H3 Group LCPSD-HV / EMPHV-SD Series User manual

power is supplied to the emergency driver.
2.This product is for use with an LED lighting load and supplies up to 7W / 12W / 25W constant power with output
voltage between 0 VDC and 0 VDC in emergency mode for a minimum of 90 minutes. 5 20
3.Make sure all connections are in accordance with the National Electrical Code or Canadian Electrical Code
and any local regulations.
converter connector of the emergency driver before servicing.
5.This emergency driver is for factory installation and .field Installation
6.This product is suitable for use in damp locations where the ambient temperature is 5ºC minimum, +50ºC
maximum. Product is not suitable for heated air outlets and wet or hazardous locations.
9.Use with grounded, UL Listed, damp location rated fixtures and
10.The Driver is intended for ordinary locations and for permanent
Contact the manufacturer for information on service.
12.The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition
16.Equipment should be mounted in locations and at heights where it
will not be subjected to tampering by unauthorized personnel.
Contains LiFePO4
Rechargeable Battery.
Must be recycled or
disposed of properly.
Page 1 of 4
STEP 1 INSTALLING THE EMERGENCY DRIVER
> Disconnect AC power from the LED luminaire.
>Mount the emergency LED driver by the mounting tabs using the supplied screws. The luminaire’s
installaion instructions may provide guidance on the recommended mounting location.
>
This product has been designed to reliably interface with a wide selection of LED loads.. However,
compatibility
cannot be guaranteed with all current
Installation of this emergency LED driver will vary based on the luminaire type, however, generally
follow these steps:
NOTE: After installation, it will be necessary to measure the egress lighting illumination levels to ensure it
complies with national, state, and local code requirements.
Page 2 of 4
Make sure the necessary branch circuit wiring is available. An unswitched
source of power is required. The emergency driver must be fed from the same
If used in conjunction with an AC driver, this distance is up to half the distance the AC driver manufacturer
recommends remote mounting the AC driver from the LED Load. If used without an AC driver, consult
installation into one or more Listed
11.
1.To prevent high voltage from being present on yellow & orange output leads prior to installation,
converter connector must be open. Do not join converter connector until installation is complete and AC
13.Do not use this product for other than intended use.
8.Do not install near gas or electric heaters,Do not use outdoors.
14.Servicing should be performed by qualified service personnel.
15.Only apply to LED Driver with the output current less than 3A.
branch circuit as
NOTE:
factory for remote mounting distances .
and future LED systems. Compatibility testing
of. the end-use system is suggested. Please contact the factory with any questions.
1. Ensure the LED load’s rated power is greater than or equal to the power output of this emergency LED
driver. This is to ensure that this emergency product will not produce more power than the LED load can
handle, thus ensuring that the LED load will not be damaged when the system is in the emergency mode.
is eligible for field installation.
2. Verify that the forward voltage of the luminaire’s LED array is within the limits of this emergency LED
voltage of the LED array is commonly designated as Vf and should be found on the
forward voltage is within the limits of this product. Using
voltage across the LED arrays when operating
driver. The forward
luminaire markings, in the luminaire
a voltage meter, it may be possible to directly measure the
from the AC driver.
3. Ensure the output current of the LED driver does not exceed 3Amps.This is the current into
doing the following:
be biven in lumens per watt (lm/w).
load. In many cases the actual lumen output in emergency mode will be greater than this
b.
calculation gives, however it will provide a good estimate for beginning the lighting design of the system.
C. Using the results of this calculation and industry standard lighting design tools, calculate the
a nticipated illumination levels in the path of egress.
Lumens In Emergency Mode = Lumens per Watt of Fixture * Output Power Emergency LED driver
________________
(Lumens) = (lm/W) * (W)
________________
case should be grounding.
3A max.
6W max. 50~200VDC 0.5A(@50Vdc) ~
0.125A(@200Vdc) 25W LiFePO4 battery
19.2V 3200mAH 90 Minutes 36 Feet
(11.0m)
120-277VAC
50/60Hz
OUTPUT
Input Voltage
Input Power
Output Voltage
Range
Output
Current
Output
Power
Battery Emergency
Operation
Max. mounting
height
INPUT
LED Driver
output current
120-277VAC
50/60Hz 3A max.
4W max. 50~200VDC 0.14A(@50Vdc) ~
0.035A(@200Vdc) 7W LiFePO4 battery
6.4V 3200mAH 90 Minutes 21 Feet
(6.4m)
3A max.
5W max. 50~200VDC 0.24A(@50Vdc) ~
0.06A(@200Vdc) 12W LiFePO4 battery
9.6V 3200mAH 90 Minutes 23 Feet
(7.0m)
120-277VAC
50/60Hz
(See electrical data table)
the blue wire.
emergency luminaires.
LED Emergency Conversion Power Pack
For Field or Factory Installation
LCPSD-HV / EMPHV-SD SERIES
NOTICE:
The LCP/EMP/LEDRV Series LED Emergency Driver Power Packs are rated for operation with an internal
pack ambient between 5°C to 50°C. To meet this rating, warranty condition and ensure optimum
component life, it is recommended that the pack be mounted remotely from the light fixture or high
ambient temperatures. Where it is necessary to mount directly to the light fixture, the installer
should verify that the stabilized light fixture surface temperature rise does not contribute radiant
heat directly to the pack surface; resulting in the pack internal ambient temperature exceeding the
max. 50°C rating. Locate or space the pack as necessary.
H3 Group Inc. 1-800-967 5541
Verify LED Luminaire Compatibility
Installation
LCPSD7HV
EMP7HV-SD
LCPSD12HV
EMP12HV-SD
LCPSD25HV
EMP25HV-SD
Do not attempt to service the battery. It is sealed unit and the battery is not replaceable.
The emergency driver with cable conduit is suitable for remote mounting from the luminaire;
the emergency driver without cable conduit is not suitable for remote mounting.
STEP 3 WIRING THE EMERGENCY BALLAST
> According wiring diagram to connect the emergency driver to the AC driver and LED load.
Make sure all connections are in accordance with the National Electrical Code and any local regulations.
> After installation is complete, supply AC power to the emergency driver and join the converter connector.
> At this point, power should be connected to both the AC driver and the emergency driver,and the Charging
Indicator Light should illuminate indicating the battery is charging.
Install and wire the test switch per wiring diagrams provided on these instructions.
indicating that the emergency inverter battery is charging.
STEP 2 INSTALLING TEST SWITCH
Mount the supplied illuminated test switch in a location that is visible and
accessible by maintenance personnel. The test switch mounts through a
0.49” hole which may need to be made in the luminaire or could come
pre-punched by the luminaire supplier.
Hex Nut
Illuminated
Test Switch
Fixture Plate
Drill or Punch
a 0.49” Hole
Page 3 of 4
A. Test switch install on switch box, switch box install on wall or ceiling surface.
TO TEST
CHARGE
> A short-term discharge test may be conducted after the emergency driver has been charged for one hour. Charge
for 24 hours before conducting a long-term discharge test. Refer to OPERATION.
> In a readily visible location, attach the label "CAUTION - This Unit Has More Than One Power Connection Point.
To Reduce The Risk Of Electric Shock, Disconnect Both The Branch Circuit-Breakers Or Fuses And Emergency
Power Supplies Before Servicing."
Page 4 of 4
Manual Operation
Auto Test Option
1. When AC power is supplied to fixture, the unit will automatically initiate a Auto test and self-diagnostic
test as follows:
(1) Verifies battery disconnection, charger board failure at every 5 seconds.
(2) 1 minute Auto testing every month.
(3) 30 minutes Auto testing on every 6 months after installation.
(4) 90 minutes Auto testing on every 12 months after installation.
2. Dual color LED lamp indicator shows the following status:
(1) Green color On / Ready
blinking: Testing
(2) Red color (Service Alert)
(3) Service Alert LED Code (Red color LED lamp indicator)
One blink, 4 second pause Battery is not connected
Two blinks, 4 second pause Battery voltage too low
Three blinks, 4 second pause
Four blinks, 4 second pause
Five blinks, 4 second pause LED load not connected or failure
NOTICE
After solving the fault of emergency equipment, please press test button for 2 seconds without
releasing to reset. LED indicator will show green.
3. AUTO test also have manual test function, press test button as follows:
Press test button once 30 seconds discharge test
Press test button twice within 2 seconds 3 minutes discharge test
Press test button 3 times within 2 seconds 30 minutes discharge test
Press test button 4 times within 2 seconds 90 minutes discharge test
Maintenance
> Mounting Height: This product meets or exceeds the NFPA minimum light requirements with all loads,
end use verification is necessary. For field installations, when the attached luminaire is mounted at
down to the smallest rated lamp load, at heights up to 7.17ft (2.2m). Many factors influence emergency
illumination levels, such as the lamp load selected, luminare design, and environmental factors therefore
heights greater than 7.17ft (2.2m), the level of illumination must be measured in the end application to
ensure the requirements of NFPA 101 and local codes are satisfied.
PUSH
NOTE: Switch box no provide.
ST: MT: Auto test Manual test
NOTE: Associated Target Luminaire : Jewoo CULPL66X-BC,Max. mounting height 21ft / 23ft / 36ft ,
Others luminaire suitable for used shall be selected according to the instruction suggestion.
(See electrical data table)
This emergency driver will operate an LED lighting load supplies
up to 7W / 12W / 25W constant power with output voltage between 50 VDC and 200 VDC in
emergency mode for minimum of 90 minutes.
(See electrical data table)
YELLOW
ORANGE
BLUE
LED LOAD
AC LED DRIVER
BLACK
WHITE
WHT/BLUE
WHT/RED
SWITCH
(OPTIONAL)
LIVE
NEUTRAL
DC+ DC-N L
WHT/BLK
WHT/BLK
RED
BLACK
TEST SWITCH
(double color LED)
CONVERTER
CONNECTOR
GREEN
BROWN
MT
+
-
ST
WIRING DIAGRAM FOR PARTED AC DRIVER AND LED MODULE
YELLOW
ORANGE
BLUE
AC LINEAR LED DRIVER
WITH LED LOAD
BLACK
WHITE
WHT/BLUE
WHT/RED
SWITCH
(OPTIONAL)
LIVE
NEUTRAL
N L
WIRING DIAGRAM FOR INTEGRAL AC DRIVER AND LED MODULE
WHT/BLK
WHT/BLK
RED
BLACK
TEST SWITCH
(double color LED)
CONVERTER
CONNECTOR
GREEN
BROWN
MT
ST
Maintenance
Transfer system failure
Charger board circuit failure

This manual suits for next models

3

Popular Power Pack manuals by other brands

Outwell AKIRA 600 instruction manual

Outwell

Outwell AKIRA 600 instruction manual

AMX WAV-LNK Dimensional drawing

AMX

AMX WAV-LNK Dimensional drawing

Chicago Pneumatic Hydraulic PAC P9 Safety and operating instructions

Chicago Pneumatic

Chicago Pneumatic Hydraulic PAC P9 Safety and operating instructions

Hilka 83-6060-12 operating instructions

Hilka

Hilka 83-6060-12 operating instructions

HYCON HPP09 operating manual

HYCON

HYCON HPP09 operating manual

EcoFlow Wave 2 user manual

EcoFlow

EcoFlow Wave 2 user manual

Intermatic IOS-PP24 Installation and configuration instructions

Intermatic

Intermatic IOS-PP24 Installation and configuration instructions

therm-ic Supermax Powerpack Instructions for use

therm-ic

therm-ic Supermax Powerpack Instructions for use

Pentax TR Power Pack-2 (PW-222 operating manual

Pentax

Pentax TR Power Pack-2 (PW-222 operating manual

Rockwood 30554 instructions

Rockwood

Rockwood 30554 instructions

AWILCO ES-500 owner's manual

AWILCO

AWILCO ES-500 owner's manual

Rescue 900 instructions

Rescue

Rescue 900 instructions

Camille Bauer SINEAX B 840 operating instructions

Camille Bauer

Camille Bauer SINEAX B 840 operating instructions

BRACKENHEATH BR1191 instructions

BRACKENHEATH

BRACKENHEATH BR1191 instructions

Hama Pipe 00137487 operating instructions

Hama

Hama Pipe 00137487 operating instructions

Broncolor Verso A2 rfs operating instructions

Broncolor

Broncolor Verso A2 rfs operating instructions

Cramer 40V110 Original instructions

Cramer

Cramer 40V110 Original instructions

Samsung SLB-1437 KIT user manual

Samsung

Samsung SLB-1437 KIT user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.