Haiwell HMI Series User manual

Xiamen Haiwell Technology Co., Ltd. www.haiwell.com
High-speed & HD HMI User Manual
IoT Cloud HMI User Manual
Human Machine Interface

www.haiwell.com Haiwell IoT Cloud HMI User Manual
2/28
Contents
Product Description
1. Product Introduction......................................................................................................................................................................................... 3
2. Product Specifications..................................................................................................................................................................................... 3
3. HMI Bundled software......................................................................................................................................................................................4
4. HMI interface diagram......................................................................................................................................................................................5
Software Instructions
1. HMI connection settings.................................................................................................................................................................................. 6
a. Notes and hardware installation steps................................................................................................................................................. 6
Notes............................................................................................................................................................................................. 6
Hardware installation steps........................................................................................................................................................ 6
b. Hardware wiring....................................................................................................................................................................................... 6
Devices connection with power................................................................................................................................................. 6
Devices connection..................................................................................................................................................................... 6
c. Network connection.................................................................................................................................................................................6
2. Project running.................................................................................................................................................................................................. 7
a. Select device models.............................................................................................................................................................................. 7
b. Download project..................................................................................................................................................................................... 8
c. Run project................................................................................................................................................................................................8
3. HMI manager.....................................................................................................................................................................................................8
a. Enter device manager interface............................................................................................................................................................ 8
Local manger................................................................................................................................................................................8
Could manager.............................................................................................................................................................................9
b. Excute device management.................................................................................................................................................................. 9
Download project......................................................................................................................................................................... 9
Upload project.............................................................................................................................................................................. 9
Offline update............................................................................................................................................................................. 10
Start calibration.......................................................................................................................................................................... 10
Update device-time................................................................................................................................................................... 10
Get the PN code........................................................................................................................................................................ 10
Check the device version......................................................................................................................................................... 10
Upload the history record......................................................................................................................................................... 11
Restart the device......................................................................................................................................................................12
4. Background settings....................................................................................................................................................................................... 13
a. Project Settings......................................................................................................................................................................................13
Connect Network Engineering.................................................................................................................................................13
Download project....................................................................................................................................................................... 13
b. Network Settings....................................................................................................................................................................................15
Ethernet connection.................................................................................................................................................................. 15
WIFI settings...............................................................................................................................................................................15
Personal Hotspot....................................................................................................................................................................... 17
Network configuration model................................................................................................................................................... 18
Routing configuration................................................................................................................................................................ 19
c. Settings....................................................................................................................................................................................................22
Settings....................................................................................................................................................................................... 22
Security settings.........................................................................................................................................................................23
Others..........................................................................................................................................................................................25
System Information................................................................................................................................................................... 26
Cloud settings.............................................................................................................................................................................27
Multi-language settings.............................................................................................................................................................28
Exit background settings.......................................................................................................................................................... 28

www.haiwell.com Haiwell IoT Cloud HMI User Manual
3/28
Product Description
1. Product Introduction
Main function
Haiwell HMI Embedded System is an embedded system software running in industrial automation monitoring and management
equipment. Through running Haiwell SCADA project, it can visually observe the situations of the industrial scene and
communicate with various industrial control equipment, by the collected production signals of industrial sites to achieve monitor.
The alarm information of the industrial site is promptly notified to the relevant staffs through the form of screen, computer
language, WeChat, SMS, and mail. Support the function of network project, so that multiple devices can be mutually client and
server, share data through the network to realize distributed control. Also support recording and storing data. Analyze and
record the real-time working condition data and historical working condition data to solve production failures, improve
production efficiency and product quality.
Haiwell HMI high-speed version is a new series of HMI launched by Haiwell Technology Co., Ltd. in 2019, based on the original
HMI system to improve the speed of the HMIS series, and on the basis of HMIS to optimize the definition of HD version HMIH
series.
Technical characteristics
Haiwell HMI embedded system is based on embedded Linux system development, integrated SVG image editing and
processing technology, TCP / IP network communication technology, serial communication technology, multi-threading,
multi-process, Javascript extended script analysis and running engine and other technologies for development.
2. Product Specifications
Specification
Model
C7S C7S-W C7S-G C7S-E
C7H C7H-W C7H-G C7H-E
C10S C10S-W C10S-G C10S-E
Display
Display
7〃TFT
7〃TFT
10.1〃TFT
Resolution
800x480pixels
1024x600pixels
1024x600pixels
Colors
16.7M
Brightness(cd/m²)
300
300
350
Contrast Ratio
800:01:00
800:01:00
500:01:00
Touch Type
Resistive Type
Backlight
Backlight Type
LED
Backlight Life Time
20,000 Hours
Automatic Dormancy
Support and Configurable
Software
Management software
Haiwell Cloud SCADA
Memory
Flash
4GB
RAM
512M
I/O Port
Micro SD Card Slot
Support
SIM Card
Support 4G network
Ethernet Port
10/100 Base-T
COM port
RS485/RS232
USB HOST
USB2.0 x 2
Print Port
COM Port/USB Print
Power
Input power
24±20%VDC
Power Consumption
7W
7W
10W
Power Isolation
Built-in
Voltage Resistance
500VAC
Isolation Resistance
Exceed 50MΩ @500VDC
Vibration Endurance
10 ~ 25 Hz (X, Y, Z direction 2G/30 minutes)
Environment
Cooling Type
Natural air Cooling
Protection Structure
IP65
Storage Temperature
-20 ~70℃
Operating Temperature
-10℃~ 60℃
Relative Humidity
10 ~ 90%RH (non-condensing)
Specification
Enclosure
Engineering Plastic ABS (Flame-retardant level)
Dimensions
200x146x37mm
200x146x37mm
270x212x35mm
Panel Cutout
193x138mm
193x138mm
260x202mm
Weight
0.8kg
0.8kg
1.3kg
Network
WiFi (Optional)
802.11b/g/n
Wireless (Optional)
4G/3G/2G

www.haiwell.com Haiwell IoT Cloud HMI User Manual
4/28
7" IOT Cloud HMI——High Speed
Model
TFT screen
Storage
LAN
USB
COM
WIFI
Wireless
Hole Size
Dimension W*H*D
C7S
7" 800*480
4G + 512M + SD
1
2
3
193x138
200x146x37mm
C7S-G
7" 800*480
4G + 512M + SD
1
2
2
4G/3G/2G
C7S-W
7" 800*480
4G + 512M + SD
1
2
3
Yes
C7S-GW
7" 800*480
4G + 512M + SD
1
2
2
Yes
4G/3G/2G
C7S-E
7" 800*480
4G + 512M + SD
1
2
2
Global4G/3G/2G
C7S-EW
7" 800*480
4G + 512M + SD
1
2
2
Yes
Global 4G/3G/2G
7" IOT Cloud HMI——HD
Model
TFT screen
Storage
LAN
USB
COM
WIFI
Wireless
Hole Size
Dimension W*H*D
C7H
7" 1024x600
4G + 512M + SD
1
2
3
193x138
200x146x37mm
C7H-G
7" 1024x600
4G + 512M + SD
1
2
2
4G/3G/2G
C7H-W
7" 1024x600
4G + 512M + SD
1
2
3
Yes
C7H-E
7" 1024x600
4G + 512M + SD
1
2
2
Global 4G/3G/2G
10.1" IOT Cloud HMI——High Speed
Model
TFT screen
Storage
LAN
USB
COM
WIFI
Wireless
Hole Size
Dimension W*H*D
C10S
10.1" 1024x600
4G + 512M + SD
1
2
3
260x202
270x212x35mm
C10S-G
10.1" 1024x600
4G + 512M + SD
1
2
2
4G/3G/2G
C10S-W
10.1" 1024x600
4G + 512M + SD
1
2
3
Yes
C10S-GW
10.1" 1024x600
4G + 512M + SD
1
2
2
Yes
4G/3G/2G
C10S-E
10.1" 1024x600
4G + 512M + SD
1
2
2
Global 4G/3G/2G
C10S-EW
10.1" 1024x600
4G + 512M + SD
1
2
2
Yes
Global 4G/3G/2G
3. HMI Bundled software
Haiwell HMI needs to be used with Haiwell SCADA editing software. Please download from download center of Haiwell
official website: www.haiwell.com.
Haiwell cloud service can be used by visiting Haiwell cloud website http://cloud.haiwell.com. It is also recommended to
download Haiwell Cloud APP.
Haiwell Cloud APP download:
Login and download from Haiwell Cloud website.
For iOS terminal, it can search and download "Haiwell Cloud"APP in Apple App Store.
Scan the QR code below to download.

www.haiwell.com Haiwell IoT Cloud HMI User Manual
5/28
4. HMI interface diagram
HMI- C7S/C10S/C7H HMI-C7S HMI-C10S HMI-C7H
Port diagram and pin definition:
C7S/C10S/C7H-S
COM3
RS232 RS485
Rxd Txd Gnd B- A+ USB
COM1
RS232 422 485 CAN LAN
24VDC
-+COM2
COM1 Pin definition
Pin
Definition
Pin
Definition
1
Carrier detect(DCD)
6
Data ready(DSR)
2
Receive data(RXD)
7
Request to send(RTS)
3
Transmit Data (TXD)
8
Clear to send(CTS)
4
Data terminal ready(DTR)
9
Ringing indicating(RI)
5
Signal ground(SG)
C7S-W/C10S-W/C7H-W
COM3
RS232 RS485
Rxd Txd Gnd B- A+ Wifi USB
COM1
RS232 422 485 CAN LAN
24VDC
-+COM2
COM1 Pin definition
Pin
Definition
Pin
Definition
1
Carrier detect(DCD)
6
Data ready(DSR)
2
Receive data(RXD)
7
Request to send(RTS)
3
Transmit Data (TXD)
8
Clear to send(CTS)
4
Data terminal ready(DTR)
9
Ringing indicating(RI)
5
Signal ground(SG)

www.haiwell.com Haiwell IoT Cloud HMI User Manual
6/28
C7S-G/C10S-G/C7H-G
COM1
RS232 RS485
Rxd Txd Gnd B- A+ USB
4G
SIM LAN
24VDC
-+COM2
C7S-GW/C10S-GW/C7H-GW
Software Instructions
1. HMI connection settings
Haiwell HMI communicates with the PLC through the 232 serial port, 485 serial port or Ethernet port. During the hardware wiring
process, the HMI C10 communicates with the PLC through the 232 serial port and connects to the static Ethernet network.
a. Notes and hardware installation steps
Notes
①The installation direction must be in accordance with the provisions of this manual, strictly in accordance with the direction of
the terminal wiring, otherwise it will cause product failure or burnout.
②The HMI and other components which are at the bottom must maintain sufficient space to avoid equipment damage caused
by poor heat dissipation
Hardware installation steps
Install the HMI into the cut-out panel and lock the four buckles on the side with the mounting panel.
b. Hardware wiring
Devices connection with power
HMI and PLC both connect with power.
Devices connection
HMI's COM-232 interface is connected to the PLC's 232 interface;
c. Network connection
Step 1: Long press the upper right corner of the HMI device to enter the background settings interface.
Step: 2: Click [Network] to enter the Ethernet settings interface;
Step 3: Open [Switch] for network;
Step 4: You can select [Static IP] or [DHCP] as needed. When the network type selects [Static IP], you need to set the network
parameters: enter the correct IP address, subnet mask, default gateway and DNS, click [Save] After the verification is passed,

www.haiwell.com Haiwell IoT Cloud HMI User Manual
7/28
the HMI device can connect to the network via Ethernet.
2. Project running
a. Select device models
Step 1: Open Haiwell SCADA software and set up a new project;
Step 2: Open [Project configuration] in the project browser, and click [Project properties] to enter the project property
configuration interface.
Step 3: Select the device model in the [Layout Info] field, which is consistent with the current device model. In this example,
HMI-10 is taken as an example. Select HMI-10 and click [OK].

www.haiwell.com Haiwell IoT Cloud HMI User Manual
8/28
b. Download project
Project Step 1: Enter the device manager, you can choose to use the local manager or cloud manager;
Step 2: Click [Download project] to enter the project download confirmation interface;
Step 3: In the confirmation download interface, you can choose whether to reserve the history and alarm records, whether to
reserve the formula and whether to package the font download. After the setting completed, click [OK];
Step 4: Wait for the pop-up prompt"Download successful!" and click [OK] to run the project on the device.
c. Run project
After the project successfully downloaded, wait for the HMI to restart, and after restart successfully, the HMI will automatically
open the project startup screen, and users can use the project as needed.
3. HMI manager
Open the scada software in computer, click the device manager icon of menu; or click the [project}, open the [HaiwellSacada]
installation document ,open the [Haiwell Device Manger] and enter device manager. Support to use the local manager and cloud
manager effective control HMI.
a. Enter device manager interface
Local manger
Enter device manager,click[local manager], set up IP address up on device and select device, click [mange] and enter currently
device manger, you can operate the current device as shown below

www.haiwell.com Haiwell IoT Cloud HMI User Manual
9/28
Could manager
Step 1: enter device manager, click [ cloud manager ], optional log in with mobile phone or email. PS: device administrator and
machine owner can manage current device through cloud manager, common user don’t have administrative authority.
Step 2: user input correct account and password, click [ sign in ] enter device manager, choice[ manage ]. enter current device
manager, can operating current device, the following diagram:
b. Excute device management
Download project
Step 1: click [ download project ], enter project download confirm;
Step 2: In the confirmation download interface can choose whether to keep the history and alarm records, whether to keep the
recipe, and whether to download the packaged fonts. After the setting are complete, click [OK];
Step 3: Wait for the pop-up prompt "Download successful!", click [OK], running the project in device.
Upload project
Step 1: click [ upload project ], choice the upload path and project name, click save;
Step 2: enter project upload and confirm interface, if project set up upload password, need to input the upload in [ project

www.haiwell.com Haiwell IoT Cloud HMI User Manual
10 /28
upload password]; if the project don’t have to set up the upload password, no pass word is required here;
Step 3: click [ upload ], wait for the pop-up prompt " upload successful!", click [OK], running the project of device in PC.
Offline update
Step 1: click [offline update],choice firm package, click [open], The latest firmware update package can be downloaded from
Haiwell official website http://en.haiwell.com/daruanjianen/HMI_Update_V2.17.1.5.hmi
Step 2: enter offline update confirm interface, click [update]
Step 3:waiting for update to complete, pop-up prompt " update success", click [OK].
Start calibration
Click [ start calibration ],the device enter the calibration interface, press the calibration mark 1above the screen for long
time, and enter next calibration site, calibration the device touch the screen in order of "left, right, up, down, mid"
Update device-time
Click [update device time], can to update system time of device. When update to complete, you can device-time, device -time
and system time of PC are same.
Get the PN code
Click [get PN code], can to view the current PN code of device.
Check the device version

www.haiwell.com Haiwell IoT Cloud HMI User Manual
11 /28
Click[check the device version], can to view the current version information of software and hardware of device.
Upload the history record
Click [ upload the history record],enter the upload interface of history record.
①split history file
Step 1: click [start split file], you can split historical files for the recent period of time.
Step 2: waiting split the historical record to complete, pop-up prompt [ split success], click [OK], historical file list will add current
split historical files.
②upload historical file

www.haiwell.com Haiwell IoT Cloud HMI User Manual
12 /28
Step 1: select historical file in historical file list, input historical file storage. Path, click [ upload select file ];
Step 2: waiting for upload the historical file to complete, pop-up prompt " upload the historical record success", click [OK].
When upload to complete, current historical file will remark "have uploaded".
③Delete history file
Step 1: Select the history file in the history file list and click [Delete Select File]
Step 2: Pop up the Confirm Delete File prompt box and click [Yes];
Step 3: Wait for the history file to be deleted successfully. The "Delete Successful!" prompt box will pop up, click [OK].
Restart the device
Step 1: Click [Restart Device], pop-up confirmation restart prompt box click [Yes];
Step 2: Wait for the device to restart. After the restart is successful, the "Device Restart Successful" prompt box is displayed,
and click [OK].

www.haiwell.com Haiwell IoT Cloud HMI User Manual
13 /28
4. Background settings
Long press the upper right corner of the HMI device to enter the background settings interface, or access the HMI through a
browser, enter IP / setting to enter the background settings interface
a. Project Settings
Connect Network Engineering
Enter the HMI-C10S background settings interface, click [Project], click [Connect Remote],enter the IP of the HMI in the LAN to
be connected to for remote access between HMIs
Download project
Step 1: Create a project, click [Project] in the Scada menu bar, expand the tab, and click [Generate U Disk or SD Card run file];

www.haiwell.com Haiwell IoT Cloud HMI User Manual
14 /28
Step 2: Enter the compilation interface, set the appropriate output path after compilation, click [Save];
Step 3: After the running file is saved successfully, the system will pop up a prompt box of saving successfully, click [OK].
Download project
U dist download project
Step 1: Enter the HMI-C10S background settings interface, click [Project] to enter the project settings interface;
Step 2: Click [Download Project] to enter the project download interface;
Step 3: Insert the U disk, select [USB]; select the project according to the requirements, click [OK]. and the hmi-c10s device will
automatically restart after the successful download.
SD card download project
Step 1: Enter the HMI-C10S background settings interface and click [Project];
Step 2: Enter the project settings interface, click [Download Project] to enter the project download interface;
Step 3: Insert the U disk, select [SD], select the project according to the requirements, click [OK]. and the hmi-c10s device will
automatically restart after the successful download.

www.haiwell.com Haiwell IoT Cloud HMI User Manual
15 /28
b. Network Settings
Ethernet connection
Enter the HMI-C10S background settings interface, click [Network], enter the Ethernet settings interface, open the [Switch], the
network type includes DHCP and Static IP.
①Dynamic IP
Connect the network cable, select [DHCP] for the network type, and click [Save], the device will automatically obtain the IP.
②Static IP
Connect the network cable, select [Static IP] for the network type, enter the correct IP address, subnet mask, default gateway,
and DNS, and click [Save]. After verification, the device can be connected to the network via Ethernet.
WIFI settings
Click [WIFI ] to enter the WIFI settings interface,which support connecting to the network via WIFI. Enter the WIFI settings
interface, turn on the WIFI switch, select the target WIFI account, enter the correct WIFI password, and connect to the WIFI
network after verification.

www.haiwell.com Haiwell IoT Cloud HMI User Manual
16 /28
After the connection is successful,display the green tick " ".
After the connection is successful, you can see the gray i "", click the gray i icon can set the IP address, subnet mask, default
gateway, DNS.
After setting, click [Save] to set WIFI IP address information.
Click the gray i icon and then click "Ignore wifi" to disconnect the WIFI connection. If you want to use the WIFI, you need to
re-enter the password to connect.

www.haiwell.com Haiwell IoT Cloud HMI User Manual
17 /28
Click the gray i icon and then click [Close] to close the window.
Personal Hotspot
Click [AP] to enter the personal hotspot interface, the HMI built-in network card can also be shared to share WIFI hotspots for
other users. Turn on the personal hotspot switch and set the hotspot name and password to share the WIFI hotspot for other
users.
Set the hotspot name, click "hotspot name", a hotspot name input box pops up.
Enter the hotspot name, click [Enter], and click [Save] to save the added hotspot name information.

www.haiwell.com Haiwell IoT Cloud HMI User Manual
18 /28
Set password, click "Password", a password input box pops up, click on the upper left corner of the input box to switch
the plaintext ciphertext of the password.
Enter the password, click [Enter], and click [Save] to save the added password information.
The factory default WIFI password is empty.
Note: The length of the hotspot name is 6 to 18 bits, and the password can be empty or set to 8 to 20 bits.when it exceeds the
range,the entered hotspot name and password will not be displayed in the corresponding location and a prompt will pop up.
Network configuration model
The new series of HMI has the following 4 different network configuration models (take C7S as an example).
Standard(HMIC7S)
The HMI standard version only has Ethernet and does not include WiFi / 4G / hotspot / routing modules,and the network onl
procide y by the network cable
With WiFi (HMIC7S-W)
HMI with WiFi version only includes Ethernet and WiFi, without 4G / hotspot / routing module, and the network is provided by
network cable / WiFi.
With 4G (HMIC7S-G)
The HMI with WiFi version includes Ethernet, 4G ,and routing modules, without WiFi / hotspots, and the network is provided
by the network cable / 4G.
The routing modes include: :close routing /4G client mode. The specific use of each routing mode will be explained below.
With 4G with WiFi (HMIC7S-GW)
The HMI with 4G and WiFi version includes Ethernet / WiFi / 4G / routing module, and the network is provided by Ethernet /
WiFi / 4G.

www.haiwell.com Haiwell IoT Cloud HMI User Manual
19 /28
The routing modes include:close routing / AP point mode / 4G routing mode / client mode / The repeate mode / 4G client
mode, the specific use of each routing mode will be described below.
Routing configuration
The routing modes include:close routing / AP point mode / 4G routing mode / The repeate mode / client mode/ 4G client mode,
the defaut is "Close routing"
Comparison of various routing modes and network types:
Close routing
(Routing switch)
AP MODE
4Grouting mode
Repeate mode
Client mode
4G client mode
Ethernet
LAN / Internet
LAN / Internet
LAN
LAN
unsupported
unsupported
WIFI
LAN / Internet
unsupported
unsupported
Connect to the Internet
Connect to the Internet
unsupported
Hotpot
LAN
LAN / Internet
LAN / Outer net
LAN / Internet
unsupported
unsupported
4G
Outer net
unsupported
Internet
unsupported
unsupported
Outer net
Network provided
Ethernet/WIFI/4G
Ethernet
4G
WIFI
WIFI
4G
Close routing mode
Enter the HMI background settings interface, click [Network], enter the route configuration interface, click "Settings", click
"Close routing", a prompt "This mode will will close the route, confirm the routing mode is closed" Click "OK", it is set to close
routing
"Close routing" mode, only turn off the Ethernet, WIFI, 4G routing function. The hotspots open in this mode only support LAN
networks, and do not support Internet access. The function settings of Ethernet, WIIF and 4G remain unchanged.

www.haiwell.com Haiwell IoT Cloud HMI User Manual
20 /28
AP mode
Enter the HMI background settings interface, click [Network], enter the routing configuration interface, click "Settings", click "AP
Mode", a prompt "This mode will turn off 4G and WIFI, are you sure to switch to this mode?", Click "OK" to set to wireless
access point mode.
In the "AP" mode, only the wired network provides the network, and Other devices can access LAN and internet by connecting
to the personal hotspot of the device.
4G routing mode
Enter the HMI background settings interface, click [Network], enter the routing configuration interface, click "Settings", click "4G
Routing Mode", a prompt "Will this turn off WIFI,confirm switching to this mode ?", click "ok" to set the 4G routing mode.
In "4G routing" mode, only 4G provides the network to the device, and other devices can connect to the local area network and
external network by connecting the personal hotspot of the device. The wired network in this mode only supports LAN
networks.
In the "4G routing" mode, only 4G provides the network to the device, and other devices can connect to the LAN and internet
through the personal hotspot of the device. Wired networks in this mode only support LAN networks.
This manual suits for next models
12
Table of contents
Popular Touch Panel manuals by other brands

Crestron
Crestron SmarTouch STX-1700CXP Operation guide

PAT
PAT DS 50 Operator's manual

Avalue Technology
Avalue Technology ASM-BYT Quick reference guide

Moxa Technologies
Moxa Technologies MPC-2150 Series user manual

Mitsubishi Electric
Mitsubishi Electric M800 Series manual

Winmate
Winmate R15IE3S-PTC3 user guide