GREISINGER electronic GHTUMP Series User manual

T20.0.0X.6C-07 page 1 of 4
Operating Manual
Relative Air Humidity And Temperature Transducer
GHTU ... MPas of V2.6
Specification:
Measuring range: relative air humidity: 0.0...100.0 % rel. humidity (temperature compensated)
temperature: -40.0...120.0 °C or -40.0...248 °F
Rec. range of application: standard: 20,0...80,0 %RH
option high humidity: 5,0...95,0 %RH
Accuracy: (at nominal temperature = 25°C)
Display relative air humidity: ±1% linearity, 2% hysteresis (at recommended range of application)
temperature: ±0.4% of measured value ±0.2°C
Add. output signal: ±0.2 % FS
Sensors: relative air humidity: cap. polymer sensor
temperature: Pt1000
Temperature compensation: automatic
Min-/Max-Value Memory: Min and max measured values are stored
Output signals: refer to type plate, both freely scaleable
Scaling: By entering display values for 4mA (resp. 0V)
and 20mA (resp. 1V/10V) output
Connection: 4 - 20 mA (2-wire) – output signals are
electrically isolated from each other
for option AV01, AV10: 0 - 1 (10) V (3-wire) – output signals are not electrically isolated from each other
for option AV01G, AV10G: 0 - 1 (10) V (3- resp. 4-wire) – output signals are electrically isolated from each other
Auxiliary energy: (supply voltage, each output) Uv = 12 - 30 V DC (4-20mA)
Uv = 12 - 30 V DC, max. 10mA (0-1V)
Uv = 18 - 30 V DC, max. 10mA (0-10V)
or refer to type plate
Reverse voltage protection: 50V permanent
Perm. impedance (at 4-20mA):RA(Ohm) < ( (Uv - 12V) / 0.02A )
Example: for Uv = 18V: RA< (18V - 12V) / 0.02A => RA< 300 Ohm
Permissible load (at 0-...V):RL(Ohm) > 3000 Ohm
Adjusting: via keypress by input of offset and scale (humidity and temperature)
Display: approx. 10 mm high, 4-digit LCD-display
Ambient conditions for electronics:
Nominal temperature: 25°C
Operating temperature: -25 to 50°C (sensor head and tube: -40 to 100°C – for short time up to 120°C)
Relative humidity: 0 to 95 %RH (non-condensing)
Storage temperature: -25 to 70°C
Housing: ABS (IP65)
Dimensions: 82 x 80 x 55 mm (without elbow-type plug and sensor tube)
Mounting: With holes for wall mounting (in housing - accessible after cover has been removed).
Mounting distance: 50 x 70mm, max. shaft diameter of mounting screws is 4 mm.
Electrical connection: elbow-type plug conforming to DIN 43650 (IP65),
max. wire cross section: 1.5 mm², wire/cable diameter from 4.5 to 7 mm
EMC: The
device corresponds to the essential protection ratings established in the Regulations of the Council for the
Approximation of Legislation for the member countries regarding electromagnetic compatibility (89/336/EWG). In
accordance with
EN61326 +A1 +A2 (appendix A, class B), additional errors: < 1% FS.
When connecting long leads adequate measures against voltage surges have to be taken.
GREISINGER
electronic GmbH
Working area of humidity sensor:

T20.0.0X.6C-07 page 2 of 4
Safety instructions:
This device has been designed and tested in accordance with the safety regulations for electronic devices.
However, its trouble-free operation and reliability cannot be guaranteed unless the standard safety measures and special safety
advises given in this manual will be adhered to when using the device.
1. Trouble-free operation and reliability of the device can only be guaranteed if the device is not subjected to any other climatic
conditions than those stated under "Specification". If the device is transported from a cold to a warm environment condensation
may cause in a failure of the function. In such a case make sure the device temperature has adjusted to the ambient temperature
before trying a new start-up.
2. General instructions and safety regulations for electric, light and heavy current plants, including domestic safety regulations (e.g.
VDE), have to be observed.
3. If device is to be connected to other devices (e.g. via PC) the circuitry has to be designed most carefully. Internal connection in third
party devices (e.g. connection GND and earth) may result in not-permissible voltages impairing or destroying the device or another
device connected.
4. If there is a risk whatsoever involved in running it, the device has to be switched off immediately and to be marked accordingly to
avoid re-starting.
Operator safety may be a risk if:
- there is visible damage to the device
- the device is not working as specified
- the device has been stored under unsuitable conditions for a longer time.
In case of doubt, please return device to manufacturer for repair or maintenance.
5. Warning:
Do not use these product as safety or emergency stop devices, or in any other application where failure of the product could result
in personal injury or material damage.
Failure to comply with these instructions could result in death or serious injury and material damage.
Disposal instructions:
The device must not be disposed in the regular domestic waste.
Send the device directly to us (sufficiently stamped), if it should be disposed. We will dispose the device appropriate and
environmentally sound.
Assignment of elbow-type plug: (depending on type)
4-20mA (2-wire connection) voltage, not electrically isolated voltage, electrically isolated
(3-wire connection) (3- resp. 4-wire connection)
(1 combined elbow type plug for humidity and (2 elbow type plugs: right plug is for humidity
temperature) left plug is for temperature)
1 = supply voltage +Uv (humidity) 1 = signal + (humidity) 1 = signal + (humidity or temp.)
2 = GND / signal (humidity) 2 = signal + (temperature) 2 = signal - (humidity or temp.)
3 = supply voltage +Uv (temperature) 3 = supply voltage +Uv 3 = supply voltage +Uv
(4) = GND / signal (temperature) (4) = supply voltage -Uv (4) = supply voltage –Uv
(note: and 2 are connected internally)
The type current or voltage output is set by works and cannot be changed
General installation instructions:
To mount the connection cable (2-, 3-, or 4-wire depending on type of device) the elbow-type plug screw has to be
loosened and the coupling insert has to be removed by means of a screw driver at the position indicated (arrow).
Pull out connection cable through PG glanding and connect to the loose coupling insert as described in the wiring
diagram. Replace loose coupling insert onto the pins at the transducer housing and turn cover cap with PG glanding in
the direction desired till it snaps on (4 different starting positions at 90° intervals). Re-tighten the screw at the angle plug.

T20.0.0X.6C-07 page 3 of 4
Arrow to Temp indicates
temperature display
Design types, dimension
Design type with 4-20mA output or voltage with not isolated outputs
GHTU-1R-MP GHTU-1K-MP GHTU-2K-MP GHTU-MP-Kabel
short sensor tube aside long sensor tube aside long sensor tube bottom separated sensor tube
At design types with electrically isolated voltage outputs there are plugs at both
sides (right plug for humidity, left plug for temperature)
Display functions
Currently measured values
During normal operation the relative air humidity in [%RH] is displayed alternating to
the temperature in [°C] or [°F].
display relative air humidity display temperature
Min/Max Value Memory
watch Min values (Lo): press ‘down‘(2) shortly once display changes between ‘Lo‘ and Min values
watch Max values (Hi): press ‘up‘(3) shortly once display changes between ‘Hi‘ and Max values
restore current values: press ‘down‘(2) or ’up’(3) once again current values are displayed
clear Min-values: press ‘down’(2) for 2 seconds Min values are cleared. The display shows shortly ‘CLr‘.
clear Max-values: press ‘up’(3) for 2 seconds Max values are cleared. The display shows shortly ‘CLr‘.
After 10 seconds the currently measured values will be displayed again.
Error and system messages
Display Description Possible fault cause Remedy
Err.1 measuring range exceeded Wrong signal Temperature above 120°C not allowed.
Err.2 Measuring value below
measuring range Wrong signal Temperature below -40°C not allowed.
Err.7 System fault Error in device Disconnect from supply and reconnect. If error
remains: return to manufacturer
Err.9 Sensor error Sensor or cable defective Check sensor, cable and connections
Er.11 Calculation not possible Calculation variable missing
or invalid Check temperature
8.8.8.8 Segment test The transducer performs a display test for 2 seconds after power up. After
that it will change to the display of the measuring.

T20.0.0X.6C-07 page 4 of 4
Configuration of the device
In the configuration following parameters can be changed:
- Display unit of temperature measuring
- Scaling of the humidity output and of the temperature output
- Adjusting of humidity and temperature display (offset and scale correction)
By means of the scaling the analogue signal outputs can be adopted to Your needs.
The adjusting by means of offset and scale is intended to be used to compensate
errors of the measurings. It is recommended to keep the scale correction deactivated
(“oFF”). The display value is given by following formula:
Display = measured value - offset
With a scale correction (just for calibration laboratories, etc) the formula changes:
Display = (measured value - offset) * ( 1 + scale adjustment/100)
To configure the parameters proceed like follows:
1. Press the key 1 (SET) for more than 4 sec’s until 'unit' with temperature arrow
appears in the display.
I.) 'unit' with Temp-arrow: Temperature unit
Enter the desired Temperature unit. All referring settings and displays are done in this unit.
2. Choose the desired value by pressing 2 (down) or 3 (up) key. Choice between °C and °F (ex works: °C)
3. Enter by key 1 (SET), select next parameter by pressing key 1 again: 'Out.0' without temperature arrow appears.
II.) 'Out.0': Display at zero output of humidity measuring (output scaling)
Enter the humidity value at which the output should have 4mA (respectively 0V).
4. Choose the desired value by pressing 2 (down) or 3 (up) key. Max. input range: 0.0...100.0 % (ex works: 0.0%)
5. Enter by pressing key 1 (SET), select next parameter: 'Out.1' without temperature arrow appears in the display.
III.) 'Out.1': Display at maximum output for humidity measuring (output scaling)
Enter the humidity value at which the output should have 20mA (respectively 10V).
6. Choose the desired value by pressing 2 (down) or 3 (up) key. Max. input range: 0.0...100.0 % (ex works: 100.0%)
7. Enter by pressing key 1 (SET) , select next parameter: 'Out.0' with temperature arrow appears in the display.
IV.) 'Out.0' with Temp-arrow: Display at zero output of temperature measuring (output scaling)
Enter the temperature value at which the output should have 4mA (respectively 0V).
8. Choose the desired value by pressing 2 (down) or 3 (up) key. (ex works: 0.0°C / 32.0°F)
9. Enter by pressing key 1 (SET), select next parameter: 'Out.1' with temperature arrow appears in the display.
V.) 'Out.1' with Temp-arrow: Display at maximum output for temperature measuring (output scaling)
Enter the temperature value at which the output should have 20mA (respectively 10V).
10.Choose the desired value by pressing 2 (down) or 3 (up) key. (ex works: 100.0°C / 212.0°F)
11.Enter by pressing key 1 (SET), select next parameter: 'OFFS' without temperature arrow appears in the display.
VI.) 'OFFS': Offset of humidity measuring (correction of measuring deviations):
The offset of the measuring will be shifted by this value, the input is in %RH. Calculation: see above.
12.Choose the desired value by pressing 2 (down) or 3 (up) key.
Max. input range: -5.0...5.0 %RH or 'oFF': offset is deactivated (=0.0%, ex works)
13.Enter by pressing key 1 (SET), select next parameter: 'SCAL' without temperature arrow appears in the display.
VII.) 'SCAL': Scale of humidity measuring (correction of measuring deviations):
The scale of the measuring is changed by this value. Calculation: see above.
14.Choose the desired value by pressing 2 (down) or 3 (up) key.
Max. input range: -5.00...5.00 or 'oFF': scale is deactivated (=0.00, ex works)
15.Enter by pressing key 1 (SET), select next parameter: 'OFFS' with temperature arrow appears in the display.
VIII.) 'OFFS' with Temp-arrow: Offset of temperature measuring (correction of measuring deviations):
The offset of the measuring will be shifted by this value, the input is in °C. Calculation: see above.
16.Choose the desired value by pressing 2 (down) or 3 (up) key.
Max. input range: -5.0...5.0 °C / -9.0...9.0°F or 'oFF': offset is deactivated (=0.0, ex works)
17.Enter by pressing key 1 (SET), select next parameter: 'SCAL' with temperature arrow appears in the display.
IX.) 'SCAL' with Temp-arrow: Scale of temperature measuring (correction of measuring deviations):
The scale of the measuring is changed by this value. Calculation: see above.
18.Choose the desired value by pressing 2 (down) or 3 (up) key.
Max. input range: -2.00...2.00 or 'oFF': scale is deactivated (=0.00, ex works)
19.Enter by pressing key 1 (SET). After pressing key 1 again, the instrument will restart (segment test).
If the jumper is removed from the
shown contacts, the configuration is
inaccessible, values are protected.
Never connect other contacts!
This manual suits for next models
4
Popular Transducer manuals by other brands

S+S Regeltechnik
S+S Regeltechnik THERMASGARD ETM 5 Operating Instructions, Mounting & Installation

novotechnik
novotechnik TEX Series user manual

LEM
LEM ITZ 10000-SB FLEX ULTRASTAB manual

Lowrance
Lowrance Active Imaging 3-IN-1 installation manual

Thyracont
Thyracont VSM77PN operating instructions

controlair
controlair 2000 Installation, operation and maintenance instructions

Fairchild
Fairchild T7800 Series Installation, operation and maintenance instructions

Balluff
Balluff BTL266T user guide

Mercury
Mercury SMARTCRAFT WIRING CONNECTIONS

GE
GE Baker Hughes Masoneilan 4411 instruction manual

TR-Electronic
TR-Electronic LA Series Assembly instructions

Schertler
Schertler DYN-B user manual