2
Important safety notice
•This equipment contains two disconnection switches for interruption of supply that do not
provide supply isolation. Means of isolation from the supply must be provided as part of the
building installation. Do not work on the equipment unless the supply is isolated. If isolation is
made by removal of fuses or other cut-outs, the removed devices must be kept secure from
replacement whilst work is performed. If isolation is provided by a switch, the switch must
conform to the requirements of IEC 947-1 and IEC 947-3 or equivalent.
•Over-current protection is not provided by the equipment and must be provided as part of the
building installation. For the domestic supply the maximum over-current device rating is 100A
at 415V AC, conforming to the requirements of BS1361 or equivalent.
•Only suitable trained and qualied personnel shall be allowed to work on the equipment. Local
safety standards shall be observed and shall take precedence over these regulations in points
of conict.
•The meters must be held securely during installation. They can cause injury if dropped.
•Meters that have fallen must not be installed. Even if no damage is apparent, meters must be
returned to the manufacturer for testing. Internal damage can result in functional disorders or
short-circuits.
•The meters must only be cleaned whilst disconnected and with a dry cloth without solvent and
on no account be cleaned with running water or with high-pressure devices. Penetrating water
can cause internal short-circuits.
•A terminal cover protects inadvertent exposure to the meter tail connections and must be
tted prior to energising the electrical supply.
jThe following safety regulations must be observed at all times.
Failure to observe precautions could result in severe injury or death.