Input
Thermocouple input K
RTD input Pt100 Ω
Input sampling cycle 500 ㎳
Input display resolution 1 ℃
Allowable
signal source resistance Thermocouple max. 100 Ω
Lead wire allowable resistance
RTD (max. 10 Ω. but the resistance among 3 lines should be same)
Performance
Display accuracy ±1 % of FS ±1 Digit
Control
functions
and
output
Control type Proportional control
Control operation Reverse action or direct action (by suffix code)
Setting range Same as range and input code
Proportional band 1 ~ 10 % of FS
Manual reset (MR) -50 ~ +50 % (Output amount)
Proportional period Approx. 20 sec (relay output)
Input disconnection detection
The output is OFF when the range is over 10 ℃
Control output Contact capacity: 1 C, 250 V a.c. 3 A (resisitive load)
Power voltage
※110 V a.c., 220 V a.c. 50/60 ㎐
Voltage fluctuation rate ±10 % of power voltage
Power consumption Max. 3 VA
Ambient temperature & humidity 0 ~ 50 ℃, 35 - 85 % RH (without condensation)
Storage temperature -25 ~ 65 ℃
Weight (g) 200
45.0+0.6
-0
45.0 +0.6
-0
60.0 60.0
44.0
100.0
14.0 14.072.0
INPUT
Pt
C
1 2 3
0 ~ 299 C
OUT
DF4
1 10
P.B
0
RST
48.0
48.0
■
■