Sensor & Intelligent Control
REMOTE FOR DIMMABLE
SENSORS WITH MEMORY FUNCTION
ON/OFF Reset
1min
30s 3min
5min 20min
10min 30min
10%
30%
20% 50%
30s
10s 1min
5min 30min10min
+
-
50% 75% 100%
Detection Range
Hold Time
Stand-by period
Start Memory Apply
5s
0s
25%
Brightness
30Lux
10Lux
80Lux Disable
120Lux
Daylight sensor
2Lux
50Lux
Tes t
(2s)
Model: HD03R
Auto
Mode
Stand-by dimming level
1. "ON/OFF" key only functions as a switch of the light.
2. If press this button to turn off the lamp before it's short-circuited,
the lamp will remain off after power-on again.
+/-
Apply
Press "Start" to customize scene, users can change detection range,
daylight threshold, holdtime, standby dimming level and standby period.
1. Press "Memory" to save all the settings.
2. The settings remained as the last time if not get resetted values.
1. Press "Apply" to deliver the saved setting.
2. Press "Apply" without “memory”will make all the setting
one-time operation.
3. Settings should be done within 30S, otherwise it exits memory mode.
1. To adjust brightness 10-100% in on/off mode.
2. To adjust highest brightenss 60-100% in sensor mode.
ON/OFF
Reset
Auto
Mode
Start
Memory
Apply
+
-
Test
(2s)
Remote Keys Function Performance
Auto Mode
Reset
Start
ON/OFF
Memory
Detection area
Hold time
Stand-by period
Stand-by
dimming level
Test mode
Press “Auto Mode” button, the sensor starts to work and all settings
remain the same before the light gets switched on/off.
1.Press "Reset" button, change brightness to max level.
2.Press “Reset” button, products with DIP switch will be controlled by DIP
switches; otherwise all the setting will be just initial, that is 100% detection
range,hold time 5S, nostand-by time and daylight threshold disabled.
Detection area (Press to define detection area 100%/75%/50%/25%.)
Daylight Threshold
Hold time (Press to define holdtime 5s/30s/1min/3min/
5min/10min/20min/30min)
Stand-by dimming level (Press to define stand-by dimming
level 10%/20%/30%/50%.)
Stand-by period (Press to define stand-by period 0s/10s/
30s/1min/5min/10min/30min/+.)
Note: “0s” means no standby period; “+”
means unlimited standby period.
Daylight threshold (Press to define daylight level 2Lux/
10Lux/30Lux/50Lux/80Lux/120Lux/Disable.)
Note: Disable means light will be turned on once sensor
detects movement, regardless of the ambient lux.
The button “Test (2s)” is for testing purpose after commissioning. Pressing
this button, the sensor goes to test mode ( hold time is only 2s )