Operating instructions
Additional languages www.stahl-ex.com
EN
C
S
&
Clifford & Snell
Flameproof Manual Call Points
Series MCP/PB

2Flameproof Manual Call Points
Series MCP/PB
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Contents
1 General Information ............................................................................................3
1.1 Manufacturer .......................................................................................................3
1.2 Information regarding the operating instructions .................................................3
1.3 Further documents ..............................................................................................3
1.4 Conformity with standards and regulations .........................................................3
2 Explanation of the symbols .................................................................................3
2.1 Symbols in these operating instructions .............................................................3
2.2 Warning notes .....................................................................................................4
2.3 Symbols on the device ........................................................................................4
3 Safety notes ........................................................................................................5
3.1 Operating instructions storage ............................................................................5
3.2 Safe use ..............................................................................................................5
3.3 Modifications and alterations ..............................................................................5
4 Function and device design ................................................................................5
4.1 Function ..............................................................................................................6
5 Technical data .....................................................................................................6
6 Transport and storage .........................................................................................7
7 Mounting and installation ....................................................................................8
7.1 Dimensions / fastening dimensions ....................................................................8
7.2 Mounting / dismounting, operating position ........................................................8
7.3 Installation ...........................................................................................................9
8 Commissioning .................................................................................................17
9 Operation ..........................................................................................................17
9.1 Troubleshooting ................................................................................................18
10 Maintenance and repair ....................................................................................18
10.1 Maintenance .....................................................................................................19
10.2 Repair ...............................................................................................................19
10.3 Returning the device .........................................................................................19
11 Cleaning ............................................................................................................20
12 Disposal ............................................................................................................20
13 Accessories and Spare parts ...........................................................................20

250306 / MCP60300050
2015-10-23·BA00·III·en·00
General Information
3
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Flameproof Manual Call Points
Series MCP/PB
1 General Information
1.1 Manufacturer
1.2 Information regarding the operating instructions
ID-No.: 250306 / MCP60300050
Publication Code: 2015-10-23·BA00·III·en·00
The original instructions are the English edition.
They are legally binding in all legal affairs.
1.3 Further documents
• Data sheet
For documents in further languages, see www.stahl-ex.com.
1.4 Conformity with standards and regulations
See certificates and EC Declaration of Conformity: www.stahl-ex.com.
The device has IECEx approval. See IECEx homepage: http://iecex.iec.ch/
2 Explanation of the symbols
2.1 Symbols in these operating instructions
R. STAHL Schaltgeräte GmbH
Business Unit Lighting & Signalling
Nordstr. 10
99427 Weimar
Germany
R. STAHL Schaltgeräte GmbH
Am Bahnhof 30
74638 Waldenburg
Germany
Phone:
Fax:
Internet:
E-mail:
+49 3643 4324
+49 3643 4221-76
www.stahl-ex.com
Phone:
Fax:
Internet:
E-mail:
+49 7942 943-0
+49 7942 943-4333
www.stahl-ex.com
Symbol Meaning
Tips and recommendations on the use of the device
General danger
Danger due to explosive atmosphere
Danger due to energised parts

Explanation of the symbols
4250306 / MCP60300050
2015-10-23·BA00·III·en·00
Flameproof Manual Call Points
Series MCP/PB
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
2.2 Warning notes
Warnings must be observed under all circumstances, in order to minimize the risk
due to construction and operation. The warning notes have the following structure:
• Signalling word: DANGER, WARNING, CAUTION, NOTICE
• Type and source of danger/damage
• Consequences of danger
• Taking countermeasures to avoid the danger or damage
2.3 Symbols on the device
DANGER
Danger to persons
Non-compliance with the instruction results in severe or fatal injuries
to persons.
WARNING
Danger to persons
Non-compliance with the instruction can result in severe or fatal injuries
to persons.
CAUTION
Danger to persons
Non-compliance with the instruction can result in light injuries to persons.
NOTICE
Avoiding material damage
Non-compliance with the instruction can result in material damage to the device and / or
its environment.
Symbol Meaning
05594E00
CE marking according to the current applicable directive.
02198E00
According to marking, device certified for hazardous areas.
15649E00
Input
15648E00
Output

250306 / MCP60300050
2015-10-23·BA00·III·en·00
Safety notes
5
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Flameproof Manual Call Points
Series MCP/PB
3 Safety notes
3.1 Operating instructions storage
• Read the operating instructions carefully.
• Store the operating instructions at the mounting location of the device.
• Observe applicable documents and operating instructions of the devices to
be connected.
3.2 Safe use
• Read and observe the safety notes in these operating instructions!
• Observe characteristic values and rated operating conditions on the rating and
data plates!
• Observe additional information plates on the device!
• Use the device in accordance with its intended and approved purpose only!
• We cannot be held liable for damage caused by incorrect or unauthorized use
or by non-compliance with these operating instructions.
• Before installation and commissioning, make sure that the device is not damaged!
• Work on the device (installation, maintenance, overhaul, repair) may only be
carried out by appropriately authorized and trained personnel.
3.3 Modifications and alterations
4 Function and device design
DANGER
Explosion hazard due to modifications and alterations to the device!
Non-compliance results in severe or fatal injuries.
• Do not modify or alter the device.
No liability or warranty for damage resulting from modifications and
alterations.
DANGER
Explosion hazard due to improper use!
Non-compliance results in severe or fatal injuries.
• Use the device only in accordance with the operating conditions
described in these operating instructions.
• Use the device only for the intended purpose specified in these
operating instructions.

Technical data
6250306 / MCP60300050
2015-10-23·BA00·III·en·00
Flameproof Manual Call Points
Series MCP/PB
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
4.1 Function
Application range
The MCP/PB is a double action safety switch. The device is certified for use in hazardous
areas of Zones 1 and 2 (gas) and 21 and 22 (dust). The device is suitable for gas group
IIC and dust group IIIC. It can also be used in harsh environments.
Mode of operation
The switch is protected by a cover. It is activated via a pushbutton and reset using the
supplied tool. The device can be supplied with a number of options and accessories.
5 Technical data
Explosion Protection
Global (IECEx)
Gas and dust IECEx BAS 08.0089X
IEC 60079-0: 2011 / IEC 60079-1: 2007-04 / IEC 60079-31: 2008
Ex d IIC T6 Ta -55 to +70 °C Gb
Ex tb IIIC T85°C Ta -55 to +70 °C Db IP66
Europe (ATEX)
Gas and dust Baseefa 08ATEX0269X
EN 60079-0: 2009 / EN 60079-1: 2007 / EN 60079-31: 2009
E II 2 G Ex d IIC T6 Ta -55 to +70 °C Gb
E II 2 D Ex tb IIIC T85°C Ta -55 to +70 °C Db IP66
Certifications and certificates
Certificates IECEx, ATEX, Brazil (INMETRO), India (PESO)
Technical Data
Electrical data
Rated operational
voltage
12 to 50 V DC, 12 to 250 V AC
Switching capacity
Contact element standard: 1 change-over contact
optional: 2 change-over contacts
Switch NO or NC
System test Test key provided
Ambient conditions
Operating
temperature range
-40 to +70 °C
DC 12 to 30 V 3 A
30 to 50 V 1 A
AC 12 to 250 V 5 A

250306 / MCP60300050
2015-10-23·BA00·III·en·00
Transport and storage
7
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Flameproof Manual Call Points
Series MCP/PB
For further technical data, see www.stahl-ex.com.
6 Transport and storage
• Transport and store the device only in the original packaging.
• Store the device in a dry place (no condensation) and vibration-free.
• Do not drop the device.
Mechanical data
Material
Enclosure material glass fibre reinforced polyester (GRP)
Surface finish two pack, acrylic polyurethane, various colour options
Degree of protection IP66 acc. to IEC 60529
Cable entries 4 cable entries, supplied with (3x) Ex d stopping plugs and (1x) dust cap
Position of
cable entries
Connection
Terminals 7 way terminal block., 4 mm2
Earth connection provided as standard
Accessories
LED status
indication
optional: red LED status indication(up to 24 V DC)
Lift flap stainless steel (break glass version only)
Duty label Metalised polyester, customer to specify wording / symbols (see main picture
for example)
Tag label Stainless steel tag with polyester label, customer to specify max 9 characters
Resistors Customer to specify value
Mounting / Installation
Assembly via holes through the back box.
see operating instruction for full details
Technical Data
13952E00 16555E00 13951E00
Break glass call point Break glass call point
with lift flap
Push button call point

Mounting and installation
8250306 / MCP60300050
2015-10-23·BA00·III·en·00
Flameproof Manual Call Points
Series MCP/PB
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
7 Mounting and installation
The device is approved for use in gas explosion hazardous areas of Zones 1 and 2
and dust explosion hazardous area of Zones 21 and 22 and in safe areas.
7.1 Dimensions / fastening dimensions
7.2 Mounting / dismounting, operating position
DANGER
Explosion hazard due to incorrect installation of the device!
Non-compliance results in severe or fatal injuries.
• Carry out installation strictly according to the instructions and national
safety and accident prevention regulations to maintain the explosion
protection.
• Select and install the electrical device so that explosion protection is not
affected due to external influences, i.e. pressure conditions, chemical,
mechanical, thermal and electric impact such as vibration, humidity and
corrosion (see IEC/EN 60079-14).
• The device must only be installed by trained qualified personnel who
is familiar with the relevant standards.
Dimensional drawings (all dimensions in mm [inches]) – subject to alterations
13954E00
MCP/PB
DANGER
Explosion hazard due to improper mounting!
Non-compliance can result in severe or fatal injuries.
• Only mount the device on walls or a suitable surface.
• Fit the core sleeves gas-tight and only using a suitable tool.
• Carefully remove or replace the components.
• Carefully protect exposed joint surfaces from damage, dust and dirt.
• Install end flange without applying force (without hammer and tool)
in straight alignment.
39
[1,54]
[1,07 ± 0,004]
78 [3,07]
27,24 ± 0,1
11,24 ± 0,1
[0,44 ± 0,004]
107,50 ± 0,1
[4,23 ± 0,004]
74 [2,91]
Ø 5,50
[Ø 0,22]
132,50 [5,22]
132,50 [5,22]
98 3 86[, ]

250306 / MCP60300050
2015-10-23·BA00·III·en·00
Mounting and installation
9
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Flameproof Manual Call Points
Series MCP/PB
7.3 Installation
7.3.1 Preparation for electrical installation
Remove the cover
• Remove cheese-head screws.
• Carefully lift MCP front cover.
DANGER
Explosion hazard due to open holes, unused cable entries and cable glands!
Non-compliance can result in severe or fatal injuries.
• Only use approved and flameproof (Ex d) cable glands.
• When selecting cable entries, observe the thread type and thread size
in the component documentation.
• Seal thread with non-hardening thread sealant.
• Always close unused holes, cable entries and cable glands using
approved stopping plugs or plugs. Observe IEC/EN 60079-14 for this.
CAUTION
Danger of electric shock due to energised parts!
Non-compliance can result in minor injuries!
• All connections must be disconnected from the power supply.
• Secure the connections against unauthorized switching.
• Correct reassembly of the unit is required to ensure ingress protection
to IP 66.
16579E00
1 Cheese-head screws
M5 x 16
2 MCP front cover
3 PCB fixing screw
4PCB
5MCP base
A retaining strap is fitted between the base and front cover.
Depending on the variant of MCP which has been selected, the PCB may
or may not have to be removed during installation.
Details about this can be found in the "Electrical connection" chapter.
54321

Mounting and installation
10 250306 / MCP60300050
2015-10-23·BA00·III·en·00
Flameproof Manual Call Points
Series MCP/PB
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Replace the components and close the cover
• If necessary, replace PCB and screws.
• Replace front cover without pinching the retaining strap.
• Tighten cheese-head screws with a torque of 6.25 Nm.
7.3.2 Electrical Connection
Key Components
7.3.3 Circuit diagrams
7.3.4 Standard devices
Single-pin MCP, switch normally open in standby / normally closed in alarm
• Make sure that the LK2 connection has been removed.
Single pin MCP, switch normally closed in standby / normally open in alarm
• Make sure that the LK2 connection has been removed.
16840E00
1 Cable connection (from right)
2 3 fixing points for PCBs
3 Breakable tabs for independent
switch function
4 Terminal block
5 Connector for switch
6 LK1, LK2 and LK3 connections
for special variants
• MCP switch can be operated normally open or normally closed to
suit different systems.
• The device can be purchased with a single or two-pin switch.
• Two-pin switch can be used as standard or to switch independent
circuits.
• An LED indication light is available as an optional extra.
• Standard wiring configurations are listed below. If further information
is required please contact your local sales office.
16841E00
1 Cable connection (from right)
2 N / -
3 L / +
16842E00
1 Cable connection (from right)
2 N / -
3 L / +
LK2
LK1
TB1
LK3
1
Common
N/O
N/C
6
3
5
4
2
LK1
TB1
LK3
1
Common
N/O
N/C
3
2
LK1
TB1
LK3
1
Common
N/O
N/C
3
2

250306 / MCP60300050
2015-10-23·BA00·III·en·00
Mounting and installation
11
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Flameproof Manual Call Points
Series MCP/PB
Two-pin MCP, switch normally open in standby / normally closed in alarm
(independent circuits)
• Unscrew PCB, lift it and break tabs.
• Make sure that the LK2 connection has been removed.
Two-pin MCP, switch normally closed in standby / open in alarm (independent circuits)
• Unscrew PCB, lift it and break tabs.
• Make sure that the LK2 connection has been removed.
7.3.5 Standard devices with monitoring resistors
Single pin MCP, switch normally closed in standby / normally open in alarm
16843E00
1 Cable connection (from right)
2 N / - pin 1
3 N / - pin 2
4 L / + pin 1
5 L / + pin 2
16844E00
1 Cable connection (from right)
2 N / - pin 1
3 N / - pin 2
4 L / + pin 1
5 L / + pin 2
• Standard variants with monitoring resistors are only available with
switch normally closed in standby / normally open in alarm.
• Resistor values are to be selected by the system designer, depending
on requirements.
• The PCB is 0 ohms resistance.
• For 24 V DC systems, a minimum resistor value of 470 ohms should
be used.
17544E00
Normal / Standby
1 Switch closed – End-of-line resistor
active
2 L / +
3 N / -
LK1
TB1
LK3
1
Common
N/O
N/C
2
3
4
5
LK1
TB1
LK3
1
Common
N/O
N/C
2
3
4
5
2
1
2
3
4
5
3
1
R1
6
7
R2

Mounting and installation
12 250306 / MCP60300050
2015-10-23·BA00·III·en·00
Flameproof Manual Call Points
Series MCP/PB
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
• Make sure that the LK2 connection has been removed.
• In-line resistor between positions 2 & 6 – R2.
• End-of-line resistor between positions 3 & 4 – R1.
7.3.6 Standard devices with LED status light
Single-pin MCP, switch normally open in standby / normally closed in alarm
• Ensure that connector wires from switch and LED are correctly installed as per
the diagram (see following figure).
17545E00
Active / Alarm
1 Switch open – In-line resistor
engaged
2 L / +
3 N / -
There is an 820 ohm resistor which is in-line with the LED. When activated,
the LED together with the resistor will draw a current. On a 24 V DC,
system this current is approximately 30 mA.
17567E00
17568E00
C
1
1a
2
3
4
Connector block
Red wire for LED
Black wire for LED
Yellow wire for switch
Blue wire for switch
Red wire for switch
17538E00
1
2
3
Cable connection (from right)
N / -
L / +
2
1
2
3
4
5
3
1
R1
6
7
R2
1a
2a
3a
4a
1
2
3
4
C
2
3
4
1
1a
C
LK1
TB1
LK3
1
Common
N/O
N/C
3
2
Lk2

250306 / MCP60300050
2015-10-23·BA00·III·en·00
Mounting and installation
13
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Flameproof Manual Call Points
Series MCP/PB
• Remove LK1 for LED activation in alarm or remove LK2 for LED activation in standby.
• Jumper/connection between terminal 1 and 2.
Single pin MCP, switch normally closed in standby / normally open in alarm
• Ensure that connector wires from switch and LED are correctly installed as per
the diagram (see following figure).
• Remove LK1 for LED activation in alarm or remove LK2 for LED activation in standby.
• Jumper/connection between terminal 1 and 2.
Two-pin MCP, switch normally open in standby / normally closed in alarm
(independent circuits)
• Ensure that connector wires from switch and LED are correctly installed as per
the diagram (see following figure).
17567E00
17568E00
C
1
1a
2
3
4
Connector block
Red wire for LED
Black wire for LED
Yellow wire for switch
Blue wire for switch
Red wire for switch
17539E00
1
2
3
Cable connection (from right)
N / -
L / +
17567E00
1a
2a
3a
4a
1
2
3
4
C
2
3
4
1
1a
C
LK1
TB1
LK3
1
Common
N/O
N/C
3
2
Lk2
1a
2a
3a
4a
1
2
3
4
C

Mounting and installation
14 250306 / MCP60300050
2015-10-23·BA00·III·en·00
Flameproof Manual Call Points
Series MCP/PB
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
• Remove LK1 for LED activation in alarm or remove LK2 for LED activation in standby.
• Jumper/connection between terminal 1 and 2.
Two-pin MCP, switch normally closed in standby / open in alarm (independent circuits)
• Ensure that connector wires from switch and LED are correctly installed as per
the diagram (see following figure).
17570E00
C
1
1a
2
2a
3
3a
4
4a
Connector block
Red wire for LED
Black wire for LED
Yellow wire for switch
Yellow wire for second switch
Blue wire for switch
Blue wire for second switch
Red wire for switch
Red wire for second switch
17540E00
1
2
3
4
5
Cable connection (from right)
N / -
N / -
L / +
L / +
17567E00
17570E00
C
1
1a
2
2a
3
3a
4
4a
Connector block
Red wire for LED
Black wire for LED
Yellow wire for switch
Yellow wire for second switch
Blue wire for switch
Blue wire for second switch
Red wire for switch
Red wire for second switch
17541E00
1
2
3
4
5
Cable connection (from right)
N / -
N / -
L / +
L / +
2a
3a
4a
1
1a
C
2
3
4
LK1
TB1
LK3
1
Common
N/O
N/C
2
3
4
5
Lk2
1a
2a
3a
4a
1
2
3
4
C
2a
3a
4a
1
1a
C
2
3
4
LK1
TB1
LK3
1
Common
N/O
N/C
2
3
4
5
Lk2

250306 / MCP60300050
2015-10-23·BA00·III·en·00
Mounting and installation
15
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Flameproof Manual Call Points
Series MCP/PB
• Remove LK1 for LED activation in alarm or remove LK2 for LED activation in standby.
• Jumper/connection between terminal 1 and 2.
7.3.7 Standard devices with monitoring resistors and LED status light
Single pin MCP, switch normally closed in standby / normally open in alarm
• Ensure that connector wires from switch and LED are correctly installed as per
the diagram (see following figure).
• Standard variants with monitoring are only available with switch
normally closed in standby / normally open in alarm with LED activated.
• There is an 820 ohm resistor which is in-line with the LED.
When activated, the LED together with the resistor will draw a current.
On a 24 V DC system, this current is approximately 30 mA.
• In standby without the LED activated, the resistance of the the PCB
is 0 ohms.
• Resistor values are to be selected by the system designer,
depending on requirements of the system.
• For 24 V DC systems, a minimum resistor value of 470 ohms should
be used.
17567E00
17569E00
C
1
1a
2
3
4
4a
Connector block
Red wire for LED
Black wire for LED
Yellow wire for switch
Blue wire for switch
Red wire for switch
Red wire for LED
17546E00
Normal / Standby
1 Switch closed – end-of-line resistor
engaged
2 L / +
3 N / -
1a
2a
3a
4a
1
2
3
4
C
2
3
4
4a
1a
C
2
1
2
3
4
5
3
1
R1
6
7
R2

Commissioning
16 250306 / MCP60300050
2015-10-23·BA00·III·en·00
Flameproof Manual Call Points
Series MCP/PB
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
• Make sure that the LK2 connection has been removed.
• In-line resistor between positions 1 & 6 – R2.
• End-of-line resistor between positions 3 & 4 – R1.
7.3.8 Earth connection
16580E00
8 Commissioning
Before commissioning, ensure the following:
• Check the mounting and installation.
• Enclosure must not be damaged.
• If necessary, remove foreign bodies.
• If necessary, clean the connection chamber.
• Check if the conductors have been inserted correctly.
• Check if all screws and nuts have been tightened firmly.
• Check if all conductors have been clamped firmly.
• Check if all prescribed tightening torques have been observed.
• Check whether the bayonet lock is tightened firmly.
• Make sure that the plug pin surface is not damaged.
• Use only in completely mounted state.
17547E00
Active / Alarm
1 Switch open – in-line resistor
engaged
2 L / +
3 N / -
DANGER
Explosion hazard due to incorrect installation!
Non-compliance results in severe or fatal injuries.
• Check the device for proper installation before commissioning.
• Comply with national regulations.
2
1
2
3
4
5
3
1
R1
6
7
R2

250306 / MCP60300050
2015-10-23·BA00·III·en·00
Operation
17
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Flameproof Manual Call Points
Series MCP/PB
9 Operation
Test and reset procedure
16581E00
Activate function:
• Open the cover.
16582E00
• Press the pushbutton.
• The pushbutton engages and
the contact is actuated.
16583E00
Reset manual signaling device:
• Put the key onto the button.
16584E00
• Rotate the key 90° to the left or right.
16585E00
• Remove the button.

Maintenance and repair
18 250306 / MCP60300050
2015-10-23·BA00·III·en·00
Flameproof Manual Call Points
Series MCP/PB
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
9.1 Troubleshooting
If the error cannot be eliminated using the mentioned procedures:
• Contact R. STAHL Schaltgeräte GmbH.
For fast processing, have the following information ready:
• Type and serial number of the device
• Purchase information
• Error description
• Intended use (in particular input / output wiring)
10 Maintenance and repair
10.1 Maintenance
• Determine the type and extent of inspections in compliance with the relevant national
regulations.
• Adapt inspection intervals to the operating conditions.
The following tests and measures must be carried out during regular maintenance.
CAUTION
Risk of electric shock or malfunction of the device due to unauthorized work!
Non-compliance can result in light injuries!
• Before carrying out work on the device, switch off voltage supply.
• Work performed on the device must only be carried out by authorized
and appropriately trained qualified electricians.
Observe the relevant national regulations in the country of use.
Check Measures
the permissible ambient temperature If exceeding the permissible ambient
temperature or falling below the device
must be taken out of operation.
the enclosure components for formation
of cracks and damage.
Replace the exchangeable enclosure
components. If the enclosure components
are non-exchangeable, the device must be
taken out of operation.
its intended use If the device is not used according to its
intended use, it must be taken out of
operation.
if the conductors are clamped properly clamp loose conductors tightly.
the cables for ageing and damage replace damaged or aged cables.
the seals for ageing and damage replace damaged, aged and porous seals
and completely change enclosure
components with foamed seal.

250306 / MCP60300050
2015-10-23·BA00·III·en·00
Cleaning
19
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Flameproof Manual Call Points
Series MCP/PB
10.2 Repair
10.3 Returning the device
Use the "Service form" to return the device if repair or service is required.
On the internet site "www.stahl-ex.com" under "Downloads > Customer service":
• Download the service form.
• Fill out the service form.
• Send the device along with the service form in the original packaging to
R. STAHL Schaltgeräte GmbH.
11 Cleaning
• Clean the device only with a cloth, brush, vacuum cleaner or similar items.
• When cleaning with a damp cloth, use water or mild, non-abrasive, non-scratching
cleaning agents.
• Do not use aggressive detergents or solvents.
12 Disposal
• Observe national and local regulations and statutory regulation regarding disposal.
• Separate materials when sending it for recycling.
• Ensure environmentally friendly disposal of all components according to the statutory
regulations.
13 Accessories and Spare parts
DANGER
Explosion hazard due to improper repair!
Non-compliance results in severe or fatal injuries.
• Repair work on the devices must be performed only by
R. STAHL Schaltgeräte GmbH.
NOTE
Malfunction or damage to the device due to the use of non-original components.
Non-compliance can result in material damage.
• Use only original accessories and spare parts from R. STAHL Schaltgeräte GmbH.
For accessories and spare parts, see data sheet on our homepage
www.stahl-ex.com.

Table of contents
Other Stahl Fire Alarm manuals
Popular Fire Alarm manuals by other brands

Global Fire
Global Fire JUNO NET installation manual

Fireboy- Xintex
Fireboy- Xintex FR-1000 installation manual

Bosch
Bosch FAP-O 500 Series Product information

Honeywell
Honeywell C7076A instruction sheet

Gamewell
Gamewell Flex 4 Installation and operation manual

FireClass
FireClass DUO-CEL Application guide