GV D1130S User manual

D1130 - Switch / Proximity Detector Repeater Relay Output ISM0048-8
D1130S - D1130D
INSTRUCTION MANUAL
INSTRUCTION MANUAL
Switch/Proximity Detector
Repeater Relay Output
DIN-Rail Models D1130S, D1130D

D1130 - Switch / Proximity Detector Repeater Relay Output G.M. International ISM0048-8
2
General Description: The Switch/Proximity Detector Repeater type D1130 is a DIN Rail unit with one or two independent channels. The unit can be configured for contact or proximity
detector, NO or NC and for NE or ND SPDT relay output contact. Each channel enables a Safe Area load to be controlled by a switch, or a proximity detector, located in Hazardous Area.
D1130D dual channel type has two independent input channels and actuates the corresponding output relay. Two actuation modes can be independently DIP switch configured on
each input channel: NO input/NE relay or NO input/ND relay. Contact or proximity sensor and its connection line short or open circuit fault detection is also DIP switch configurable:
fault detection can be enabled (in case of fault it de-energizes the corresponding output relay and turns the fault LED on) or disabled (in case of fault the corresponding output relay
repeats the input line open or closed status as configured).
D1130S single channel type has one input channel and two output relays; the unit has two DIP switch configurable operating modes:
Mode A) input channel actuates in parallel the two output relays (DPDT contact). Relay actuation mode can be independently configured for each output in two modes: NO input/NE
relay or NO input/ND relay.
Mode B) input channel actuates output relay A configurable in two modes as in mode A above. Output relay B operates as a fault output (in case of input fault, relay B actuates and the
fault LED turns on while relay A repeats the input line as configured).
Actuation can be DIP switch configured in two modes: No input fault/energized relay (it de-energizes in case of fault) or No input fault/de-energized relay (it energizes in case of fault).
Function: 1 or 2 channels I.S. switch repeater for contact or EN60947-5-6 proximity. Provides 3 port isolation (input/output/supply).
Signalling LEDs: Power supply indication (green), output status (yellow), line fault (red).
Field Configurability: NO/NC input for contact/proximitor, NE/ND relay operation and fault detection enable/disable.
EMC: Fully compliant with CE marking applicable requirements.
Supply:
115-230 Vac, 50-60 Hz nom (85 to 250 Vac, 48 to 400 Hz), ripple within voltage limits 10 Vpp. Limit supply voltage to 250 Vrms for Instrinsic Safety applications.
Current consumption @ 115 Vac: 25 mA with short input and relays energized.
Current consumption @ 230 Vac: 15 mA with short input and relays energized.
Max. power consumption: at 250 Vac supply voltage, short circuit input and relays energized, 2.0 W for 2 channels D1130D, 1.9 W for 1 channel D1130S.
Isolation (Test Voltage): I.S. In/Out 2.5 KV; I.S. In/Supply 2.5 KV; Out/Supply 2.5 KV; Out/Out 2.5 KV.
Input switching current levels: ON 2.1 mA, OFF 1.2 mA, switch current 1.65 mA ± 0.2 mA hysteresis.
Fault current levels: open fault 0.2 mA, short fault 6.8 mA
(when enabled both faults de-energize channel relay with dual channel unit D1130D or actuate fault relay with single channel unit D1130S).
Input equivalent source: 8 V 1 Ktypical (8 V no load, 8 mA short circuit).
Output: voltage free SPDT relay contact.
Contact material: AgCdO.
Contact rating: 2 A 250 Vac 500 VA, 2 A 250 Vdc 80 W (resistive load).
DC Load breaking capacity:
Mechanical / Electrical life: 30 * 106/ 1 * 105operation, typical.
Operate / Release time: 7 / 3 ms typical.
Bounce time NO / NC contact: 3 / 5 ms.
Response time: 20 ms.
Frequency response: 10 Hz maximum.
Compatibility:
CE mark compliant, conforms to 94/9/EC Atex Directive and to 2004/108/CE EMC Directive.
Environmental conditions: Operating: temperature limits -20 to + 60 °C, relative humidity max 90 % non condensing, up to 35 °C.
Storage: temperature limits – 45 to + 80 °C.
Safety Description:
II (1) G [Ex ia Ga] IIC, II (1) D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I, II 3G Ex nA IIC T4, [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I associated electrical apparatus.
Uo/Voc = 10.7 V, Io/Isc = 15 mA, Po/Po = 39 mW at terminals 13-14, 15-16.
Um = 250 Vrms, -20 °C Ta 60 °C.
Approvals: DMT 01 ATEX E 042 X conforms to EN60079-0, EN60079-11, EN60079-26, EN61241-0, EN61241-11,
IECEx BVS 07.0027X conforms to IEC60079-0, IEC60079-11, IEC60079-26, IEC61241-0, IEC61241-11, GM International CRR028 conforms to EN60079-0, EN60079-15,
UL & C-UL E222308 conforms to UL913 (Div.1),UL 60079-0 (General, All Zones), UL60079-11 (Intrinsic Safety “i” Zones 0 & 1) for UL and
CSA-C22.2 No.157-92 (Div.1), CSA-E60079-0 (General, All Zones), CSA-E60079-11 (Intrinsic Safety “i” Zones 0 & 1) for C-UL,
refer to control drawing ISM0143 for complete UL and C-UL safety and installation instructions,
FM & FM-C No. 3024643, 3029921C, conforms to Class 3600, 3610, 3611, 3810 and C22.2 No.142, C22.2 No.157, C22.2 No.213, E60079-0, E60079-11, E60079-15,
Russia according to GOST 12.2.007.0-75, R 51330.0-99, R 51330.10-99 [Exia] IIC X, Ukraine according to GOST 12.2.007.0,22782.0,22782.5 Exia IIC X,
DNV and KR Type Approval Certificate for marine applications.
Mounting: T35 DIN Rail according to EN50022.
Weight: about 145 g D1130D, 140 g D1130S.
Connection: by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2.
Location: Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA
T4 installation.
Protection class: IP 20.
Dimensions: Width 22.5 mm, Depth 99 mm, Height 114.5 mm.
Technical Data
Characteristics
0.20.1
V (V)
I (A)
10
20
30
40
50
100
200
300
0.3 0.5 1 2 5
Resistive
Load

3
D1130 - Switch / Proximity Detector Repeater Relay OutputG.M. International ISM0048-8
Model: D1130
1 channel S
2 channels D
Ordering information
Front Panel and Features
• Input from Zone 0 (Zone 20), Division 1, installation in Zone 2, Division 2.
• Universal AC supply voltage (85 to 250 Vac, 48 to 400 Hz).
• NO/NC contact/proximity Detector Input.
• Two SPDT Relay Output Signals.
• SPDT Relay Output for fault detection on single channel version.
• Three port isolation, Input/Output/Supply.
• EMC Compatibility to EN61000-6-2, EN61000-6-4.
• In-field programmability by DIP Switch.
• ATEX, IECEx, UL & C-UL, FM & FM-C, Russian and Ukrainian Certifications.
• Type Approval Certificate DNV and KR for marine applications.
• High Reliability, SMD components.
• High Density, two channels per unit.
• Simplified installation using standard DIN Rail and plug-in terminal blocks.
• 250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier.
D1130
1 2 3 4
16151413
5 6 7 8
PWR ON
1 2
STATUS/
FAULT

4 D1130 - Switch / Proximity Detector Repeater Relay Output G.M. International ISM0048-8
D1130D
+ Input Ch 1 for Proximity or
Input Ch 1 for Voltage free Contact
Terminal block connections
HAZARDOUS AREA SAFE AREA
- Input Ch 1 for Proximity or
Input Ch 1 for Voltage free Contact
+ Input Ch 2 for Proximity or
Input Ch 2 for Voltage free Contact
- Input Ch 2 for Proximity or
Input Ch 2 for Voltage free Contact
13
14
15
16
Output Ch 1 Common
1
Output Ch 1 Relay Normally Opened (NO)
2
L Power Supply 115-230 Vac
3
N Power Supply 115-230 Vac
4
Output Ch 2 Common
5
Output Ch 2 Relay Normally Opened (NO)
6
Output Ch 2 Relay Normally Closed (NC)
7
Output Ch 1 Relay Normally Closed (NC)
8
D1130S
+ Input Ch 1 for Proximity or
Input Ch 1 for Voltage free Contact
HAZARDOUS AREA SAFE AREA
- Input Ch 1 for Proximity or
Input Ch 1 for Voltage free Contact
13
14
Output Ch 1-A Common
1
Output Ch 1-A Relay Normally Opened (NO)
2
L Power Supply 115-230 Vac
3
N Power Supply 115-230 Vac
4
Output Ch 1-B Common
5
Output Ch 1-B Relay Normally Opened (NO)
6
Output Ch 1-B Relay Normally Closed (NC)
7
Output Ch 1-A Relay Normally Closed (NC)
8

5
D1130 - Switch / Proximity Detector Repeater Relay OutputG.M. International ISM0048-8
Parameters Table
In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check
its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded
by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D1130 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check
that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective
gas group. See parameters on enclosure side and the ones indicated in the table below:
Must
be
Hazardous Area/
Hazardous Locations
Device Parameters
D1130 Associated
Apparatus Parameters
Must
be
Hazardous Area/
Hazardous Locations
Device + Cable Parameters
Uo / Voc = 10.7 V Ui / Vmax
D1130 Terminals
Ch1
Ch2
13 -14
15 -16
Io / Isc = 15 mA
Ch1
Ch2
13 -14
15 -16
Po / Po = 39 mW
Ch1
Ch2
13 -14
15 -16
Ii/ Imax
Pi / Pi
D1130 Terminals
Ch1
Ch2
13 -14
15 -16
Ch1
Ch2
13 -14
15 -16
Ch1
Ch2
13 -14
15 -16
D1130 Associated
Apparatus Parameters
Ci / Ci device + C cable
Li / Li device + L cable
Li / Ri device and
L cable / R cable
(IIC-A, B)
Co / Ca = 2.23 µF
Co / Ca = 15.6 µF
Co / Ca = 69 µF
(IIB-C)
(IIA-D)
(IIC-A, B)
Lo / La = 172 mH
Lo / La = 689 mH
Lo / La = 1379 mH
(IIB-C)
(IIA-D)
(IIC-A, B)
Lo / Ro = 930 µH/
Lo / Ro = 3720 µH/
Lo / Ro = 7440 µH/
(IIB-C)
(IIA-D)
NOTE for USA and Canada:
IIC equal to Gas Groups A, B, C, D, E, F and G
IIB equal to Gas Groups C, D, E, F and G
IIA equal to Gas Groups D, E, F and G
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 % of the Co and Lo parameters of the Associated Apparatus (excluding the cable),
then 50 % of Co and Lo parameters are applicable and shall not be exceeded (50 % of the Co and Lo become the limits which must include the cable such that
Ci device + C cable 50 % of Co and Li device + L cable 50 % of Lo).
If the cable parameters are unknown, the following value may be used: Capacitance 60pF per foot (180pF per meter), Inductance 0.20µH per foot (0.60µH per meter).
The Intrinsic Safety Entity Concept allows the interconnection of Intrinsically Safe devices approved with entity parameters not specifically examined in combination as a system
when the above conditions are respected.
For Division 1 and Zone 0 installations, the configuration of Intrinsically Safe Equipment must be FM approved under Entity Concept (or third party approved);
for Division 2 installations, the configuration of Intrinsically Safe Equipment must be FM approved under non-incendive field wiring or Entity Concept (or third party approved).

6 D1130 - Switch / Proximity Detector Repeater Relay Output G.M. International ISM0048-8
Function Diagram
HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC,
HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D,
CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1,
CLASS I, ZONE 0, GROUP IIC
SAFE AREA, ZONE 2 GROUP IIC T4,
NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2,
GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4
MODEL D1130D
=
=
13
14
3 L
4 N
8 NC
2 NO
1 COM
Supply 115-230 Vac
Out 1
+
-
In 1
15
16
7 NC
6 NO
5 COM
+
-
In 2 Out 2
=
voltage free
Contact Proximity
Proximity
Common
positive
connection
_
voltage free
Contact
MODEL D1130S
=
=
13
14
8 NC
2 NO
1 COM
Out 1-A
+
-
In 1
7 NC
6 NO
5 COM
Out 1-B
=
voltage free
Contact Proximity
3 L
4 N Supply 115-230 Vac
_
Relay contact shown in de-energized position

7
D1130 - Switch / Proximity Detector Repeater Relay OutputG.M. International ISM0048-8
D1130 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN Rail located in Safe Area/Non Hazardous Locations or Zone 2, Group IIC,
Temperature Classification T4, Class I, Division 2, Groups A, B, C, D, Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA Temperature Code T4 Hazardous Area/Hazardous
Locations (according to EN/IEC60079-15, FM Class No. 3611, CSA-C22.2 No. 213-M1987, CSA-E60079-15) within the specified operating temperature limits Tamb -20 to +60 °C, and
connected to equipment with a maximum limit for AC power supply Um of 250 Vrms.
Non-incendive field wiring is not recognized by the Canadian Electrical Code, installation is permitted in the US only.
For installation of the unit in a Class I, Division 2 or Class I, Zone 2 location, the wiring between the control equipment and the D1130 associated apparatus shall be accomplished
via conduit connections or another acceptable Division 2, Zone 2 wiring method according to the NEC and the CEC.
Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground.
D1130 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards
(e.g. IEC/EN60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165,
ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505,
Canadian Electrical Code CEC) following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones.
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area/Hazardous Locations or
unless area is known to be nonhazardous.
Warning: substitution of components may impair Intrinsic Safety and suitability for Division 2, Zone 2.
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosureto avoid electrical shock
when connected to live hazardous potential.
Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury.
The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
Warning
Operation
D1130 accepts as an input from Hazardous Area/Hazardous Locations a proximity sensor or voltage free electrical contact and repeats their status to Safe Area/Non Hazardous
Locations by a voltage free SPDT relay contact. Presence of supply power and status of output (energized or de-energized), as well as integrity or fault condition of sensor and
connecting line are displayed by signaling LEDs (green for power, yellow for status and red for fault condition). D1130D (dual channel type) has two independent input channels and
actuates the corresponding output relay SPDT contact; two actuation modes can be independently DIP switch configured for each input channel:
Normally open input / Normally energized relay or Normally close input / Normally energized relay.
Contact or proximity sensor and its connection line short or open circuit fault detection is also DIP switch configurable. Fault detection can be enabled (in case of fault de-energizes the
corresponding output channel relay and turns ON the fault LED) or be disabled (in case of fault the corresponding output channel relay repeats the input line open or close status as
configured). D1130S (single channel type) has one input channel and two output relays; the unit has two DIP switch configurable operating modes:
A) Input channel actuates in parallel output relays SPDT contacts (providing a DPDT type of output). Relays actuation can be independently configured for each output in two modes:
Normally open input / Normally energized relay or Normally close input / Normally energized relay.
B) Input channel actuates output relay (A) SPDT contacts configurable in two modes as above. Output relay B operates as fault output (in case of input fault, relay B actuates and the
fault LED turns on while relay A repeats the input line as configured). Actuation can be configured in two modes:
No input fault / Energized relay (it de-energizes in case of fault) or No input fault / De-energized relay (it energizes in case of fault).
Note: use of voltage free electrical contacts with fault detection enabled requires, near the switch at the end of the line, a 1 Kseries connected resistor and a 10 Kparallel connected
resistor in order to allow the fault detection circuit to distinguish between a condition of contact close/open and a line open/short circuit fault.
D1130 Associated Apparatus
FM Approved
under Entity Concept
and non-incendive field wiring
Unclassified Locations or
Hazardous (Classified) Locations
Class I, Division 2, Groups A, B, C, D, T-Code T4
Class I, Zone 2, Group IIC, IIB, IIA, T-Code T4
FM Approved under Entity Concept,
or third party approval
Hazardous (Classified) Locations
Class I, Division 1, Groups A, B, C, D
Class II, Division 1, Groups E, F, G
Class III, Division 1
Class I, Zone 0, Group IIC, IIB, IIA
Intrinsically
Safe Equipment
Must not use or generate
more than 250 Vrms or Vdc
Control
Equipment
Unclassified Locations
Hazardous (Classified) Locations
Class I, Division 2, Groups A, B, C, D
Class II, Division 2, Groups E, F, G
Class III, Division 2
Class I, Zone 2, Group IIC, IIB, IIA
FM Approved under non-incendive field
wiring (permitted only for US installations),
or third party approval
13
14
1
2
+
-
Power Supply
3 L/+
4 N/-
16
15
-
+
Intrinsically
Safe Equipment
Unclassified Locations or
Hazardous (Classified) Locations
Class I, Division 2, Groups A, B, C, D, T-Code T4
Class I, Zone 2, Group IIC, IIB, IIA, T-Code T4
Unclassified Locations
Must not use or generate
more than 250 Vrms or Vdc
8
Control
Equipment
7
6
5
+
Non-incendive
Equipment
Non-incendive
Equipment
+
-
-
113
16
15
14
7
6
5
8
2
Control
Equipment
Power Supply
Control
Equipment
D1130 Associated Apparatus
FM Approved
under Entity Concept
and non-incendive field wiring
3 L/+
4 N/-

8 D1130 - Switch / Proximity Detector Repeater Relay Output G.M. International ISM0048-8
Start-up
Before powering the unit check that all wires are properly connected, particularly supply conductors and their polarity, input and output wires, also check that Intrinsically Safe conductors
and cable trays are segregated (no direct contacts with other non I.S. conductors) and identified either by color coding, preferably blue, or by marking. Check conductors for exposed
wires that could touch each other causing dangerous unwanted shorts. Turn on power, the “power on” green led must be lit, status and fault led on each channel must be in accordance
with condition of the corresponding input line. If possible close and open input lines one at time checking the corresponding status and fault leds condition as well as output to be correct.
Power Dissipation of D1130 Isolators
Section “Technical Data” of D1130 isolator specifies the current consumption (maximum current from the nominal power supply); this data serves to dimension the current rating of the
power supply unit. Section “Technical Data” indicates also the maximum power consumption (maximum power required from the power supply in the worst (abnormal) operating
conditions like, short circuit on the outputs and on the inputs terminals.
The power dissipated Pd inside the enclosure for analog signal isolators is: Pd = Current Consumption (A) * Supply Voltage (V) - Power Dissipated into the input/output loads
Digital signal isolators have lower dissipation than analog signal isolators, in addition 2 channels barriers (D1130D) have higher dissipation than single channel units (D1130S).
Isolators are not running at the maximum current all at the same time, the average power consumption of a multitude of isolators can be considered to be only 70 % of the value obtained
from the section “Technical Data”. Considering the 1/3 load power and the 70 % above discussed, the power effectively dissipated internally by the isolators can therefore become ½ of
the actual power delivered by the power supply. Digital barriers dissipate all the supply power inside the enclosure consequently the total power dissipation into a cabinet, with mixed
analog and digital barriers, is determined by the number of channels more than by the number of isolator enclosures. The following tables give advises for the DIN rail orientation
(vertical or horizontal) of the barriers mounting, D1130D (double channel) and D1130S (single channel) isolators, installed on DIN rail or custom board assembly.
A) Cabinet with Natural Ventilation
Maximum recommended ambient temperature in °C depending on barrier type and installation method:
Installation in Cabinet
Any orientation Vertical Horizontal
Installation of Multiple units with DIN-rail BusSingle unit Installation
Type of Isolator
Vertical Horizontal
Installation on Custom Boards
B) Cabinet with Forced Ventilation
Maximum recommended ambient temperature in °C depending on barrier type and installation method:
Any orientation Vertical Horizontal
Installation of Multiple units with DIN-rail BusSingle unit Installation
Type of Isolator
60°C 40°C 45°C
Vertical Horizontal
Installation on Custom Boards
45°C 50°C
D1130S
60°C 30°C 35°CD1130S
60°C Not recommended (1) 30°C
D1130D
35°C 40°C
30°C 35°C
(1) Installation is not recommended since it would significantly shorten the units life and increase the probability of failures.
60°C 40°C 45°C 45°C 50°CD1130D
Installation
D1130 series are AC supply switch/proximity detector repeaters housed in a plastic enclosure suitable for installation on T35 DIN Rail according to EN50022.
D1130 unit can be mounted with any orientation over the entire ambient temperature range, see section “Installation in Cabinet” and "Installation of Electronic Equipments in Cabinet"
Instruction Manual D1000 series for detailed instructions.
Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit
without suffering or causing any damage (for Zone 2 or Division 2 installations check the area to be nonhazardous before servicing).
The wiring cables have to be proportionate in base to the current and the length of the cable.
On the section “Function Diagram” and enclosure side a block diagram identifies all connections and configuration DIP switches.
Identify the number of channels of the specific card (e.g. D1130S is a single channel model and D1130D is a dual channel model), the function and location of each connection terminal
using the wiring diagram on the corresponding section, as an example:
Connect AC power supply (85 to 250 Vac, 48 to 400 Hz) at terminal “3” and “4” (limit supply voltage to Um 250 Vrms for Intrinsic Safety applications).
For Model D1130S connect common relay contact output of channel 1 at terminal “1”, normally closed contact at terminal “8” and normally opened contact at terminal “2”.
For Model D1130D connect common relay contact output of channel 2 at terminal “5”, normally closed contact at terminal “7” and normally opened contact at terminal “6”.
For Model D1130S connect proximity sensor or voltage free contact at terminal “13” for positive and “14” for negative.
For Model D1130D in addition to channel 1 connections above, connect terminal “15” for positive and “16” for negative on channel 2.
Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards
(e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165,
ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505,
Canadian Electrical Code CEC), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect SPDT relay contacts checking the load rating to be within the contact maximum rating (2 A, 250 V, 500 VA 80 W resistive load).
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation
requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation.
Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts.
If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D1130 must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided.
According to EN61010, D1130 series must be connected to supply non exceeding category II, pollution degree II overvoltage limits.
Relay output contact must be connected to loads non exceeding category II, pollution degree II overvoltage limits.
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock
when connected to live hazardous potential.

9
D1130 - Switch / Proximity Detector Repeater Relay OutputG.M. International ISM0048-8
Input Output Input Output
OutputInputOutputInput
A configuration DIP switch is located on component side of pcb. This switch allows the configuration of input/output relationship, fault detection functions and operating mode.
Configuration
1234
ON
CH1 CH2
Dip switch configuration
D1130D
2
1
CH1
Setting
Line fault
detection
ON
IN / OUT
Operation
NO-NE or
NC-ND
NO-ND or
NC-NE ON
1OFF
4
4
3
3
Disabled
(contact / proximity sensor)
Enabled
(proximity sensor or contact
with terminating line resistor)
ON
13
2
OFF
NO
14
1
2
8
NE
OR
NC 13
14
1
2
8
ND
13
NO
14
1
2
8
NE
OR
NC 13
14
1
2
8
ND
Side A Panel View
Input Output Input Output
OutputInputOutputInput
CH2
Setting
Line fault
detection
ON
IN / OUT
Operation
NO-NE or
NC-ND
NO-ND or
NC-NE ON
OFF
Disabled
(contact / proximity sensor)
Enabled
(proximity sensor or contact
with terminating line resistor)
15
OFF
NO
16
5
6
7
NE
OR
NC 15
16
5
6
7
ND
15
NO
16
5
6
7
NE
OR
NC 15
16
5
7
6
ND

10 D1130 - Switch / Proximity Detector Repeater Relay Output G.M. International ISM0048-8
4
4
1
CH
Setting
Line fault
detection
IN / OUT
Operation
NO-NE or
NC-ND
NO-ND or
NC-NE
1
4
4
3
3
1234
ON
CH1
Dip switch configuration
D1130S
B Output
Operation Normal Parallel
Mode
Reverse
Mode
OFF
ON
Fault
Output ON ND
Mode
NE
Mode
OFF
ON
OFF
Configuration
Input Output Input Output
OutputInputOutputInput
2ON
13
2
OFF
NO
14
1
2
8
NE
OR
NC 13
14
1
2
8
ND
13
NO
14
1
2
8
NE
OR
NC 13
14
1
2
8
ND
ON
OFF
Disabled
(contact / proximity sensor)
Enabled
(proximity sensor or contact
with terminating line resistor)
Out BOut A
1
2
8
5
6
7
Out A
1
2
8
Out B
5
6
7
No Fault
5
6
7
5
6
7
NE NE
NE ND
ND
NE
No Fault
D1130D Configuration Summary Table
Channel
IN/OUT Operation
NO-NE or NC-ND
NO-ND or NC-NE
SW2
OFF
SW4
OFF
ON
1 2 Channel
Line fault detection
Disabled
(contact/proximity sensor)
Enabled
(proximity sensor or contact with terminating line resistor,
detects field open circuit and short circuit de-energizing output)
SW1 SW3
1 2
ON
OFF OFF
ONON
IN/OUT Operation
NO-NE or NC-ND
NO-ND or NC-NE
SW2
OFF
ON
Line fault detection
Disabled
Enabled
SW1
OFF
ON
B Output Operation
Normal
Fault Output
SW3
OFF
ON
Mode
Direct
Reverse
ND
NE
SW4
OFF
ON
OFF
ON
D1130S Configuration Summary Table
This manual suits for next models
1
Table of contents