LOAD
16 Amp resistive load
10 Amp incandescent lighting
6 Amp fluorescent lighting
3 Amp compact fluorescent lighting
3 Amp low energy lighting
3 Amp low voltage lighting (switch primary of transformer)
Fluorescent lighting (max 6 fittings recommended)
For fluorescent lighting total power factor correction capacitance must not exceed 40μF
3 Amp fans and ventilation equipment
Switch SON lighting loads via a contactor
SUPPLY VOLTAGE 220-240 Volts AC 50 Hz
TIMING PERIOD Adjustable 1 second to 2 hours in ranges
TERMINAL CAPACITY4.0mm2
IP RATING IP 66
MATERIAL Polystyrene
TYPE Class 2
TEMPERATURE -10°C to 35°C
CONFORMITY EMC-2004/108/EC
LVD-2006/95/EC
LOAD DOES NOT COME ON
Check to see if the live supply to the circuit is
good. Strap across the L and LIVE OUT termi-
nal to check.
LOAD DOES NOT GO OFF
Check that the time setting is correct.
When using external triggers, ensure that live is
removed from the trigger terminal to enable the
timer to start (for resetting mode only).
Part Numbers
Fault Finding Specification
MRT16-WP Weatherproof multi-range timer
/PN Permanently illuminated neon
/TN Temporarily illuminated neon (only illuminates during timing)
Warning. This device works at mains potential. Be sure to take care when working with electricity.
1. Make sure the load is connected and in working order.
2. Isolate the mains supply to the circuit at the main consumer unit.
3. Connect the controller via the terminal block. Live supply to the Lterminal, Neutral to the N terminal and the load to the LIVE OUT terminal.
Where required connect the external trigger to the TRIG terminal.
4. Set the timing range according to the diagram below. Set the thumbwheel to the time setting (anticlockwise is minimum, clockwise is maxi-
mum).
5. Set the function according to the diagram below (see above for description).
6. Screw the unit to the wall and switch the mains supply back on at the distribution board.
Installation
Due to our policy of continual product improvement CP Electronics reserves the right to alter the specification of this product without prior notice.
FM 45789 EMS 534520
C.P. Electronics Ltd
Brent Crescent
London
NW10 7XR
United Kingdom
Tel: + 44 (0) 333 900 0671
Fax: + 44 (0) 333 900 0674
www.green-iswitches.co.uk
enquiry@green-iswitches.co.uk
Ref: #WD129 Issue 3
IMPORTANT NOTICE!
This device should be installed by a qualified electrician in
accordance with the latest edition of the IEE Wiring
Regulations and any applicable Building Regulations.