Harrington Signal Network Plus 21 User manual

Network Plus 21
Access Terminal
Guide

Index
Operate Access Terminal . . . . . . . . . . . . . .III
Screen 0 Terminal Index . . . . . . . . . . . . . . 01
Screen 0 Terminal Index Priv. Level 2. . . . . . . 02
Screen 1 LCD . . . . . . . . . . . . . . . . . . . 03
Screen 2 Misc. Info . . . . . . . . . . . . . . . . 04
Screen 3 Battery. . . . . . . . . . . . . . . . . . 05
Screen 4 AC . . . . . . . . . . . . . . . . . . . . 06
Screen 5 Bell & Strobes . . . . . . . . . . . . . . 07
Screen 6 Function Relays . . . . . . . . . . . . . 08
Screen 7 Releasers . . . . . . . . . . . . . . . . 09
Screen 8 Municipal Relays . . . . . . . . . . . . . 10
Screen 9 Alarm List . . . . . . . . . . . . . . . . 11
Screen 9 Alarm List with detail . . . . . . . . . . 12
Screen 10 Miscellaneous Trouble. . . . . . . . . . . 13
Screen 10 Miscellaneous Trouble with details . . . . 14
Screen 11 OutPut Supervision.. . . . . . . . . . . . 15
Screen 12 Relay Summary . . . . . . . . . . . . . . 16
Screen 13 Archive . . . . . . . . . . . . . . . . . 17
Screen 14 Printer . . . . . . . . . . . . . . . . . 18
Screen 15 Printer Status . . . . . . . . . . . . . . 19
Screen 16 Network . . . . . . . . . . . . . . . . . 20
Screen 17 Port 1 . . . . . . . . . . . . . . . . . . 21
Screen 18 Port 2 . . . . . . . . . . . . . . . . . . 22
Screen 19 Port 3 . . . . . . . . . . . . . . . . . . 23
Screen 19 Port 3 with annunciators assigned. . . . . 24
Screen 21 Conventional Database . . . . . . . . . . 25
Screen 21 Conventional Database Fully Load.. . . . . 26
Screen 22 Conventional Analog . . . . . . . . . . . 27
Screen 22 Conventional Analog fully loaded.. . . . . 28
Screen 23 Conventional Details . . . . . . . . . . . 29
Screen 27 Miscellaneous Outputs. . . . . . . . . . . 30
Screen 29 System Reset . . . . . . . . . . . . . . . 31
Screen 29 System Reset Active. . . . . . . . . . . . 32
Screen 30 Port 9 Communicate with CoProcessors .. . 33
Screen 31 Addressable 1-8 . . . . . . . . . . . . . 34
Screen 32 Jumps to Screen 0 Index . . . . . . . . . .35
Screen 33 Addressable 17-24 . . . . . . . . . . . . 36
Screen 34 Control Modules . . . . . . . . . . . . . 37
Screen 35 Sensitivity . . . . . . . . . . . . . . . 38
Screen 36 Sensitivity List . . . . . . . . . . . . . 39
Screen 37 Bypass & Test . . . . . . . . . . . . . . 40
II

Screen 37 Bypass & Test in Test Mode . . . . . . . . 41
Screen 37 Bypass & Test in Bypass Mode . . . . . . . 42
Screen 38 Switches . . . . . . . . . . . . . . . . 43
Screen 49 Clock . . . . . . . . . . . . . . . . . . 44
Screen 50 Task. . . . . . . . . . . . . . . . . . . 45
Screen 51 FIFO . . . . . . . . . . . . . . . . . . 46
Screen 52 Extended Memory . . . . . . . . . . . . . 47
Screen 60 Annunciator. . . . . . . . . . . . . . . . 48
Screen 61 Local Annunciator. . . . . . . . . . . . . 49
Screen 61 Local annunciator Active . . . . . . . . . 50
Screen 68 Remote Terminal . . . . . . . . . . . . . 51
Screen 69 Network Verify . . . . . . . . . . . . . . 52
Co-processor Screens
Screen 0 Index 9-16 CoProccessor .. . . . . . . . . 53
Screen 2 Misc. Info. . . . . . . . . . . . . . . . 54
Screen 10 Misc. Trouble . . . . . . . . . . . . . . 55
Screen 15 Comlink . . . . . . . . . . . . . . . . . 56
Screen 19 Read Me . . . . . . . . . . . . . . . . . 57
Screen 20 Totals . . . . . . . . . . . . . . . . . 58
Screen 21 Detail . . . . . . . . . . . . . . . . . 59
Screen 22 Type On-line . . . . . . . . . . . . . . 60
Screen 23 Type Assigned . . . . . . . . . . . . . . 61
Screen 24 Errors . . . . . . . . . . . . . . . . . 62
Screen 25 Alarms . . . . . . . . . . . . . . . . . 63
Screen 26 Function . . . . . . . . . . . . . . . . 64
Screen 27 Modules . . . . . . . . . . . . . . . . 65
Screen 28 Bypass . . . . . . . . . . . . . . . . . . 66
Screen 29 Test Mode . . . . . . . . . . . . . . . . 67
Screen 30 Analog . . . . . . . . . . . . . . . . . . 68
Screen 50 Tasks . . . . . . . . . . . . . . . . . . 69
Screen 51 FIFO . . . . . . . . . . . . . . . . . . 70
III

NP21 Access Terminal Guide
01-28-02
Technical Service
1
Screen 0 Index
The number zero followed by (Tab) gets you into the INDEX SCREEN when you first go
to Access Terminal Window. This screen allows you to view the screen numbers and
commands you have accessibility to. The addressable Co-processor screens are not given
on this index screen. It has its Index screen.

NP21 Access Terminal Guide
01-28-02
Technical Service
2
Screen 0 Index
Index screen when in level 2.

NP21 Access Terminal Guide
01-28-02
Technical Service
3
Screen 1 LCD & Keypad
This screen lets the user, to view and control what is happening at the LCD display of the
FACP. By following the commands at the bottom of the screen, will give you full control
of the LCD Screens.

NP21 Access Terminal Guide
01-28-02
Technical Service
4
Screen 2 Miscellaneous. Information
This screen let the viewer see what operating system is in the FACP the version date, the
program date, the internal serial number, board models that are installed in the panel, how
disconnects are setup, disconnect timeout setup and passcode sequence number.

NP21 Access Terminal Guide
01-28-02
Technical Service
5
Screen 3 Battery
This screen lets the viewer see the display for the current battery level, the calibrated high
and low values and the current status of the battery and AC power. Also shows the timer
for the battery test.
When you are in passcode level 1 or higher it will show the commands of print
calibration, run fast test, run long test and calibrate.

NP21 Access Terminal Guide
01-28-02
Technical Service
6
Screen 4 AC Power
This screen lets the viewer see the current status of the AC power and the delay timer for
report a trouble for AC failure.

NP21 Access Terminal Guide
01-28-02
Technical Service
7
Screen 5 Bells & Strobes
This screen lets the viewer see the current status and settings of the output circuits and the
system setup for coded bells ect..

NP21 Access Terminal Guide
01-28-02
Technical Service
8
Screen 6 Function Relays
This screen lets the viewer see the current status and settings for the four function relays.

NP21 Access Terminal Guide
01-28-02
Technical Service
9
Screen 7 Releasers
This screen lets the viewer see the current status and settings for any releasing circuits
that maybe setup in the database,

NP21 Access Terminal Guide
01-28-02
Technical Service
10
Screen 8 Municipal Relays
This screen lets the viewer see the current status of the common system relays (Alarm,
Supervisory & Trouble). Also shows which relays maybe disconnected by the Municipal
Disconnect Hotkey button on the front of the panel.

NP21 Access Terminal Guide
01-28-02
Technical Service
11
Screen 9 Alarm List
This screen lets the viewer see the current alarm list on the system when they are active.
This is the same list that is displayed on the LCD menu. Each screen in the LCD display
corresponds to one line in the terminal screen. Up to 10 lines of events per page.
Commands:
J Page Down
0J Go to end of list
K page up
0K Go to beginning of list

NP21 Access Terminal Guide
01-28-02
Technical Service
12
Screen 9 Alarm List

NP21 Access Terminal Guide
01-28-02
Technical Service
13
Screen 10 Miscellaneous Troubles
This screen lets the viewer see the current list of all troubles currently displayed in the
STATUS/MISC. TROUBLES selection from the LCD display.

NP21 Access Terminal Guide
01-28-02
Technical Service
14
Screen 10 Miscellaneous Troubles

NP21 Access Terminal Guide
01-28-02
Technical Service
15
Screen 11 Output Supervisory
This screen lets the viewer see the current supervision readings and status for bells,
releasers and auxiliary power circuits. These values should be in the range of 130 to 150
for Vhi and 10 to 20 Vlo. If the numbers are jumping all over the place, there may be a
hardware fault with the panel.

NP21 Access Terminal Guide
01-28-02
Technical Service
16
Screen 12 Relay Summary
This screen lets the viewer see the current display of which function and relays have been
activated:
O = Outputs 1 thru 8
F = Function Relays 1 thru 4
A = Common Alarm Relay
S = Common Supervisory Relay
T = Common Trouble Relay
G = Ground Fault
W = Walk Test
L = LCD Back Light

NP21 Access Terminal Guide
01-28-02
Technical Service
17
Screen 13 Archive
This screen lets the viewer see the display of the Archive History List. This list can hold
approximately 1000 events, Alarms, Supervisory and Trouble. Events in Test Mode,
Non-Reporting and Network can be logged to the archive by programming at the panel in
passcode level 2 in the Archive screen.
Commands
J Page down
0J Go to end of list
KPage up
0K Go to beginning of list
Popular Fire Alarm manuals by other brands

Wheelock
Wheelock MT-12-LS installation instructions

Kidde
Kidde PE9UK manual

Honeywell
Honeywell ESSER 761694 Installation instructions manual

Simplex
Simplex 4001-9403 Installation and operating instructions

Notifier
Notifier NBG-12LA quick start guide

Hochiki
Hochiki FireNET FN-DAC Installation and operation manual

Numens
Numens 405 Series instruction manual

Advanced
Advanced MxPro5 5000 Series product manual

Honeywell
Honeywell SILENT KNIGHT SK-5208 Installation and operation manual

Kentec Electronics
Kentec Electronics Syncro Operation and maintenance manual

GST
GST C-9401 Installation and operation manual

Spectrex
Spectrex SharpEye 40/40 Duct Mount installation manual