as much of the heat energy as possible.
If the heat pump is not capable of satisfying the heating load
the boiler will be called in and the EvoLink will mix the boiler
ow with the heat pump ow to maintain the required ow
temperature. However, if the return temperature starts to rise
to a point where the heat pump will switch o, the mixing is
reduced to ensure that the heat pump can remain operating
for as long as possible.
5.2.1 SPACE HEATING
• If there is a space heating demand to the EvoLink from
the heating system controls, i.e., the programmer heating
channel and room thermostats(s) are ‘calling’, the EvoLink
will operate to provide space heating.
• The heat pump operates to achieve the weather
compensated HEATING SETPOINT ow temperature (as set
on the EvoLink user interface).
• If the heat pump is unable to achieve a ow temperature
within the TEMP BELOW SP AUTO CH band after the
TIME BELOW SP AUTO CH time period has elapsed (both
values as set on the EvoLink user interface) the EvoLink will
automatically start the boiler to raise the ow temperature to
the required weather compensated value.
• When the boiler ow temperature on the boiler ow pipe (left
hand pipe, refer to Figures 2-1 and 5-1) is 3°C above the
ow temperature on the EvoLink system ow pipe the PWM
mixing pump will start – feeding the boiler ow into the mixing
tank to achieve the required weather compensated ow
temperature.
• As the ambient outside temperature falls, and the heat
demand on the system increases, the required higher
weather compensated ow temperature in the mixing tank
is achieved by using a greater amount of the boiler ow until
the weather compensated ow temperature is achieved.
• This may be at the maximum ow temperature from the
boiler.
• Once started, even when the required weather compensated
ow temperature has been achieved, the boiler will remain in
operation until either,
a) the end of that heating demand, i.e., until the room
thermostat or programmer switches o.
or
b) when the heating load diminishes and %PWM falls
to below the END SUPP CH PWM setting for longer
than the END SUPP CH TIME setting, when it will be
automatically switched o.
• When there is a heating demand and the outside air
temperature is below or falls to below the OUTSIDE TEMP
BOILER ONLY setting, the boiler will be automatically
started, along with the EvoLink circulating pump, and
become the ‘lead’ heat source. The heat pump will not
operate as it will be inecient for it to do so at this low
outside air temperature.
• If the outside temperature rises to above the OUTSIDE
TEMP BOILER ONLY setting, the boiler, and the EvoLink
circulating pump, will be automatically switched o and the
heat pump will start up as lead heat source.
Section 5: EvoLink OperationPage 16
5.2.2 HOT WATER
• If there is a hot water demand to the EvoLink, i.e., if both
the hot water channel of the programmer and the cylinder
thermostat are ‘calling’, the EvoLink will operate to provide
hot water.
• Note that if the EvoLink is operating to provide space
heating when the hot water demand occurs, the EvoLink will
immediately ignore the space heating demand and switch
over to meet the hot water demand.
• The heat pump operates to achieve the HOT WATER
SETPOINT ow temperature (as set on the EvoLink user
interface). Note that this is not weather compensated.
• If the heat pump is unable to achieve a ow temperature
within the TEMP BELOW SP AUTO DHW band after the
TIME BELOW SP AUTO DHW time period has elapsed (both
values as set on the EvoLink user interface), the EvoLink will
automatically start the boiler to raise the ow temperature to
the required HOT WATER SETPOINT level.
• When the boiler ow temperature on the boiler ow pipe (left
hand pipe, refer to Figures 2-1 and 5-1) is 3°C above the
ow temperature on the EvoLink system ow pipe, the PWM
mixing pump will start – feeding the boiler ow into the mixing
tank to achieve the required ow temperature.
• Once started, even when the required Hot Water Setpoint
ow temperature has been achieved, the boiler will remain in
operation until the end of that hot water demand, i.e., until the
cylinder thermostat or programmer switches o.
• When there is a hot water demand and the outside air
temperature is below, or falls to below, the OUTSIDE TEMP
BOILER ONLY setting, the boiler will be automatically started
along with the EvoLink circulating pump, and become the
‘lead’ heat source. The heat pump will not operate as it will
be inecient for it to do so at this low outside air temperature.
• If the outside temperature rises to above the OUTSIDE
TEMP BOILER ONLY setting, the boiler, and the EvoLink
circulating pump, will be automatically switched o and the
heat pump will start up as lead heat source.
5.2.3 LEGIONELLA DEMAND COUNT
• This function requires the EvoLink Legionella Interface to be
tted. Refer to Section 4.5.
• It is designed to automatically operate an electric immersion
heater to provide anti-legionella protection after a pre-set
number of hot water demands (up to a maximum of 20) have
occurred.
• However Grant UK recommend the use of a 7-day Immersion
programmer to provide anti-legionella protection. This will
control the timed operation of the cylinder immersion heater
for the required period on either a daily or weekly basis.
Refer to the Aerona³ installation instructions Section 5.3
for details on Legionella sanitation regimes and Section
4.5 of these instructions for details of the 7-day immersion
programmer.
5.2.4 SUPPLEMENTARY DHW TYPE
Although the EvoLink shows this function accessible tapping the
hot water icon, this function remains inoperative. The element is
not operable but the boiler is if required.
5.2.5 BOOST MODE
Although this function can be accessed by tapping the Hot Water
icon on the touchscreen user interface, it is currently inoperable
and not available for use.